Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: DP12-0098
Parcel: 117170020

Review Status: Active

Review Details: RESUB - SITE/GRADING ALL

Permit Number - DP12-0098
Review Name: RESUB - SITE/GRADING ALL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2013 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. It appears that previous comments have not been addressed. Provide response to comments or approval documentation with the next submittal.

2. Projects within the Rio Nuevo and Downtown (RND) Zone shall be reviewed in accordance with the Administrative Design Review Procedures; 23A-32. Applications for RND Zone shall be referred to the design review board (DRB) to be scheduled for consideration at the first available meeting for determination of preliminary findings and commendations. Include with re-submittal DRB review approval documentation. Indicate on the lower right hand corner of the site plan, the case number, date of approval, and any conditions imposed.

3. Ensure that all Zoning comments and concerns are addressed.

4. Additional comments may apply.
01/09/2013 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP12-0098
140 E. Broadway Blvd.
Development Package

TRANSMITTAL DATE: 01/11/13

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-01.3.3 This project has been assigned case number DP12-0098. Place this case number near the lower right corner of all sheets.

MDR and DRB reviews will be required. Place the case numbers near the lower right corner of all sheets.

Provide on the plan as a general note the case number, date of approval, what the MDRs are requesting and any conditions of approval.

2. DS 2-01.3.7.A.6.b Provide as a general note: This project has been designed to meet the criteria of Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone, Sec. 2.8.4, Gateway Corridor Zone.

3. DS 2-01.3.8.B The indicated electrical easement will be required to be abandoned prior to approval of the development package. Provide recording sequence number on the plan for the abandonment.

4. DS 2-01.3.9.F Provide the zoning of the property to the south of the proposed project on the plan.

5. DS 2-01.3.9.H.5.b The removal of the existing parking lot and the number of parking spaces being provided, which is zero for all three parcels, will require a separate MDR approval for each parcel.

The number of required parking spaces for the proposed development is 56 parking spaces. Provided is zero.

The number of parking spaces required for the existing "Julian Drew Block" is 29 parking spaces. Provided is zero.

The number of required parking spaces for the existing "carriage House" is 10 parking spaces. Provided is zero.

DS 2-01.3.9.H.5.b If any of the required parking is located off -site as permitted by the LUC, a drawing of that parking area is to be provided, together with the City's required
parking agreement (include a copy of the lease agreement if applicable). Please remember that in these situations, if the off-site parking location is a new parking area, it must comply with all parking area requirements and must be allowed as a principal use by the zoning classification of that property. If the off-site parking area location is an existing parking lot, the parking spaces utilized for the proposed land use must be nonrequired parking for the existing use for which the parking area was established.

6. DS 2-01.3.9.H.5.c Based on the square footage and uses provided no loading zone is required for each of the three parcels. Revise calculations to reflect zero loading zones required.

7. DS 2-01.3.9.H.5.d The number of bicycle parking spaces being provided, which is zero for all three parcels, will require a separate MDR approval for each parcel.

The number of required short term bicycle parking spaces for the proposed project is 20. The number provided is zero.

The number of required long term bicycle parking spaces for the proposed project is 28. The number provided is zero.

The number of required short term bicycle parking spaces for the existing "Julian Drew Block" is 6. The number provided is zero.

The number of required long term bicycle parking spaces for the existing "Julian Drew Block" is 13. The number provided is zero.

The number of required short term bicycle parking spaces for the existing "Carriage House" is 6. The number provided is zero.

The number of required long term bicycle parking spaces for the existing "Carriage House" is 6. The number provided is zero.

8. DS 2-01.3.9.K If applicable, provide all proposed easements along with description, recording information, size and location.

9. DS 2-01.3.9.O The required street setback per LUC Sec. 3.2.6.5.B along Arizona Ave and Broadway is 21' or the height of the structure from the back of future curb. Revise notes and include in the MDR application.

10. DS 2-01.3.7.A.9 Per LUC Sec. 3.2.3.1.D a project with a development designator of "X" requires a lot coverage maximum of 80%. This project is proposing a lot coverage of 100%. Provide in the application for the MDR.



If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSDDp12-0098-2.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
01/14/2013 RONALD BROWN H/C SITE REVIEW Approved
01/14/2013 PAUL MACHADO ENGINEERING REVIEW Denied To: Gene Goldstein DATE: January 14, 2013
6225 N. Cam. Primeria Alta, #136 Tucson, Arizona 85701

Subject: Julian Drew Bldg., 140 E. Broadway Blvd.
Development Package, DP12-0098 (First Review)
T14S, R13E, Section 13

RESUBMITTAL REQUIRED: Development Package and Drainage Statement

The Development Package (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Package:

1. Please include a response letter to the comments along with the corrected copies of the DP. A response letter was not included in the re-submittal package. It appears that many of my comments were not addressed, see last comment for more information.
2. Existing Site Conditions. The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within fifty (50) feet of the site. On sites bounded by a street with a width of fifty (50) feet or greater, the existing conditions across the street will be provided. D.S. 2-01.3.8.
C. The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. Per previous comment.
E. Indicate the ground elevation on the site based on City of Tucson Datum (indicate City of Tucson field book number and page). Per previous comment.
G. Other significant conditions on the site, such as major rock outcrops, structures, fences, walls, etc., shall be shown. These elements should be indicated in a different line weight than the proposed improvements and labeled "to be removed" or "to be retained." Show any landscaping/hardscaping in the right-of-way and/or on the parking lot area to determine if any "needed items" are removed.
3. Information on Proposed Development. The following information on the proposed project shall be shown on the drawing or added as notes. D.S. 2-01.3.9.
H. Proposed traffic circulation:
2. Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section. Existing = future right-of-way, show the existing SVT's.
c. Show all loading zones, and vehicle maneuverability fully dimensioned, and access route, and provide, as a note, the number of loading spaces required, the number provided, and the design vehicle. Per previous comment.
N. In conjunction with a drainage report or statement, as applicable, prepared in accordance with the City Engineer's instructions and procedures, the following information will be indicated on the development package documents. For additional information regarding drainage standards, see the City of Tucson Standards Manual for Drainage Design and Floodplain Management.
7. Draw locations and indicate types of off-site runoff acceptance points and/or onsite
run-off discharge points.
8. Since the parking lot may presently accept roof drainage from the existing building surrounding this site, how will the existing roof drainage than run-off? Sidewalk scuppers are required for the new roof drainage or down spouts.
T. Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Development Standard 6-01.0. Refuse collection on all projects shall be designed based on that Standard, even if collection is to be contracted to a private firm. Per previous comment.
4. Include a compact disk (CD) containing the latest/revised submittal of the dev. plan, reports and documents associated with this project with the latest submittal.
5. It is suggested that while my comments are being addressed or have been addressed, that you make an appointment/call/email me to discuss any of my comments that you may have questions on. If I missed any information or made a mistake, we can go over those items at the meeting, over the phone or through email. Do not hesitate to call if there are any questions or disagreements on my comments as you address them.


Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted along with the site plan and accepted with the approval of the grading plan.
3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2.
4. Address the sidewalk scupper situation mentioned above.
5. Show the project address or administration address on the cover sheet of the DS.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/140 E. Broadway Blvd. DEVPKG-SITE 2
01/16/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the size of the water meter and backflow preventer to serve this building
b. the location of the main water lines and fire hydrants
c. the future location of the gas meter
d. the location of the building connection to the public sewer
e. the location, invert, and rim elevation of the upstream and downstream manholes
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
01/17/2013 KEN BROUILLETTE FIRE REVIEW Denied 1. The note 1 under Building Plan Notes on Sheet 1 is not an acceptable answer to previous review comment to locate the nearest fire hydrant on site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2013 CPIERCE1 REJECT SHELF RECEIVED