Permit Review Detail
Review Status: Completed
Review Details: SITE and/or GRADING
Permit Number - DP12-0128
Review Name: SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2012 | RBROWN1 | ADA | REVIEW | Passed | |
| 08/17/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 08/23/2012 | RONALD BROWN | H/C SITE | REVIEW | Denied | 1. Connect existing accessible route from existing warehouse to new modular building entrance. 2. Man gate and stairs do not comply with the 29006 IBC, Section 1108.1.4.; landings on both side of door/gate. 3. Provide an accessible entrance to the new modular building. a. All ramps are to comply with ICC A117.1, Section 405 including handrails and landings. 4. Please provide large scale details of the steps and ramp. 5. Obtain a placement permit from the state of Ariziona. END OF REVIEW |
| 08/24/2012 | TERRY STEVENS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Terry Stevens Lead Planner PROJECT: DP12-0128 1840 N. 7th Av. Development Package TRANSMITTAL DATE: 08/28/12 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. DS 2-01.2.5: Revise the development plan document to include the correct CDRC approval stamp in the lower right quadrant of each sheet. The link to the stamp can be found here: http://cms3.tucsonaz.gov/pdsd/cdrc-rezoning/cdrd-stamp. 2. DS 2-01.3.3 This project has been assigned case number DP12-0128. Place this case number near the lower right corner of all sheets. 3. DS 2-01.3.7.A.4 Clearly indicate compliance with the subject to section 3.5.10.3.C &.F. This section of the code is applicable because of LUC Sec. 3.5.7.7.C. 4. DS 2-01.3.7.A.6.a This project will require a Design Development Option variance in order to reduce the required setback from the west property line. Provide a note indicating the DDO case number, date of approval, what the variance is for and any conditions of approval. Place the case number also near the lower right corner of all sheets. 5. DS 2-01.3.8.A The property lines as indicated do not appear to be correct. Per the county assessors records this property is one continuous lot not 3 lots as indicated. Provide distance and bearing of all property lines. 6. DS 2-01.3.9.F All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. 7. DS 2-01.3.9.H.5.c The loading zone notes provided do not appear to relate to this project. Revise. 8. DS 2-01.3.9.O Per LUC Sec. 2.7.2.2 H.2 this project has a development designator of "34". Per LUC Sec. 3.2.3.2.B development designator "34" has a perimeter yard indicator of "DD". Per LUC Sec. 3.2.6.4 the perimeter yard indicator refers to Sec. 3.2.6.5 for the street frontage. Per LUC Sec. 3.2.6.5.A the required setback for the west side street setback is 10'. This project proposes a setback of 2'-2". A DDO variance to reduce the required setback is required. This comment can be used to apply for the DDO variance. 9. DS 2-01.3.9.Q Provide dimensions on the footprint of the proposed structure. If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961 C:\planning\cdrc\DSD\DP12-0128.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 08/28/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the site drawing to include the following information: a. the location and size of the water meter and backflow preventer b. the location of the main water lines and fire hydrants c. the location of the gas meter (if one exists or is planned) d. the location and size of the public sanitary sewer e. the location of the building connection to the public sewer f. the location, invert, and rim elevation of the upstream and downstream manholes Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006. |
| 08/28/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/30/2012 | JOE LINVILLE | NPPO | REVIEW | Passed | n/a |
| 08/30/2012 | JOE LINVILLE | LANDSCAPE | REVIEW | Denied | 1) Revise the plans to provide street landscape border per LUC 3.7.2.4. for the expansion area. 2) Revise the plans to comply with LUC 3.7.3.2.C relative to the location of the screen for the expansion area. 3) Revise the plans to provide canopy trees in the vehicular use area per LUC 3.7.2.3.A.1.a |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/04/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |