Permit Number: DP12-0181
Parcel: 10408095C

Address:
700 W WETMORE RD

Review Status: Completed

Review Details: DEV PKG - REVISION

Permit Number - DP12-0181
Review Name: DEV PKG - REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2016 AROMERO4 START PLANS SUBMITTED Completed
03/22/2016 MARTIN BROWN COT NON-DSD FIRE Approved
04/01/2016 LOREN MAKUS ENGINEERING REVIEW Approved
04/04/2016 SSHIELD1 ZONING HC REVIEW Approved
04/04/2016 STEVE SHIELDS ZONING REVIEW Approved
04/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The rim elevation of the next upstream sanitary manhole (MH# 9752-01, 2309.81') is higher than the first floor elevation of the existing detail building (FFE 2308.0').Backwater valve protection will be required for any future plumbing modifications in this building per Section 710.1, UPC 2006, as amended by the City of Tucson.
2. It is not clear how the proposed car wash building (FFE 2305.5') will be connected to the sewer system. If the finished floor elevation is less than 12" above the rim elevation of the next upstream manhole, provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
04/06/2016 JOE LINVILLE LANDSCAPE REVIEW Reqs Change 1) AM 2-06.4.9.G If the project is to be phased, provide calculations, setbacks, etc., to indicate that each phase complies with all requirements as a separate entity. Show phase lines on the drawing.

The Landscape Plans and the Site/Phasing Plan are required to reflect the same boundaries to clarify compliance with requirements.

2) UDC 7.6.4.B.1.a.(3) An unpaved planting area, which must be a minimum of 34 square feet in area and four feet in width, must be provided for each canopy tree.
04/12/2016 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

1) Four rolled sets of the plans
2) All items requested by review staff
3) All items needed to approve these plans
04/29/2016 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approv-Cond See letter and map documents in PRO/SIRE.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2016 ARUIZ1 OUT TO CUSTOMER Completed