Permit Number: DP12-0236
Parcel: 101211310

Review Status: Completed

Review Details: GRADING

Permit Number - DP12-0236
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2013 ELIZABETH EBERBACH ENGINEERING REVIEW Denied TO: Peter Livingston, P.E.
SUBJECT: 5141 N Gracious Ct Grading Plan Review
LOCATION: Gracious Estates S05-051 - lot 7
REVIEWER: Elizabeth Leibold P.E.
ACTIVITY NUMBER: DP12-0236

Summary: Engineering Division has reviewed the submitted development package including a copy of the grading plan. Engineering does not recommend approval until the following comments are addressed.

GRADING PERMIT COMMENTS:
1) Admin Manual Sec.2-06.4.8.B: An 1-ft No Access Easement exists along west property line per Final Plat S04-051. Show and label all easements per Final Plat on planviews.
2) Tech Manual Sec.2-01.4.1.C.3: Adjust grading limits to assure grading limits include all disturbance areas such as septic field disturbance, grading, staging area, and stormwater control area.

I can be reached at 837-4934 if you have questions.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
City of Tucson
01/18/2013 ANDREW CONNOR NPPO REVIEW Denied The grading plan has been reviewed by the Landscape / NPPO Section but cannot approve the plan until all Engineering, comments, concerns, and appropriate revisions have been addressed
12/24/2012 MICHAEL ST. PAUL ZONING REVIEW Denied December 24, 2012

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

DP12-0236 Grading Plans for T12CM08014
5141 North Gracious Court


Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. The site plan and grading plan are interrelated and interdependent. Correct the lot dimension along the north property line. The correct dimension is 204.13 feet.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved site plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed