Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP12-0231
Parcel: 12801005H

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP12-0231
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2013 STEVE SHIELDS ZONING REVIEW Approved
02/01/2013 SSHIELD1 NPPO REVIEW Passed
02/01/2013 RONALD BROWN HC SITE REVIEW Approved
02/05/2013 ANDREW CONNOR LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2013 CPIERCE1 APPROVAL SHELF Completed
02/11/2013 CPIERCE1 OUT TO CUSTOMER Completed