Permit Number: DP12-0187
Parcel: 133110010

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0187
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2012 RONALD BROWN H/C SITE REVIEW Passed
10/24/2012 KEN BROUILLETTE FIRE REVIEW Approved
10/25/2012 JOE LINVILLE NPPO REVIEW Approved exception.
10/25/2012 JOE LINVILLE LANDSCAPE REVIEW Passed n/a
11/09/2012 TERRY STEVENS ZONING REVIEW Approved
11/14/2012 RBROWN1 ADA REVIEW Denied 1. Bleachers and shade structure to be constructed under a separte building permit.
SHEET CS201
2. Details 1 and 2
a. Show max 2% slope for all accessible parking surfaces in all directions
b. Show depth dimension of the accessible parking space
c. Show top of "Van Accessible" sign at 84"
3. Detail 3: Show height of both drinking spouts as per ICC A117.1, Section 602.4.
END OF REVIEW
11/15/2012 ELIZABETH EBERBACH ENGINEERING REVIEW Approved Detail sheet CS201: Water fountain drywells to not be installed deeper than 6-ft.
11/20/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
11/27/2012 CPIERCE1 REJECT SHELF Completed