Permit Review Detail
Review Status: Completed
Review Details: REVISION - SITE
Permit Number - DP12-0069
Review Name: REVISION - SITE
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/08/2013 | TERRY STEVENS | ZONING | REVIEW | Passed | |
04/17/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/23/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/24/2013 | RONALD BROWN | H/C SITE | REVIEW | Denied | 1. Please indicate on the large scale floor plan where Detail "A", Cross Section is cut. 2. At the detail entitled "Ramp Grading Detail": a. Please provide an alphabetical identification of "D". b. The grade elevations shown on the higher landing, 11.07 TC, conflict with the same elevations shown on the site plan of 12.00 TC. If 11.07 TC was to remain the landing slope would be non compliant a with a slope of 14%. Reference ICC A 117.1, section 405. c. Please provide all dimensions of the ramp and sidewalk. d. Please provide a handrail elevation compliant with ICC A117.1, Section 405.8 and 505. END OF REVIEW |
04/26/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The revision to the first floor elevation of the new classroom building has resulted in the first floor elevation (2609.77') being less than 12" above the rim elevation of the next upstream sanitary manhole (2609.10'). Provide a backwater valve for the building sewer per Section 710.1, UPC 2006, as amended by the City of Tucson. |
04/29/2013 | ANDREW CONNOR | LANDSCAPE | REVIEW | Passed | |
05/01/2013 | ANDREW CONNOR | NPPO | REVIEW | Passed |