Permit Number: DP12-0089
Parcel: 117061080

Address:
504 E 9TH ST

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP12-0089
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2012 PGEHLEN1 START PLANS SUBMITTED Completed
11/27/2012 PGEHLEN1 ENV SVCS REVIEW Denied The project plans are not approved. Need DSMR to address 9 APC's listed in plans. In addition, plans need to detail how APC's will be serviced and brought to curb. General note that on site mgmt will address refuse on site does not cover APC's.




Jeff Drumm, P.E.
Environmental Manager
City of Tucson Environmental Services
520-837-3713
11/28/2012 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: The Junction At Iron Horse
Development Package (3rd Review)
DP12-0089

TRANSMITTAL DATE: November 30, 2012

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This development package was reviewed for full code compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for the entire site.

2. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is June 10, 2013

3. The following comments are based on Development Standard 2-01.0:

4. This comment has not been addressed. D.S. 2-01.3.8.B The existing easements shown to be "ABANDONED BY SEPARATE INSTRUMENT" will need to be abandoned prior to approval of the development package.

5. This comment has not been addressed. D.S. 2-01.3.9.E As this project comprises numerous parcels, once the alley is abandoned, a lot combination is required. Provide a copy of the approved Pima County Combo Request form with your next submittal.

6. D.S. 2-01.3.9.H.5.a Due to the changes to the plan the individual parking plan (IPP) will need to be submitted and approved prior to approval of this development package. Once approved the vehicle parking requirements can be reviewed.

7. D.S. 2-01.3.9.H.5.d Due to the changes to the plan the individual parking plan (IPP) will need to be submitted and approved prior to approval of this development package. Once approved the bicycle parking requirements can be reviewed.

8. D.S. 2-01.3.9.L Provide the sequence number for all proposed easements. These easements will need to recorded prior to approval of the development package.

9. D.S. 2-01.3.9.O Provide building elevations so that all building perimeter yard setback requirements can be verified.

10. D.S. 2-01.3.9.O Based on the information provided under the "SITE DATE 3. REQUIRED/PROPOSED BUILDING SETBACKS" the following Modification of Development Regulations (MDR) or Board of Adjustment for Variance is required:

a. Per LUC Section 3.2.6.5.B and Table 3.2.6-I, ADT over 140 but less than 1,000, the required North street perimeter yard setback is based on the height of the proposed building wall, measured from the outside edge of the nearest adjacent travel lane. Based on a wall height of 58'-8", the required perimeter yard setback is 58'-8", the proposed street perimeter yard setback is 40'-0".
b. Per LUC Section 3.2.6.5.B and Table 3.2.6-I, ADT of 140 or less, the required South street perimeter yard setback is based on the ½ the height of the proposed building wall, measured from the back of existing curb or future curb location. Based on a wall height of 55'-2", the required perimeter yard setback is 27'-7", the proposed street perimeter yard setback is 23'-9".
c. Per LUC Section 3.2.6.4, Development Designator 33, Perimeter Yard Indicator "DD", the required perimeter yard setback to adjacent R-3 zoned parcels is 1 ½ times the height of the building exterior wall. Based on a wall height of 58'-8" the required East perimeter yard setback to the adjacent R-3 zoned parcels is 88'-0", proposed perimeter yard setback to the adjacent R-3 zoned parcels is 79'-6".
As building elevations were not provided with this submittal the required perimeter yard setbacks could not be verified.

11. D.S. 2-01.3.9.O The required West perimeter yard setback does not appear to be shown correctly. Based on an ADT of >140 the required setback should be 29'-4".

12. D.S. 2-01.3.9.Q Per LUC Section 3.2.3.2.B, Development Designator 33, the allowed building height is 50'-0", proposed building height is 55'-2". A Modification of Development Regulations (MDR) or Board of Adjustment for Variance is required. As building elevations were not provided with this submittal the required perimeter yard setbacks could not be verified.

13. The MDR or Board of Adjustment must be approved prior to approval of the development package. If approved provide the number, date of approval, what was approved, and any conditions of approval on the development package.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ DP12-0089

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package, approved Pima County Combo Request form.
12/04/2012 TIM ROWE PIMA COUNTY WASTEWATER Approved PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


December 4, 2012


To: JOHN GRENIER M. P.E.
GRENIER ENGINEERING, INC.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: THE JUNCTION AT IRON HORSE
Development Plan - 3rd submittal
DP12-0089


The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:

The Pima County Regional Wastewater Reclamation Department hereby approves the above referenced submittal of the development plan.
12/05/2012 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond 1. No issues with the Landscape plan submitted.

2. Prior to landscape approval signature include with re-submittal MDR or DRB approval documentation. Indicate on the lower right hand corner of the site plan, the case number, date of approval, and any conditions imposed.

3. Ensure that all Zoning comments and concerns are addressed

4. Additional comments may apply
12/07/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/07/2012 LOREN MAKUS ENGINEERING REVIEW Approved
12/10/2012 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change Review completed. Revisions required.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/26/2012 PGEHLEN1 OUT TO CUSTOMER Completed
12/26/2012 CPIERCE1 REJECT SHELF Completed