Permit Number: DP12-0038
Parcel: 113080740

Address:
1119 E GLENN ST

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP12-0038
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2012 CAGUILA1 START PLANS SUBMITTED Completed
10/10/2012 RONALD BROWN ZONING HC REVIEW Denied SHEET 1
1. At the marked crossing:
a. Delete the flared ramp sides and provide a return curb.
b. Provide detectable warnings ap required by ICC A117.1, Sections 406.12, 13 and 14.
c. Reference the large scale detail on sheet 2.
2. At the accessible parking space:
a. Indicate the accessible parking and aisle areas to have a maximum of 2% slope in all directions as required by ICC A117.1, Section 502.5.
b. Reference to the large scale detail on sheet 2.
3. Provide an accessible route directly to the interior court yard w/o having to access through a building.
4. All new accessible route slopes are to be 5% maximum running and 2% maximum cross slopes as required by ICC A117.1, Section 403.3.
SHEET 2
5. All accessible requirements for this project are to comply with the 2006 IBC, Chapter 11 and ICC A117.1, 2003 Edition.
a. Please replace all ADA and ADAAG references to that as stated above.
6. At the marked crossing detail:
a. Flared sides on the ramps are not required for this configuration. They may be removed and replaced with return curbs to the top of the ramp -or- if so desired, retain the flared ramp sides and comply with ICC A117.1, Section 406.3 and maintain a minimum slope of 1:10.
b. Detectable warning strips are to be placed 6" to 8" from the curb line and are to be as wide as the marked crossing and 24" deep in the direction of travel as required by section 406.12, 13 and 14.
7. At the accessible parking detail:
a. Show 2% maximum slope in all directions for all areas of the accessible parking space and aisle.
b. Please indicate the rise of the ramp. If more than 6" then grab bars are required as per ICC A117.1, Section 405.8.
c. Show the location iof the accessible parking sign.
8. At the sign detail: The reserved sign and the Van Accessible sign are normally separate signs. COT DOT standards require that the bottom of the larger sign (Reserved Parking) to be at a minimum of 7'-0" above finished grade.
END OF REVIEW
10/12/2012 STEVE SHIELDS ZONING REVIEW Approved CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Little Ranch Preschool
Development Package (2nd Review)
DP12-0038

TRANSMITTAL DATE: October 12, 2012

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section approves the development package for this project. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ DP12-0038

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
10/15/2012 PGEHLEN1 COT NON-DSD ENVIRONMENTAL SERVICES Approved The project drawings are approved for solid waste and recycle enclosure and storage.






Jeff Drumm, P.E.
Environmental Manager
City of Tucson Environmental Services
520-837-3713
10/17/2012 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
10/18/2012 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702

WR#249929 October 17, 2012

A2 Studio Architecture
Attn: Aaron Katz
4009 E Poe Street
Tucson, Arizona 85711

Dear Mr. Katz :

SUBJECT: Little Ranch Preschool
DP12-0038

Tucson Electric Power Company has reviewed and approved the development plan submitted October 2012. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

There are two poles shown on Development Plan that do not appear to be in conflict with any new development. There are also two poles (not shown on Development Plan) thare are south of property line in road right-of-way that do not appear to be in conflict with any new development. There is an OH service that runs from pole unit #231 that currently feeds property. If service goes over any structure and does not meet proper clearances it will need to be relocated.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Mr. Richard Harrington
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8726

Should you have any technical questions, please call the area Designer Jennifer Crawford at (520) 917-8708.

Sincerely,


Elizabeth Miranda
Office Support Specialist
Design/Build
lm
Enclosures
cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
J. Crawford, Tucson Electric Power
10/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Tucson Water will require the installation of backflow protection for the water service to the buildings. Revise the site drawing to include a note requiring the property owner to arrange for the installation of the backflow protection with Tucson Water. (Contact: Mark Titus, 837-2248). Approval of the development plan can be done over the counter after the note is added to the site plan.
10/23/2012 PAUL MACHADO ENGINEERING REVIEW Approv-Cond To: Arron Katz, AIA DATE: October 23, 2012
4009 E. Poe Street Tucson, Arizona 85711

Subject:Little Ranch Pre-School, 1119 E. Glenn Street
Development Package, DP12-0038 (Second Review)
T13S, R14E, Section 31

RESUBMITTAL REQUIRED: Engineering: None.

The Development Package (DP) is approved conditionally. Please address the following review comments.

Development Package:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Information on Proposed Development. The following information on the proposed project shall be shown on the drawing or added as notes. D.S. 2-01.3.9.
H. Proposed traffic circulation:
1. Proposed traffic circulation will be designed in accordance with Street Development Standard 3-01.0, to include streets, intersections, street names, right-of-way widths, curve radii of centerlines and curb returns, and proposed improvements, such as pavement, curbs, access points (driveways), handicap ramps, and sidewalks. Street improvements, such as sidewalks, curbs, pavement, and handicap ramps, do not need to be drawn on the plan if such information is provided on typical street cross sections.
2. Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section. See "redlines" for proper location and addition of exist. SVT's. See following comment.
I. Show all right-of-way dedications on or abutting the site and label. If the development package documents have been prepared in conjunction with a subdivision plat or is required as a condition of approval of a review process, such as a rezoning, street dedications in accordance with the Major Streets and Routes (MS&R) Plan may be required by these processes. Projects bounded by streets having only a portion of the right-of-way width dedicated will be required to dedicate right-of-way, up to one-half (½), to complete the street width. Should there be any proposed street or alley vacation, provide this information. If vacation has occurred, include the recording information. Dedication for the intersection widening is required showing the metes and bounds for the ½ ROW transition from 45' to 32' along the property frontage. Although the future ROW will not be dedicated at this time and TDOT has indicated that it is unlikely that ROW be required to be dedicated any time soon, the MS&R is an ordinance that was adopted by the Mayor and Council and cannot be waived. Hence the ROW shall be shown on the plans but not be required to be dedicated.
O. All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown. Adjust all SVT's accordingly.
9. See additional comments on the "redlines" on the plan sheets. Include the "redlines" on the re-submittal for comparison. Show the ROW as shown on the previous redlines.

Drainage Statement:
1. The DS has been accepted by engineering.

If you have any questions/comments, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/1119 E. Glenn St_DEVPKG-_2-01.0-R2
10/23/2012 PGEHLEN1 COT NON-DSD TUCSON POLICE DEPARTMENT Approved I have no issues with this request/proposal.

CSO Becky Noel #37968
Tucson Police Dept
837-7428
10/23/2012 ANDREW CONNOR LANDSCAPE REVIEW Approved
10/23/2012 PGEHLEN1 WWM REVIEW Approv-Cond Revise notes as discussed at counter with Kristin Greene.
10/24/2012 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied This review has been completed. Revisions are required.
10/24/2012 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Approved PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

DP12-0038 Little Ranch_GlennSt.

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other - Elevations

CROSS REFERENCE: SE12-62 Little Ranch_GlennSt

NEIGHBORHOOD PLAN: Cragin-Keeling Area Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: Oct. 23, 2012

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies with Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on: 5/22/12
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other


REVIEWER:msp 791-5505 DATE: 10/23/12

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2012 CPIERCE1 REJECT SHELF Completed