Permit Number: DP12-0115
Parcel: 113080240

Address:
2904 N 1ST AV

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0115
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2012 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Provide previous approved site and landscape plans for reference.

2. Note: Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval per LUC 3.7.1.2.B.

3. Include with re-submittal DDO approval documentation. Indicate on the lower right hand corner of the site plan, the case number, date of approval, and any conditions imposed

4. Ensure that all zoning comments and concerns are addressed

5. Additional comments may apply
08/01/2012 ANDREW CONNOR NPPO REVIEW Approved
08/09/2012 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: USA Pawn & Jewelry Company - Façade Remodel
Development Package (1st Review)
DP12-0115

TRANSMITTAL DATE: August 10, 2012

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

Provide a copy of the last approved site plan. Additional comments may be forth coming.

The following comments are based on Development Standard 2-01.0:

1. D.S. 2-01.3.3 Provide the development package number, DP12-0115 adjacent to the title block on all sheets.

2. D.S. 2-01.3.7.A.4 Revise General Note 3 to reflect the correct subject to section 3.5.2.9.A for General Merchandise Sales and add Vehicle Rental and Sales "31", subject to: Sec. 3.5.9.5.A and .B to the note.

3. D.S. 2-01.3.7.A.4 Under "Site Development Plan Data, Development Designator" add the use General Merchandise Sales and correct the subject to section 3.5.2.9.A and add Vehicle Rental and Sales "31", subject to: Sec. 3.5.9.5.A and .B.

4. D.S. 2-01.3.9.H.2 The proposed façade is located within the future sight visibility triangles, as Development Standard Modification Request (DSMR) may be required. See Engineering comments.

5. D.S. 2-01.3.9.H.5.a The provided vehicle parking calculation is not correct. Unless the indoor storage area is a separate use under a separate C of O the vehicle parking calculation is based on 1 to 200 of gross floor area. Provide a copy of the last approved site plan, see comment 1.

6. D.S. 2-01.3.9.O Per LUC Section 3.2.6.5.B and Table 3.2.6-I, ADT of 1,000 or greater the required setback is 21' or the height (H) of the proposed exterior building wall measured from the back of future curb. As a perimeter street setback dimension to the back of future curb was not provided the setback cannot be verified.

7. D.S. 2-01.3.9.O The setback called out under Keynote 22 does not appear to be correct. Per Section 3.2.6.5.B and Table 3.2.6-I, ADT of 1,000 or greater the required setback is 21' or the height (H) of the proposed exterior building wall measured from the back of future curb. Based on the height provide on the plan the required setback would be 26'-6". Provide building elevations so that the required setback can be verified.

8. It appears that the proposed façade remodel is located within the future right-of-way (ROW), either design to meet the future right-of-way or provide a future site plan that demonstrates how the site will function if the ROW is taken.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ DP12-0115

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
08/15/2012 KEN BROUILLETTE FIRE REVIEW Approved
08/16/2012 ZELIN CANCHOLA COT NON-DSD TRAFFIC Denied Sight visiblity triangles do not meet standards. Additional information required.
08/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location of the main water lines and fire hydrants
b. the location of the gas meter (if one exists or is planned)
c. the first floor elevation for the building
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
08/17/2012 RONALD BROWN H/C SITE REVIEW Denied 1. Show accessible parking sign location.
a. Provide large scale detail
b. Include "Van Accessible" sign.
2. Make the accessible parking aisle 8'-0" for "Van Accessible" parking space.
3. Show maximum slope of 2% in all directions for accessible parking space and aisle.
4. New accessible route to 1st Av. to have maximum running slope of 5% and 12% max cross slope.
END OF REVIEW
08/22/2012 PAUL MACHADO ENGINEERING REVIEW Denied To: Gene Goldstein DATE: August 27, 2012
6255 N. Camino Pineria Aria Tucson, Arizona 85718

Subject: 2904 N. 1st Ave, USA PAWN
Development Package, DP12-0115 (First Review)
T13S, R14E, Section 31

RESUBMITTAL REQUIRED: Development Package and Drainage Statement

The Development Package (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Package:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. List the following note on all development package documents: "No structure or vegetation shall be located or maintained so as to interfere with the sight visibility triangles in accordance with Development Standard 3-01.0." Therefore a DSMR will be required if the design is left as is.
3. The location and amount of curb cuts on First Ave., especially the curb cuts west of the building, may suggest to drivers that parking is allowed in those areas which will have to back out onto First Ave in order to leave. Backing out onto a MS&R Collector Street is prohibited. The City of Tucson is requesting that the curb cuts be closed leaving the 36'-10" driveway remaining.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/ 2904 N. 1st Ave DP

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2012 CPIERCE1 OUT TO CUSTOMER Completed