Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP12-0016
Parcel: 132171220

Review Status: Completed

Review Details: SITE

Permit Number - DP12-0016
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2012 MARTIN BROWN FIRE REVIEW Approved
02/09/2012 RBROWN1 ADA REVIEW Passed
02/10/2012 JASON GREEN ENGINEERING REVIEW Approved
02/13/2012 RONALD BROWN H/C SITE REVIEW Denied 1. Connect the West side accessible route to the North side accessible route.
2. Confirm and indicate all accessible route slopes, both new and existing.
3. Provide a marked crossing as per Sections 405, 406.12 and a 406.14 in front of the overhead doors to the warehouse building.
4. Please identify the "Van Accessible parking space as called out on detail 2/C2.
5. Zoning may require a pedestrian access to the Park Av. right of way. If so, please make it an accessible way. Reference Zoning comments.
SHEET C2
6. Please provide a large scale accessible parking sign including the "Van Accessible sign. Please show all sign locations on Sheet C1.
END OF REVIEW
02/21/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The rim elevation of the next upstream sanitary manhole (2496.47') is less than 12" below the first floor elevation (2497.38'). Provide a backwater valve for the first floor building drains per Section 710.1, UPC 2006, as amended by the City of Tucson.
03/05/2012 ANDREW CONNOR LANDSCAPE REVIEW Denied Submittal must meet criteria found within Development Standard 2-01

Ensure that all Zoning and Engineering comments and concerns are addressed.
03/06/2012 ANDREW CONNOR NPPO REVIEW Approved
03/08/2012 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP12-0016
4370 S. Fremont Ave.
Development Package

TRANSMITTAL DATE: 02/08/12

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. It appears that the asphalt is being removed and the parking spaces are being restriped. Provide the width of all PAALs and access lanes.

2. On the site plan, wheel stops are indicated for all vehicle parking spaces. Provide the location of the wheel stops on the handicap parking space detail and the standard parking space detail (1&2 of C-2). Max. 2'-6" from the front of the parking space.

3. FYI: This site does not require a loading zone per LUC Sec. 3.4.5.

4. On detail 6-C-2 the minimum distance between the short term bicycle racks is four (4) feet. See LUC Sec. 3.3.9.5.B.

5. Provide a note on the plan indicating that the 24' gate will remain open during business hours. The parking spaces are required parking spaces and must be accessible to the public.

6. The above comments are minor in nature and can be reviewed over the counter by setting an appointment with me.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP12-0016 .doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/12/2012 CPIERCE1 WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2012 CINDY AGUILAR OUT TO CUSTOMER Completed