Permit Number: DP12-0071
Parcel: 13330086C

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0071
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2012 RBROWN1 ADA REVIEW Passed
06/06/2012 KEN BROUILLETTE FIRE REVIEW Approved
06/12/2012 RONALD BROWN H/C SITE REVIEW Denied 1. As per the 2006 IBC, Section 1106.5 one of the accessible parking spaces is to be a "Van Accessible" as per ICC A117.1, Section 502 requirements. Please identify which space is to be "Van Accessible".
2. Please show the curb ramp deplicted on the standard accessible curb ramp detail on the Site Plan. I believe that the aisle for the accessible parkinmg space will have to be located in the middle of the building columns in order to have a clear access to the accessible route.
3. Provide one accessible parking sign per parking space loacated just inside the curb line and on the center line of each accessible parking space.
4. Please provide a large scale detail of the accessible parking signage including the "Van Accessible" sign.
5. As per ICC A117.1, section 502.5, all accessible parking surface area slopes shall not exceed 2% in all directions.
END OF REVIEW
06/15/2012 JOE LINVILLE LANDSCAPE REVIEW Denied 1) A 10' wide street landscape border per LUC 3.7.2.4.A is required along the entire street frontage.

2) Within a vehicular use area, one (1) canopy tree is required for each four (4) motor vehicle parking
spaces or fraction thereof. The canopy trees must be evenly distributed throughout the vehicular use area. Every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk). LUC 3.7.2.3.A.1

3) Revise the street landscape border tree calculation to reflect the correct border length and number of required trees.

4) The area between the right-of-way line and sidewalk and the area between the sidewalk and the curb, if not covered with vegetation, shall be covered with an appropriate inorganic ground cover, such as decomposed granite. Revise the plans to clarify compliance. LUC 3.7.2.4.A.4

5) If use of the right-of-way along Broadway is desired to partially meet the landscape border width requirements contact the City Engineer. Landscape borders proposed in right-of-way or MS&R areas must be approved by the City Engineer or designee and comply with the City Engineer's requirements on construction, irrigation, location, and plant type. Provide verification, in writing, of any approvals obtained. Contact Gary Wittwer, DOT Landscape Architect for specific requirements.

6) Revise the landscape to include a maintenance schedule per DS 2-072.2.A.4 including:

A) Pruning schedules to show that plant material will maintain
pedestrian and vehicular clearances or that the material will
establish opaque hedge screens

B) Replacement criteria, should plant material not survive.

C) Replacement or upkeep maintenance schedules for inert ground
cover materials.

D) Maintenance schedules for exterior hardscape materials.

E) Maintenance and replacement schedules for irrigation systems.


7) The site is required to include screening per LUC Table 3.7.2-I. (north and south sides of the site. Revise as necessary. LUC 3.7.3 & DS 2-06.3.7.

8) An irrigation plan shall be submitted together with the landscape plan. LUC 3.7.4.5.C
The plan is required to include the following:

A) Type of water conserving irrigation systems proposed and differentiation between systems for the different water use zones on the site.

B) Source of irrigation water.

C) System specifications, design, and layout (Development Standard 2-06.5.4.A and 2-06.5.4.B).

D) Extent of supplementary irrigation in each planting area, provided by water harvesting methods.

E) Point of drainage off roof areas, amount of flow, and disposition of flow.

F) The extent to which systems are proposed within the public right-of-way.
06/19/2012 JOE LINVILLE NPPO REVIEW Approved
06/20/2012 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP12-0071
8723 E. Broadway Blvd.
Development Package

TRANSMITTAL DATE: 06/19/12

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This project has been submitted as a parking lot remodel. The plan indicates a proposed building expansion of 4000 sq. ft. The expansion appears to be greater than 25% therefore requiring full code compliance for the entire site. Review DS 2-01 for criteria for a full code compliance of a commercial site.

Provide documentation of permits of the expansions indicated on the aerial photos for building #1, appears to have a possible eating area at the rear (enclosed porch?) as well as two storage buildings.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP12-0071.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
06/20/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/20/2012 PAUL MACHADO ENGINEERING REVIEW Denied To: Rhonda Rawson DATE: June 20, 2012
P.O. Box 13152 FROM: Paul Machado
Tucson, Arizona 85732 Engineering Division


Subject: Plaza Del Rey ctr., 8723 E. Broadway Blvd.
Development Package, DP12-0071 (First Review)
T14S, R15E, Section 10


RESUBMITTAL REQUIRED: Development Package, Drainage Statement and Geotechnical Report


The Development Package (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Package:

1. This project is subject to full code compliance per D.S. 2-01.0

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. A Drainage report is required for any site greater than one acre in size or for any site subject to detention requirements…..per S.M.D.D.F.M., chap. II, 2.1.2.
3. The content and format of the Drainage Report should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address on the cover sheet of the DR.
5. A geotechnical report will be required for recommendations associated with building over a drainage pipe.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/8723 E. Broadway Blvd_DEVPKG-SITE_2-01.0

Final Status

Task End Date Reviewer's Name Type of Review Description
06/25/2012 CINDY AGUILAR OUT TO CUSTOMER Completed