Permit Number: DP12-0019
Parcel: 110090330

Review Status: Completed

Review Details: RESUB - SITE/GRADING ALL

Permit Number - DP12-0019
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2013 RONALD BROWN H/C SITE REVIEW Passed
03/26/2013 RONALD BROWN ADA REVIEW Denied SHEET AS1
1. Please provide panic hardware on the new gate as required by the 2006 IBC, Section 1108.1.9. Reference note 11.
2. In reference to Previous review comment 2, there is a zoning requirement that will not allow decomposed granite for pedestrian walk ways. Please reference the last comment of the zoning reviewer's (Steve Shield) first review.
3. Detail 10/AS2 references the accessible parking sign to the civil drawings. The Civil drawings sheet C-3, note 11 and detail 6, reference back to the architectural drawings.
a. Please provide a large scale detail of the accessible parking sign as per the requirements of COT DOT. Section 307.3 of the 2010 ADASAD as noted is fine as a general sign minimum standard however Section 502.6 is more specific to accessible parking heights as a minimum. The COT DOT standards are 7'-0" to the bottom of the main sign.
END OF REVIEW
04/11/2013 MARTIN BROWN FIRE REVIEW Approved
04/11/2013 JASON GREEN ENGINEERING REVIEW Denied DATE: April 11, 2014
SUBJECT: Fort Lowell Park Development Plan Package- 2nd Engineering Review
TO: John Mirto
LOCATION: 5444 E Fort Lowell Rd T13S R14E S35 Ward 2
REVIEWERS: Jason Green, CFM
ACTIVITY: DP12-0019


SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the proposed Development Plan Package, Drainage Statement (Kimley-Horn and Associates, Inc., 20FEB12), Geotechnical Report (Terracon, 04AUG11) and Stormwater Pollution Prevention Plan (Kimley-Horn and Associates, Inc.,06NOV12). Engineering Division does not recommend approval of the Development Plan Package at this time. This review falls under Development Standard 2-01. All comments reflect Site Plan, Grading Plan and Storm Water Pollution Prevent Plan review. The following items need to be addressed:

SITE PLAN:

1) DS Sec.2-01.3.2: Revise the development plan document and the page number and number of pages within the set to be consistent. For the DP Package portion Sheet 1 of 16, some sheets are missing the page number completely and some sheets repeat the page numbering (example is 2 Sheet 8's and missing Sheets 13-16), revise.

GENERAL COMMENTS:

Please provide a revised Development Plan Package that addresses the comment provided above. For expedite purposes the development plan package can be reviewed over the counter (PDSD Engineering Division comment only) for stamp approval once the comment has been addressed. Please call to schedule an appointment when ready.

For any questions or to schedule meetings call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services Department
04/15/2013 TERRY STEVENS ZONING REVIEW Approved
04/17/2013 JOE LINVILLE NPPO REVIEW Approved
04/17/2013 JOE LINVILLE LANDSCAPE REVIEW Approved