Permit Number: DP12-0061
Parcel: 99999999A

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0061
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2012 KAY MARKS COT NON-DSD ADDRESSING Passed
04/30/2012 RBROWN1 ADA REVIEW Passed
05/02/2012 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The site is required to include screening per LUC Table 3.7.2-I. Revise as the site and landscape plans as necessary to clarify compliance. LUC 3.7.3 & DS 2-06.3.7.

2) Additional screening is required to screen the parking lots from adjacent streets and residentially zoned properties (within 100 feet) and a 5' high screen is required along Gollob Rd, instead of a 30" high screen.

3) A Native Plant Preservation is required for all off site work. These plans should be submitted with the development package. LUC 3.8

4) Revise the Native Plant Preservation to delete the planting plan layer.

5) Coordinate the landscape plan notes and the grading plan relative to water harvesting basins. The grading plan includes a specific keynote for water harvesting landscape areas (used sparingly) while the landscape plan indicates that all landscape areas will be depressed 6".

6) Provide additional plantings for the retention /detention basins inaccordance with the Stormwater Detention-Retention Manual. DS 10-03. Inert groundcover alone should not comprise over 35% of the total basin area. (p.95)
05/10/2012 CHRIS POIRIER PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 2ND FL
TUCSON, AZ 85701-1207

AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: DP12-0061 THE PLACE AT PRESIDIO TRAIL/DEVELOPMENT PLAN
DATE: May 29, 2012



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1. On all title blocks include the section, township and range, the legal description and the apartment and building numbers.


Reason(s) for denial:

A brief legal description of the property, including lot numbers, subdivision name and recording information, section, township and range reference (G & S R M, Pima County, Arizona)
Development Plan Checklist Requirements (Per Chapter 18.71) II I 3

Please contact Audrey Farenga at 740-6800 for questions regarding this comment letter.
A denial may be appealed by contacting Thomas Drzazgowsaki at 740-6675.
No time frames are currently in effect for this process.
05/14/2012 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
05/18/2012 JOE LINVILLE NPPO REVIEW Denied See Landscape Comments.
05/22/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A separate permit is required for the installation of a private sewer collection system and private manholes. Reference: Title 18, R18-9-E302, 4.02 General Permit, Arizona Administrative Code.
2. Indicate which buildings will require the installation of a backwater valve to protect the fixtures located on the first floor (e.g. buildings 1, 8, 9, 14, and the maintenance garage). Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson.
05/22/2012 RONALD BROWN H/C SITE REVIEW Denied SHEET 9
1. Zoning will require pedestrian walk ways to all three public right of ways.
a. These walk ways are to be accessible and comply with all the requirements for accessibility as per the 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition.
b. Marked crossing complete with detectable warnings shall be provided for accessible routes crossing a PAAL.
2. All accessible route slopes are to comply with ICC A117.1, Section 403.3, 5% max running and 2% max cross slopes.
3. Please show accessible route and accessible exits of and to swimming pool and all other resident amenities.
4. Please comply with ICC A117.1 section 405 Ramps, for all accessible routes with slopes greater than 1:5 (20%). Include all landings and handrails. Provide a handrail elevation with all required dimensions and designs.
SHEET 14
5. Please provide reduced vertical clearance as required by ICC A117.1, Section 307.4 at all stairways.
6. Please provide stairway details showing compliance with the 2006 IBC, sections, 1009 and 1012 along with ICC A117.1, Section 504 and 505. Include all riser and tread minimuns as per code.
SHEET 16
7. At detail "H": detectable warnings are not required at accessible parking aisles. These are considered safe zones.
END OF REVIEW
05/23/2012 LOREN MAKUS ENGINEERING REVIEW Denied 1. Review spot grades and slopes to make sure they are consistent. For example on sheet 10 the sidewalk is labeled as sloping downward but the spot grade where it joins the adjacent sidewalk appears to be higher.
2. The site plan shows building constructed over the abandoned alleyway subject to easements. Provide evidence that the buildings are not incompatible with the easements.
3. I recommend that you evaluate the FFEs for each structure as compared to adjacent grades.
4. Clarify in the table on page 6 of the drainage report that the retention volumes are in cubic feet and not square feet.
5. Provide a discussion within the drainage report showing how all of the requirements for underground retention systems in the retention detention manual 3.5.5 and the drainage manual section 14.5. Include details for maintenance access and sediment chambers.
6. Note that the plat must be approved before the development package is approved.
05/23/2012 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP12-0061
9193 E. Old Spanish Trail
Development Package

TRANSMITTAL DATE: 05/23/12

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This project cannot be approved until the final plat, S12-017, has been completed and approved.

2. DS 2-01.2.9 A legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet.

3. DS 2-01.3.2.B The title block shall include the following information.
A brief legal description

4. DS 2-01.3.3 Case number DP12-0061 has been assigned to this development package (DP). Please place this number in the right corner of all sheets of the development package, landscape plan, NPPO, and any other associated sheets.

5. DS 2-01.3.5 When the development package documents consists of more than one (1) sheet, a sheet index (a legible drawing of the site showing the area represented on each sheet) is to be placed on the cover sheet or the second sheet.

6. DS 2-01.3.7.A.6.b In general note number 4 add the following: Sec. 2.8.4 Gateway Corridor Zone

7. DS 2-01.3.9.F Provide the zoning classification for the adjacent property along the east boundary of the project. Zoning is SR.

8. DS 2-01.3.9.H.5.d Keynote #10 indicates the bicycle parking detail is on O/16, the detail is on O/17. Revise keynotes.

Detail O/17 is incorrect as far as the spacing between the short term racks. Per LUC Sec.
3.3.9.2.B. 6. Each required short-term bicycle parking space must be at least two (2) feet by six (6) feet therefore requiring 4' between racks. Revise detail.

Per LUC Sec. 3.3.9.2.B.7 A bicycle rack must be a minimum of two and one-half (2½) feet from a wall or other obstruction. Revise detail.

9. DS2-01.3.9.O Provide a dimension from the proposed carport covers to the back of future curb along Old Spanish Trail, to the edge of the nearest travel lane along Gollob Road, and to the east property line.

The carports along the east property line does not appear meet the required setback. Per LUC Sec. 3.2.6.4 a project with a perimeter yard indicator of CC adjacent to a SR zoned property requires a setback of 25'. FYI: An accessory structure can be approved closer than the required setback by obtaining written permission from the adjacent property owners. This permission must be provided on the site plan.

In the zoning development criteria on sheet 1/39 note #5, revise the required setback for the east property line from "20' or H" to "25'.

10. DS 2-01.3.9.Q Provide overall dimensions and height on the footprint of each proposed building.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP12-0061.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/24/2012 MARTIN BROWN FIRE REVIEW Approved
05/24/2012 PGEHLEN1 WWM REVIEW Denied PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


May 9, 2012

To: TRI MILLER
RICK ENGINEERING

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: THE PLACE AT PRESIDIO TRAILS
Development Plan - 1st submittal
DP12-0061

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:

1. Obtain a letter from the PCRWRD's Development Liaison Unit, written within the past year, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/developer.htm#permits

The development plan for this project cannot be approved until a copy of this letter has been received by this office. Ref. A

2. Sheet 1: Revise General Note # 12 to read as follows (Ref. A):

THE ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.
3. Sheet 23: Call out the slope of the proposed public sewer line segment downstream of proposed public MH #6. Ref. A


This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second(2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.





cc: Chad Amateau, PE Checked by:_________
Kristin Greene, PE, DLU Manager
DLU Project folder

Ref. A. Development Plan Checklist Requirements - Chapter 18.71 of the Pima County Code - Section J
http://www.pimaxpress.com/SubDivision/Documents/2006/DP_Requirements2Aug04.pdf

Ref. C - Arizona Administrative Code, Title 18, Chapters 5 & 9 (R18-5-205)
http://www.azsos.gov/public_services/Title_18/18-05.htm
and (R-18-9-E301)
http://www.azsos.gov/public_services/Title_18/18-09.htm

Ref. D - PCRWRD Procedures, Preliminary Sewer Layout Requirements, 1984 (revised April 1988)
http://www.pima.gov/wwm/eng/stddet/pdf/procedures.pdf

Ref. E - PCRWRD Design Standards for Public Sewerage Facilities, 1983 (revised April 1988)
http://www.pima.gov/wwm/eng/stddet/pdf/design_standards.pdf

Ref. F - City of Tucson/Pima County Standard Details
http://www.pima.gov/wwm/eng/stddet/pdf/all_det.pdf

Ref. G - Pima County Code of Ordinances, Title 13 - Public Services, Division II - Sewers
http://library.municode.com/index.aspx?clientID=16119&stateID=3&statename=Arizona

Ref. H - City of Tucson/Pima County Standard Specifications for Public Improvements, 2003 Edition
http://dot.pima.gov/transeng/stdspecsdet/standardspecs2003.pdf

Ref. I - PCRWRD Engineering Directives
http://www.pima.gov/wwm/eng/directives/
05/25/2012 JWILLIA4 ZONING-DECISION LETTER WRITE DECISION LETTER Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

May 25, 2012

Tri Miller
Rick Engineering Company Inc.
3945 E. Fort Lowell Road Suite 111
Tucson, Arizona 85712

Subject: DP12-0061 THE PLACE AT PRESIDIO TRAILS Development Package

Dear Tri:

Your submittal for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 3 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE ROLLED

3 Rolled Copies of Revised Development Package

2 Copies of Revised Drainage Report

1 CD containing All Plans and Documents of Resubmittal

1 Check made out to “Pima County Treasurer” for $100.00 (Wastewater)


Should you have any questions, please call me at 837-4893.

Sincerely,



John Williams
Planning Technician

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/

Via fax: (520)

Final Status

Task End Date Reviewer's Name Type of Review Description
06/08/2012 CPIERCE1 OUT TO CUSTOMER Completed