Permit Review Detail
Review Status: Completed
Review Details: RESUB - SITE/GRADING ALL
Permit Number - DP12-0162
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 02/06/2013 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 02/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The downstream manhole (4735.04) is incorrectly labeled as the upstream manhole (4735.05); show and label the upstream manhole. If the first floor elevation of existing building #2 is less than 12" above the rim elevation of the upstream manhole, backwater valves (if they do not currently exist) will be required as part of any modifications to the sanitary drain system of building #2. [Previous comment: Revise the site drawing to include the location, invert, and rim elevation of the upstream manhole (it should be number 4735-05). The downstream manhole is shown in two locations - I assume that the one located over the sewer is correct and the other is just a drafting artifact. Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.] |