Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP12-0208
Parcel: 13340001C

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0208
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2012 RBROWN1 ADA REVIEW Passed
11/21/2012 MARTIN BROWN FIRE REVIEW Approved
11/26/2012 STEVE SHIELDS ZONING REVIEW Approved
12/06/2012 RONALD BROWN H/C SITE REVIEW Denied Please identify the covered accessible parking spaces.
END OF REVIEW
12/11/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied Delineate EHS and 100-year floodplain limits on site plan and provide civil engineer's seal on the site plan sheet for this data. (DS Sec.10-02.2.3.1.4.C.8)
12/12/2012 JOE LINVILLE NPPO REVIEW Denied Submit a native plant prservation plan or application for exception.
12/12/2012 JOE LINVILLE LANDSCAPE REVIEW Denied The proposed project is in proximity to the proposed Pantano River Park.
Please refer to the Pima Regional Trails System Master Plan and the excerpts below for pertinent standards that may be applicable.

Corridor Width. The minimum corridor width for River Parks is 100 feet on both river banks. However, additional space is recommended wherever possible to help enhance the quality and impact of the river park system, reduce the urban heat island effect, and allow for the restoration of the wildlife habit that once existed along the edges of the community's major watercourses.

Encroachment. New development shall not encroach into River Park corridors.

Provide labels for the future river park and include dimensions of any areas reserved.
12/12/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a detail showing the minimum clearance that will be afforded from underground utilities (e.g. sewers and natural gas pipes) to the footings for the canopies. The clearance shall allow sufficient room for safe excavation and repair of the underground utilities without disturbing the footings.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2012 CPIERCE1 REJECT SHELF Completed