Permit Number: DP12-0128
Parcel: 11506215A

Address:
1830 N 7TH AV

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0128
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2012 RBROWN1 ADA REVIEW Passed
08/17/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/23/2012 RONALD BROWN H/C SITE REVIEW Denied 1. Connect existing accessible route from existing warehouse to new modular building entrance.
2. Man gate and stairs do not comply with the 29006 IBC, Section 1108.1.4.; landings on both side of door/gate.
3. Provide an accessible entrance to the new modular building.
a. All ramps are to comply with ICC A117.1, Section 405 including handrails and landings.
4. Please provide large scale details of the steps and ramp.
5. Obtain a placement permit from the state of Ariziona.
END OF REVIEW
08/24/2012 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP12-0128
1840 N. 7th Av.
Development Package

TRANSMITTAL DATE: 08/28/12

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-01.2.5: Revise the development plan document to include the correct CDRC approval stamp in the lower right quadrant of each sheet. The link to the stamp can be found here: http://cms3.tucsonaz.gov/pdsd/cdrc-rezoning/cdrd-stamp.

2. DS 2-01.3.3 This project has been assigned case number DP12-0128. Place this case number near the lower right corner of all sheets.

3. DS 2-01.3.7.A.4 Clearly indicate compliance with the subject to section 3.5.10.3.C &.F. This section of the code is applicable because of LUC Sec. 3.5.7.7.C.

4. DS 2-01.3.7.A.6.a This project will require a Design Development Option variance in order to reduce the required setback from the west property line. Provide a note indicating the DDO case number, date of approval, what the variance is for and any conditions of approval. Place the case number also near the lower right corner of all sheets.

5. DS 2-01.3.8.A The property lines as indicated do not appear to be correct. Per the county assessors records this property is one continuous lot not 3 lots as indicated. Provide distance and bearing of all property lines.

6. DS 2-01.3.9.F All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined.

7. DS 2-01.3.9.H.5.c The loading zone notes provided do not appear to relate to this project. Revise.

8. DS 2-01.3.9.O Per LUC Sec. 2.7.2.2 H.2 this project has a development designator of "34". Per LUC Sec. 3.2.3.2.B development designator "34" has a perimeter yard indicator of "DD". Per LUC Sec. 3.2.6.4 the perimeter yard indicator refers to Sec. 3.2.6.5 for the street frontage. Per LUC Sec. 3.2.6.5.A the required setback for the west side street setback is 10'. This project proposes a setback of 2'-2". A DDO variance to reduce the required setback is required. This comment can be used to apply for the DDO variance.

9. DS 2-01.3.9.Q Provide dimensions on the footprint of the proposed structure.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP12-0128.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
08/28/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter and backflow preventer
b. the location of the main water lines and fire hydrants
c. the location of the gas meter (if one exists or is planned)
d. the location and size of the public sanitary sewer
e. the location of the building connection to the public sewer
f. the location, invert, and rim elevation of the upstream and downstream manholes
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
08/28/2012 LOREN MAKUS ENGINEERING REVIEW Approved
08/30/2012 JOE LINVILLE NPPO REVIEW Passed n/a
08/30/2012 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Revise the plans to provide street landscape border per LUC 3.7.2.4. for the expansion area.

2) Revise the plans to comply with LUC 3.7.3.2.C relative to the location of the screen for the expansion area.

3) Revise the plans to provide canopy trees in the vehicular use area per LUC 3.7.2.3.A.1.a

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2012 CINDY AGUILAR OUT TO CUSTOMER Completed