Permit Number: DP12-0025
Parcel: 14121024K

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP12-0025
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2012 CPIERCE1 START PLANS SUBMITTED Completed
03/08/2012 RONALD BROWN ADA REVIEW Passed
03/14/2012 MARTIN BROWN FIRE REVIEW Approved
03/19/2012 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
03/26/2012 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Within a vehicular use area, one (1) canopy tree is required for each 4 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.

2. The site, grading and landscape plans must show identical site layout to avoid conflict between the plans. Ensure that all changes to the site and grading plans are reflected on the landscape plan.

3. Additional comments may apply.
03/26/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/28/2012 ANDREW CONNOR NPPO REVIEW Approved
04/02/2012 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP12-0025
9245 E. Old Vail Rd.
Development Package

TRANSMITTAL DATE: 04/03/2012

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-01.3.3 This project has been assigned case number DP12-0025. Place this number in the lower right corner of all sheets.

2. DS 2-01.3.4 On the location map indicate the location of the railroad.

3. DS 2-01.3.7.A.4 In general note number 3 of zoning and land use notes remove the "subject to section 6.3.5".

Remove from the building footprint on all sheets the reference to " production area". This project has been submitted a transportation service not a manufacturing use.

4. DS 2-01.3.7.A.6.b In general note #4 of the zoning and land use notes, add the following:
1. This project shall be designed to meet the criteria of the NCD-A 65 within the Davis Monthan Airport Envrions Zone.
2. This project shall be designed to meet the criteria of the ADC-2 within the Davis Monthan Airport Envrions Zone.
a. No more than twenty (20) employees per acre of site area at any time may be accommodated by intention, design, or in fact.

5. DS 2-01.3.7.A.9.a Provide the square footage and dimensions for all buildings on the site. Missing for the storage building and covered yard building north of the existing main structure.

Provide documentation that the above two buildings have been permitted. Per the aerial photos there appears to be an additional storage container at the north east corner of the property and a building in the middle of van and bus parking area. Clearly indicate if these are to be removed or permitted. All additional square footage must be included when providing parking calculations.

6. DS 2-01.3.7.A.9.b Per LUC Sec.2.8.5.B.1.a The maximum allowed Floor Area Ratio (FAR) in the ADC-2 is 0.30. Revise FAR calculations.

7. DS 2-01.3.7.A.9.c Provide the building expansion calculations for the additional structures listed in comment #5.

8. DS 2-01.3.8.B If applicable, provide the recordation information, location, width and purpose of all easements on the site plan.

9. DS 2-01.3.9.H.5.d Provide a dimensioned detail of the long term bicycle parking space including the required access aisle.

Provide a dimensioned detail of the long term bicycle locker.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP12-0025.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents


04/04/2012

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
04/03/2012 RONALD BROWN ZONING HC REVIEW Denied SHEET 2
1. Delete the detectable warning strips at the accessible parking aisles. They are not required at this location.
2. At note 5: Delete all reference to PC/COT 207 and ADA standards. As per your cover sheet, general note 5, the governing accessibility code is the 2006 IBC/ICC 117.1. Substitute this code reference and add sections 405 and/or 406 as appropriate. Detectable warning strips are as per Sections 406.12, 13, 14 and 705.5.
3. Change note 3 to read: Marked Crossings are as per ICC A117.1, Sections 406.12 and 106.5.
4. At the curb ramp located south of the Production Building:
a. Flared sides are not required at this situation. Please delete the flared sides and provide return curbs.
or
b. Provide the flared side as per section 406.3 with a minimum slope of 1:10.
SHEET 4
5. At detail 10, please indicate that the accessible parking aisle has a flush access to the concrete walk accessible route.
END OF REVIEW
04/06/2012 PAUL MACHADO ENGINEERING REVIEW Denied To: The WLB Group, Inc. DATE: April 12, 2012
4444 E. Broadway Blvd. FROM: Paul Machado
Tucson, Arizona 85711 Engineering Division

Subject: 9245 E. Old Vail Road
Development Package, DP12-0025 (First Review)
T15S, R15E, Section 27

RESUBMITTAL REQUIRED: Development Package and Drainage Statement

The Development Package (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Package:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. The title block shall include the following information. D.S. 2-01.3.2.
A. The proposed name of the project or subdivision, or if there is no name, the proposed tenant's name.
B. A brief legal description and a statement as to whether the project is a resubdivision are to be provided. On resubdivisions, provide the recording information of theexisting subdivision plat.
C. The number of proposed lots and common areas are to be noted. If the subdivision is a Residential Cluster Project (RCP), a condominium, or a similar type of residential subdivision utilizing special provisions of the LUC, it shall be so noted.
D. The administrative street address.
3. Relevant case numbers (development package document, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. D.S. 2-01.3.3.
4. General Notes. The following general notes are required. Additional notes specific to each plan are required where applicable. D.S. 2-01.3.7.
6. List special exceptions, zoning variances, zoning and development standard modifications, overlay zones, and other reviews that are applicable to the project.
a. List special exceptions, variances, and modifications such as Sec. 2.8.10.8, Modification of Development Regulations (MDR), Sec. 5.1.7, Board of Adjustment (BOA), Sec. 5.1.8, Design Review Board (DRB), Sec. 5.1.9, Historical Commission, Sec. 5.1.10, Historic District Advisory Board (HDAB), Sec. 5.3.4 and 5.3.5, a Design Development Option (DDO), 5.3.9 Special Exception Land Uses, Sec. 5.4.1 and General Legislative Procedures, and 5.4.3 Zoning Examiner Legislative Procedure (SE), or DS 1-01.0, Development Standard Modification Request (DSMR), by case number, in lower right corner of each sheet. As a general note provide the case number, date of approval, what was approved, and the conditions of approval.
b. List overlay zones that are applicable to the property, such as Sec. 2.8.1, Hillside Development Zone (HDZ); Sec. 2.8.2, Scenic Corridor Zone (SCZ); Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone; Sec. 2.8.4, Gateway Corridor Zone; Sec. 2.8.5, Airport Environs Zone (AEZ); Sec. 2.8.6, Environmental Resource Zone (ERZ); Sec. 2.8.7, Downtown Heritage Incentive Zone; Sec. 2.8.8, Historic Preservation Zone (HPZ), 2.8.9 Drachman School Overlay (DSO), or 2.8.10 Rio Nuevo And Downtown (RND) of the LUC; or Sec. 29-12 through 29-19 Watercourse Amenities, Safety, and Habitat (WASH) Ordinance of the Tucson Code, by case number, in lower right corner of each sheet. As a general note state that the project is designed to meet the overlay zone(s) criteria, and provide the case number, date of approval, what was approved, and conditions of approval. If there is more than one (1) lot within the site, the note should specify which lots are affected by the overlay zones. Projects involving Historic Preservation Zones, Downtown Heritage Incentive Zones (involving demolition), or overlay

5. Existing Site Conditions. The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within fifty (50) feet of the site. On sites bounded by a street with a width of fifty (50) feet or greater, the existing conditions across the street will be provided. D.S. 2-01.3.8.
A. Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.
B. All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.
C. The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.
F. Existing storm drainage facilities on and adjacent to the site will be shown.
G. If the project is to be phased, provide calculations, setbacks, etc., to indicate that each phase complies with all requirements as a separate entity. Show phase lines on the drawing. Show and label any temporary improvements that may be needed to make the site function for each phase as one entity. If such temporary improvements are off
the site of the phase under consideration, a temporary easement or other legal documentation to assure legal use of the property is required. Note recording information.
H. Proposed traffic circulation:
2. Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.
4. Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.
a. Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include theratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Development Standard 3-05.0.
c. Show all loading zones, and vehicle maneuverability fully dimensioned, and access route, and provide, as a note, the number of loading spaces required, the number provided, and the design vehicle.
d. Show bicycle parking facilities fully dimensioned. For specifics, refer to Development
J. If street dedication is not required or proposed and the project site is adjacent to a Major Street or Route, draw the Major Street right-of-way lines for those streets. (Add the MS&R future sidewalk, right-of -way lines, sight visibility triangles, etc.)
L. All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private.
N. In conjunction with a drainage report or statement, as applicable, prepared inaccordance with the City Engineer's instructions and procedures, the following information will be indicated on the development package documents. For additional information regarding drainage standards, see the City of Tucson Standards Manual for Drainage Design and Floodplain Management.
1. Show areas of detention/retention including 100-year ponding limits with water surface elevations.
3. Provide locations and types of drainage structures, such as, but not limited to, drainage crossings an pipe culverts.
4. Indicate all proposed ground elevations at different points on each lot to provide reference to future grading and site drainage.
5. Verification will be provided that any drainage solutions which occur outside the boundaries of the development document area are constructed with adjacent owners' permission. (Additional notarized documentation of that approval will be submitted with the drainage report.)
7. Draw locations and indicate types of off-site runoff acceptance points and/or onsite
runoff discharge points.
O. All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.
P. The following Pima County Wastewater Management information will be indicated on the development package documents.
Q. Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).
T. Show existing or proposed pedestrian circulation along abutting rights-of-way. Such sidewalks must comply with accessibility requirements for the physically disabled and the design criteria in Development Standard 3-01.0. Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Development Standard 6-01.0. Refuse collection on all projects shall be designed based on that Standard, even if collection is to be contracted to a private firm.

Drainage Report:
1. The DR has been accepted by engineering.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
C:9245 E. Old Vail Rd.
04/09/2012 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed Planning has no comments and passes. Thanks!
04/12/2012 GBONILL1 ZONING-DECISION LETTER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2012 GERARDO BONILLA REJECT SHELF Completed