Permit Number: DP12-0062
Parcel: 133165760

Address:
2040 N WILMOT RD

Review Status: Completed

Review Details: RESUB - SITE/GRADING ALL

Permit Number - DP12-0062
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2012 MARTIN BROWN FIRE REVIEW Approved
06/20/2012 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Sante Tucson
Development Package (2nd Review)
DP12-0062

TRANSMITTAL DATE: June 21, 2012

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This comment was not addressed. Provide the zoning for all adjacent parcels on the site plan. D.S. 2-01.3.9.F Sheet A-100, all existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined.

2. Until the Wash Ordinance T12SA00195 has been approved by all PDSD agencies Zoning cannot approve the development package

3. Once the above comments have been addressed Zoning is willing to provide an over-the-counter review. Please call or email to schedule an appointment for this review.


If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ DP12-0062

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
06/28/2012 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
07/10/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/16/2012 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The project is subject to the provisions of the Watercourse, Amenities, Safety, and Habitat Ordinance, TCC Ch. 29 Art. VIII, Sec. 29-17. Approval of the application is required prior to Development package approval.

2) The Rainwater Harvesting plan is required to include a Water Budget. See DS 10-03.4.1. Provide calculations per DS 10-03, Exhibit A Table A-1.

3) Record the easement(s) for trail and maintenance access on sheet A-100 and note the recording data on the plans. This will be required prior to permit approval.

The seperate proposed easement for the protected riparian area on site can just be included in the public easements discussed above. A seperate easement is not necessary. The plans can remain the same except that only the term "easement" should be removed from demolition note 6 wherever it appears on the plans.
07/17/2012 RONALD BROWN H/C SITE REVIEW Denied 1. I'm confused about the loading zones. Do you have a passenger loading zone at the front entrance and on the north side of the building. An accessible passenger loading zone is required at one of these areas, preferably at the front entrance. Please provide as per the 2006 IBC, Section 1106.7 and ICC A117.1, Section 503. Make it look like figure 503.3 with a 5' widwe marked, secured area out of the PAAL.
2. You missed the dectectable warnings at the marked crossing at the West enterance of the facility.
END OF REVIEW
07/17/2012 PAUL MACHADO ENGINEERING REVIEW Denied comments to be posted 18JUL12
07/17/2012 JOE LINVILLE NPPO REVIEW Approved
07/17/2012 PAUL MACHADO ENGINEERING REVIEW Denied To: Hubbard Engineering DATE: July 20, 2012
1840 S. Stapley Dr. Ste 137
Mesa, Arizona 85204

Subject: Sante Tucson, 2040 N. Wilmot Rd.
Development Package, DP12-0062 (Second Review)
T14S, R15E, Section 06

RESUBMITTAL REQUIRED: Development Package and Drainage Report.

The Development Package (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Package:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. The project is subject to the provisions of the Watercourse, Amenities, Safety, and Habitat Ordinance, TCC Ch. 29 Art. VIII, Sec. 29-17. The plan will be approved when all provision given on the first submittal are satisfied.
3. Clarify the easement(s) for trail and maintenance access on sheet A-100. The plans shows both a 25' trail easement and a 53' trail easement. When the easements are approved by Engineering, record the easements in favor of the City of Tucson and note the recording data on the plans.
4. See additional comments on the "redlines" on the plan sheets. Include the "redlines" on the re-submittal for comparison.
5. A mitigation plan will be required for any disturbance in the resource area. Upon our telephone conversation, the engineering dept. will help facilitate/expedite the mitigation review in order to avoid a lengthy review time.


Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. A drainage maint./Trail esmt. will be required along the Rose Hill Wash per S.M.D.D.F.M. 1.5.1. Combine both easements with the correct description and the recorders sequence no.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/2040 N. Wilmot Rd_DEV-SITE_2-01.0 rev.