Permit Number: DP12-0237
Parcel: 113081060

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP12-0237
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2013 AROMERO4 START PLANS SUBMITTED Completed
07/23/2013 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Blacklidge Development, Units 1 -13 - 1218 E. Blacklidge Drive.
Development Package (2nd Review)
DP12-0237

TRANSMITTAL DATE: July 24, 2013

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

The following comments are based on Development Standard 2-01.0:

1. D.S. 2-01.3.9.H Keynote two calls out 6" vertical curb. There is a call out for Keynote 2 at the driveway for unit 4, it appears that this is incorrect.

2. D.S. 2-01.3.9.O As no building height was provided within the footprint of the buildings as required and the "BUILDING HEIGHT SECTION" was removed from sheet 3, the required perimeter yard setbacks cannot be verified. Provide the building height within the footprint.

3. Once the above comments have been addressed Zoning is willing to do an over-the-counter review. Call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov.

Sshield1 on DS1/planning/New Development Package/ DP12-0237

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
08/07/2013 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change 1. Interior Landscape Borders are required along site boundaries of multifamily land uses adjacent to residential zoned properties LUC 3.7.2-I.

2. One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border per LUC 3.7.2.4.

3. Identify on the landscape plan 5' wall to screen adjacent residential zoned property to the south from vehicle use area LUC 3.7.2-I.

4. Ensure that all the Zoning and Engineering comments are addressed and all the appropriate revisions are made to the site, grading and landscape plans.

5. Additional comments may apply.
08/08/2013 RONALD BROWN ZONING HC REVIEW Denied Please provide a large scale detail of the west end of the marked crossing showing where the 1:12 ramp starts and ends and define the landings plus all dimensional widths.
END OF REVIEW
08/15/2013 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied This review has been completed and resubmittal is required.

Please resubmit the following items:

1) Two rolled sets of the plans
2) All items requested by review staff
3) All items needed to approve these plans
08/15/2013 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 08/15/2013,

SUBJECT: Blacklidge Development, Units 1-13
DP12-0237, T13S, R14E, SECTION 31

RECEIVED: Development Package on July 22, 2013

The subject submittal has been reviewed and it can not be approved at this time. Address the following comments before review can continue. Prepare a detailed response that explains the revisions that were made and references the exact location in the drainage report and on the Development Package where the revisions were made:

Drainage Report:

1. Provide a drainage exhibit that delineates the regulatory floodplain and demonstrates its impact on the subject parcel. Provide the 100-year water surface elevations upstream of every proposed building to justify the proposed finished floor elevations.
2. Determine the proposed building finished floor elevations based on the 100-year water surface elevations.

BASE LAYER SHEET COMMENTS:

1. Show on the plan, graphically and by notes, the impact of the regulatory floodplain on the entire parcel. Provide a note, which states that the proposed buildings finished floor elevations shall be at least one foot above the flood elevation (D.S. 2-01.3.9.N.6).

Permitting/General Notes:

1. Revise Drainage Note #18 to specify that the entire parcel is impacted by Mountain Avenue Wash 100-year floodplain.
2. Revise Drainage Note #15 to specify that the project is required to have a floodplain use permit for the grading and the construction of the infrastructure and a floodplain use permit for every individual building. Additionally, every building will have its own elevation certificate which will be based on the finished floor elevation of the lowest unit.

Site Plan:

2. It appears that Keynote #2 call out, near building 4, is pointing to the wrong location. Revise.

Grading Plan:

1. Since the entire parcel is impacted by the regulatory floodplain, provide 100-year water surface elevations across the proposed buildings, based on the JE Fuller study, to justify the proposed finished floor elevations. (D.S. 2-01.3.9.N.6).
2. The PAAL width should be measured from the gutter line; not from the top of curbs. Clarify this requirement on the appropriate details graphically and with notes.

If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov


RESUBMITTAL REQUIRED: Revised Development Plan Package and drainage report

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2013 SHANAE POWELL OUT TO CUSTOMER Completed
09/26/2013 CPIERCE1 REJECT SHELF Completed