Permit Review Detail
Review Status: Completed
Review Details: SITE and/or GRADING
Permit Number - DP12-0116
Review Name: SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/06/2012 | RBROWN1 | ADA | REVIEW | Passed | |
| 09/11/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | Exiting shall be per the 2006 IFC with local amendments |
| 09/14/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 09/21/2012 | STEVE SHIELDS | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Planning and Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: Social Bar Development Package (2nd Review) DP12-0116 TRANSMITTAL DATE: September 21, 2012 DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Provide all conditions of MDR, DRB and Historic review on the plan and demonstrate on the plan how all conditions are met. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com Sshield1 on DS1/planning/New Development Package/ DP12-0116 RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 09/24/2012 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Approved | |
| 09/25/2012 | RONALD BROWN | H/C SITE | REVIEW | Approv-Cond | If the rail is to be a drink rail, please provide an accessible bar rail as required by 2006 IBC, Section 1109.11 and ICC A117.1, Sections, 902 and/or904 which ever is most applicapable. END OF REVIEW |
| 09/25/2012 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | Provide all conditions of MDR, DRB and Historic review on the plan and demonstrate on the plan how all conditions are met. |
| 09/25/2012 | ANDREW CONNOR | NPPO | REVIEW | Approved | |
| 09/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the site drawing to include the following information: a. the location of the main water lines and fire hydrants b. the location of the gas meter (if one exists or is planned) c. the location and size of the public sanitary sewer d. the location of the building connection to the public sewer e. the location, invert, and rim elevation of the upstream and downstream manholes and cleanouts f. the first floor elevation for the building Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/27/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |