Review Details: RESUB - SITE and/or GRADING
Permit Number - DP12-0225
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/22/2013 | RONALD BROWN | HC SITE | REVIEW | Denied | RESUBMITTAL REVIEW COMMENTS IN ALL CAPS SHEET 2 1. As per Table 1106.1, a total of 4 accessible parking spaces are required for 82 total parking spaces provided. Please provide two more. OK SHEET 3 2. Provide a large scale detail of the following showing all accessibility requirements such dimensions, grade and ramp slopes, detectable warnings as required, handrails, markings, tread and riser heights and runs, ramp runs, widths, marked crossings, markings, aisles, access to accessible routes, van accessible spaces and ramps as required: a. Accessible parking layouts b. All different types of sidewalk and curb ramps c. Stairs NO ACCESSIBLE PARKING PLAN DETAILED, NO STAIR PLAN NOR SECTION SHOWN. PROVIDE HANDRAIL ELEVATION FOR STAIRS. 3. Provide an accessible route connection of the East and West sides of the 1 story, proposed building. accessible routes . NO CONNECTION SHOWN END OF REVIEW |
| 02/22/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |