Permit Number: DP12-0225
Parcel: 137055310

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0225
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2012 RBROWN1 ADA REVIEW Passed
12/10/2012 TERRY STEVENS ZONING REVIEW Approved
12/19/2012 RONALD BROWN H/C SITE REVIEW Denied SHEET 2
1. As per Table 1106.1, a total of 4 accessible parking spaces are required for 82 total parking spaces provided. Please provide two more.
SHEET 3
2. Provide a large scale detail of the following showing all accessibility requirements such dimensions, grade and ramp slopes, detectable warnings as required, handrails, markings, tread and riser heights and runs, ramp runs, widths, marked crossings, markings, aisles, access to accessible routes, van accessible spaces and ramps as required:
a. Accessible parking layouts
b. All different types of sidewalk and curb ramps
c. Stairs
3. Provide an accessible route connection of the East and West side accessible routes.
END OF REVIEW
12/20/2012 LOREN MAKUS ENGINEERING REVIEW Approved
12/21/2012 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed
12/26/2012 JOE LINVILLE LANDSCAPE REVIEW Approved
12/26/2012 KEN BROUILLETTE FIRE REVIEW Approved
12/27/2012 JOE LINVILLE NPPO REVIEW Approved
12/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The rim elevation of the next upstream sanitary manhole (2462.04') is higher than the first floor elevation (2460.73'). Include a note on the drawing to require the installation of a backwater valve. Reference: Section 715.1, IPC 2006, as amended by the City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2013 CPIERCE1 REJECT SHELF Completed