Review Details: RESUB - SITE and/or GRADING
Permit Number - DP12-0092
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/24/2013 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Required Street landscape borders shall be located entirely on site, except that, if approved by the City Engineer or designee, up to five (5) feet of the required ten (10) foot width be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets LUC 3.7.2.4.3. Obtain permission for use of ROW. Letter included with submittal was addressed to Loren Makus. Permission for use of ROW must be granted from The Transportation Department, contact Gary Wittwer Landscape Architect Transportation @ Gary.Wittwer@tucsonaz.gov 2. Include with e-mail or other correspondence a copy of the site and landscape plan alone with the request for ROW use. |
| 02/05/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The rim elevation of the next upstream sanitary manhole (2333.73') is higher than the first floor elevation (2333.63'). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. [Previous comment: Verify the rim and invert elevations of sanitary manhole 9855.01; the invert elevation is generally not 3-feet higher than the rim elevation. If the rim elevation of the next upstream sanitary manhole (2333.73') is correct, it is higher than the first floor elevation (2333.63'). Provide note on the site plan stating that any future plumbing work for this address will require the installation of a backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson.] |
| 02/05/2013 | RONALD BROWN | HC SITE | REVIEW | Denied | 1. Provide detectable warning strips as per ICC A 117.1, Section 406.12, 13 and 14 and curbs ramps as needed as per Section 405 and 406 at both ends of the new marked crossing. a. Provide large scale details of all ramps showing all accessibility requirements. 2. Provide a dimensional width for all accessible routes, ramps and marked crossings. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/06/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 02/06/2013 | CPIERCE1 | REJECT SHELF | Completed |