Review Status: Completed
Review Details: SITE and/or GRADING
Permit Number - DP12-0127
Review Name: SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2012 | RBROWN1 | ADA | REVIEW | Passed | |
| 08/16/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/16/2012 | SSHIELD1 | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/16/2012 | SSHIELD1 | LANDSCAPE | REVIEW | Passed | |
| 08/16/2012 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 08/16/2012 | SSHIELD1 | H/C SITE | REVIEW | Passed | |
| 08/22/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Revise the drainage statement floodplain delineation. The aerial photos of the site show a curb island and solid waste container enclosure upstream of cross-section 4. Revise the analysis to include a cross section at these obstruction and upstream of them as well. (SMDDFM Fig. 5.1) Provide details of the fence design to demonstrate that the clear openings in the area affected by the regulatory flows. Show how the gates will respond to potential clogging by debris carried downstream from the subdivision areas. Discuss the use of break-away latches or some other means for preventing adverse effects caused by clogging. |
| 08/29/2012 | MARTIN BROWN | FIRE | REVIEW | Approv-Cond | All manual and automatic gates are required to comply with local amendments from the 2006 IFC Section 503.6. The man gates for firefighting access to exterior walls shall also be capable of being opened by fire personnel. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/05/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |