Permit Number: DP12-0062
Parcel: 133165760

Address:
2040 N WILMOT RD

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP12-0062
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2012 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Record the Trail/Drainage Access easement and note the recording data on the plans. This will be required prior to permit issuance.
09/13/2012 PAUL MACHADO ENGINEERING REVIEW Approved To: Hubbard Engineering DATE: September 13, 2012
1840 S. Stapley Dr. Ste 137 Mesa, Arizona 85204

Subject: Sante de Tucson, 2040 N. Wilmot Rd.
Development Package, DP12-0062 (Fourth Review)
T14S, R15E, Section 06

The Development Package (DP) is conditionally approved as follows:

Development Package conditions:

1. All easements and agreements (bleed off pipe) shall be recorded with the sequence numbers shown on the plans.
2. Install a clean-out for the bleed-off pipe adjacent to the Rose Hill/Sante de Tucson property line.
3. Correct the plan view of detail 12 on sht. 8 of 32 for the gabion scour protection. It appears that the bleed-off pipe is draining up stream or that the top and bottom of the banks are reversed or something of that nature.
4. The future near side SVT for Wilmot Rd. is not shown correctly. The stem side of the SVT is 20'.

Drainage Report:
1. The Drainage Report has been accepted by engineering.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/2040 N. Wilmot Rd_DEV-SITE_2-01.0 rev.4