Permit Number: DP12-0168
Parcel: 114540600

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP12-0168
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2012 CAGUILA1 START PLANS SUBMITTED Completed
09/28/2012 RONALD BROWN ADA REVIEW Passed
10/03/2012 MARTIN BROWN COT NON-DSD FIRE Approved
10/16/2012 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review , 10/16/2012,

SUBJECT: Senior Care Facility
DP12-0168, T15S, R13E, SECTION 02

RECEIVED: Development Package on September 26, 2012

The subject submittal has been reviewed and it can not be approved at this time. Prepare a detailed response that explains the revisions that were made and references the exact location on the Development Package where the revisions were made:

Drainage Report:

The drainage statement is acceptable and it is hereby approved.

Cover Sheet:

1. Provide a legend that shows and describes all symbols as required by D.S. 2-01.2.9.
2. Complete the missing information in Development Plan General Notes 5, 6 and 7.

EVERY PAGE OF PACKAGE:

1. Provide the DP12-0168 case number as required by D.S. 2-01.3.3.

BASE LAYER SHEET COMMENTS:

1. Show on the plan the basis of bearing and provide the tie between the basis of bearing and one of the corners of the parcel (D.S. 2-01.3.8.A).
2. If applicable, all easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided (D.S. 2-01.3.8.B) and (D.S. 2-01.3.9.L).

Site/Grading Plan:

1. Provide the existing/proposed sidewalks widths (D.S. 2-01.3.8.C).

2. Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section (D.S. 20-1.3.9.H.2).
3. Provide all missing radii to ensure that fire trucks and garbage trucks can easily enter and maneuver onsite (D.S. 20-1.3.9.H.3).
4. Propose a method to block the PAAL extension and the 15' depressed curb to prevent inadvertent vehicular access (D.S. 20-1.3.9.H) (e.g. bollards).
5. All proposed work in the public right of way will require a right of way excavation permit or a Private Improvement Agreement. Contact Richard Leigh of Transportation Department Permit and Codes at 791-5100 for additional information.
6. Revise the Development Plan Package according to the Drainage Report revisions.

Landscape Plan:

1. Ensure that the proposed landscaping does not obstruct visibility within the sight visibility triangles.


If you have any questions, I can be reached at 837-4933 or Laith.Alshami@tucsonaz.gov

RESUBMITTAL REQUIRED: Revised Development Plan Package
10/17/2012 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Senior Care Facility @ 9050 E. Tanque Verde Road
Development Package (1st Review)
DP12-0168

TRANSMITTAL DATE: October 17, 2012

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

The following comments are based on Development Standard 2-01.0:

1. D.S. 2-01.3.3 Provide the development package number, DP12-0168, adjacent to the title block on all sheets.

2. D.S. 2-01.3.7.A.9.b Per LUC Section 3.2.3.2.A Development Designator 9 the maximum lot coverage allowed for this site is 15%. It appears that the lot coverage has been exceeded. Provide a lot coverage calculation that meets the requirements of LUC Section 3.2.9 on the development package. A Board of Adjustment for Variance may be required.

3. Provide the Scenic Corridor Zone (SCZ) overlay date of approval and any conditions of approval on the development package.

4. Provide the Watercourse Amenities, Safety, and Habitat (WASH) ordinance number, date of approval and any conditions of approval on the development package.

5. Provide the Development Standard Modification Request (DSMR) date of approval and what was approved on the development package.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ DP12-0168

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
10/18/2012 RONALD BROWN ZONING HC REVIEW Approved
10/22/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter and backflow preventer
b. the location of the main water lines and fire hydrants
c. the location of the gas meter (if one exists or is planned)
d. the location and size of the public sanitary sewer
e. the location of the building connection to the public sewer
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
10/24/2012 JOE LINVILLE NPPO REVIEW Approved
10/24/2012 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond The Protected Riparian Area shall be protected through a conservation or public easement or other legal restriction upon further development. DS 9-06.2.6

Note the recording data on the Development Plan.
10/24/2012 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
10/25/2012 PATRICIA GEHLEN ZONING-DECISION LETTER WRITE DECISION LETTER Denied This review has been completed. Revisions are required.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2012 CPIERCE1 OUT TO CUSTOMER Completed
10/29/2012 CPIERCE1 REJECT SHELF Completed