Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0102
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2012 RBROWN1 ADA REVIEW Passed
07/24/2012 KEN BROUILLETTE FIRE REVIEW Approved
07/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter and backflow preventer
b. the location of the main water lines and fire hydrants
c. the location of the gas meter (if one exists or is planned)
d. the location and size of the public sanitary sewer
e. the location of the building connection to the public sewer
f. the location, invert, and rim elevation of the upstream and downstream manholes and cleanouts
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
07/30/2012 ANDREW CONNOR LANDSCAPE REVIEW Approved
07/31/2012 ANDREW CONNOR NPPO REVIEW Approved
08/02/2012 RONALD BROWN H/C SITE REVIEW Denied 1. The slope from the top of the new sidewalk to Craycroft Road is greater than 5% and must meet the requirements of a ramp and comply with ICC A117.1, Section 405 complete with handrails.
a. Provide a handrail elevation in accordance with ICC A117.1, sections 405.9 and 505.10.1.
2. Provide detectable warning strips at both ends of the marked crossing as required by ICC A117.1, section 406.12, 13 and 14.
3. Delete the non-compliant (in the asphaltic paving) and provide a concrete ramp in the concrete walkway that complies with ICCA 117.1, section 406. complete with a detectable warning strip.
4. Neither accessible parking asile ramps are compliant. Provide ramps that comply with ICCA 117.1, section 406.
5. Provide large scale details of all the different types of ramps showing all accessible requirements such as: dimensions, elevations, slopes, detectable warning strips as required and handrails as required. Reference ICC A117.1, sectios 405 and 406.
6. Provide large scale details of the accessible parking layouts showing all accessible requirements such as: dimensions, elevations, grade slopes, markings, signage, ramps, "Van Accessible" spaces and etc.
a. Provide a large scale sign detail including "Van Accessible" identification as per COT DOT requirements.
7. Zoning will require pedestrian pathways to both 5th Street and Baker Street right of ways. Reference Zoning comments. These must be accessible.
a. Provide all marked crossings as required.
b. Provide all ramps and handrails as required.
c. All new accessible routes slopes are to comply with ICC A117.1, Section 403.3; 5% max running slope, 2% max cross slope.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed