Permit Number: DP12-0171
Parcel: 13330079H

Review Status: Completed

Review Details: RESUB - SITE/GRADING ALL

Permit Number - DP12-0171
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2013 ANDREW CONNOR LANDSCAPE REVIEW Approved
02/12/2013 LOREN MAKUS ENGINEERING REVIEW Approv-Cond This Development Package is approved on the condition that a DSMR is applied for and approved for the solid waste enclosure and accessibility.
02/12/2013 DAVID RIVERA ZONING REVIEW Approved
02/13/2013 RONALD BROWN H/C SITE REVIEW Approved SHEET C3.1
1. It appears that the 5% slope indicated for the concrete drainage swale crosses the marked crossing at 5%. Please insure that the marked crossing complies with ICC A117.1, Section 403.3; 5% maximun running slope and 2% maximum cross slopes.
RESUBMITTAL REVIEW COMMENT:
RESPONSE IS INCORRECT. CROSS SLOPE AT THE MARK CROSSING MAY NOT EXCEED 2%. PLEASE RECONCILE AND RESUBMIT.
END OF REVIEW