Permit Number: DP12-0027
Parcel: 119046070

Address:
502 W AJO WY

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP12-0027
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; revise the site drawing to include the following information:
a. the location and size of the water meter and backflow preventer
b. the location of the main water lines
c. the invert and rim elevation of the upstream and downstream manholes and cleanouts
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
06/15/2012 PAUL MACHADO ENGINEERING REVIEW Approved
06/18/2012 CPIERCE1 ZONING REVIEW Needs Review
06/18/2012 CPIERCE1 LANDSCAPE REVIEW Needs Review