Permit Number: DP12-0050
Parcel: 11205283E

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP12-0050
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2012 RBROWN1 ADA REVIEW Passed
04/17/2012 C.C. PATEL WWM REVIEW Passed
04/18/2012 RONALD BROWN H/C SITE REVIEW Denied 1. Please retain the existing marked crossing from the Campbell and Glenn Street public right of ways.
2. Please explain how access from the accessible parking aisle to the accessible route to the front door is acheived.
a. Please provide a large scale detail of the actual designed accessible parking showing all accessible requirements. Detail 4/A-03 present generic details that do not reflect the actual accessible parking conditions and are not applicable.
END OF REVIEW
04/20/2012 LOREN MAKUS ENGINEERING REVIEW Denied 1. Revise the trash enclosure detail and on the plan view to show the required bollards along the back and side walls of the enclosure. (DS 6-01.5.2.B)
2. Provide a complete site plan showing how this project fits within the overall shopping center site.
3. The photo of the existing site shows an existing solid waste container location near the proposed new enclosure. Show how the two will be compatible or show the other enclosure being removed.
4. Since this site plan is incomplete, additional comments may be forthcoming on the next review.

Loren Makus, EIT
Senior Engineering Associate
loren.makus@tucsonaz.gov
04/23/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a site drawing that includes the following information:
a. the location and size of the water meter and backflow preventer
b. the location of the main water lines and fire hydrants
c. the location of the gas meter (if one exists or is planned)
d. the location and size of the public sanitary sewer
e. the location of the building connection to the public sewer
f. the location, invert, and rim elevation of the upstream and downstream manholes and cleanouts
g. the first floor elevation for the building
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
05/09/2012 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP12-0050
2800 N. Campbell Avenue
Development Package

TRANSMITTAL DATE: 05/10/12

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Provide two copies of the last approved site plan, clearly indicating the existing required and provided parking calculations for the entire shopping center, the existing Floor Area Ratio (FAR), existing building expansion calculations, etc.

Provide on the submitted site plan the revised required and provided parking calculations for the entire shopping center, the new FAR calculation, percentage of cumulative building expansion.

2. If the above cannot be provided then a development package would be required for the entire shopping center meeting the requirements of Development Standard 2-01.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP12-0050.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
05/11/2012 ANDREW CONNOR NPPO REVIEW Passed
05/11/2012 ANDREW CONNOR LANDSCAPE REVIEW Passed
05/25/2012 MARTIN BROWN FIRE REVIEW Approved Please indicate exiting fire hydrant location(s), with dimensions to building(s) and/or property lines. Refer to City of Tucson amendments to the 2006 International Fire Code (section 508) for spacing and location requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2012 CPIERCE1 OUT TO CUSTOMER Completed
05/31/2012 GERARDO BONILLA REJECT SHELF Completed