Permit Number: DP12-0013
Parcel: 13215001C

Address:
705 E AJO WY

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - DP12-0013
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2012 MARTIN BROWN FIRE REVIEW Approved
02/27/2012 TERRY STEVENS ZONING REVIEW Needs Review Meeting with Swaim & Associates to go over previous comments on this Thursday. Additional comments may apply.
03/05/2012 RONALD BROWN H/C SITE REVIEW Denied SHEET C1
1. OK

SHEET C2
2. At note 20, change the code reference from PC/COT to ICC/ANSI 117.1, Section 406.13 and 705.5
RESUBMITTAL REVIEW COMMENT:
Non-responsive

SHEET X1.1
3. OK

4. Insure the existing ramp (Note 2.4) meets all the accessible requirements of ICC/ANSI 117.1, Section 406.
RESUBMITTAL REVIEW COMMENT:
Non-responsive

SHEET C2, X1.1 AND DETAIL 6/X1.3
5. OK
SHEET X/1.3, DETAILS 5 AND 6
6. OK
END OF REVIEW
03/06/2012 JOE LINVILLE LANDSCAPE REVIEW Denied Previous comments have been addressed. Revise plans as necessary to receive approval from other agencies. Submit any revised plans for additional review.
03/06/2012 JOE LINVILLE NPPO REVIEW Approved
03/06/2012 PAUL MACHADO ENGINEERING REVIEW Needs Review Comments, if necessary, to be posted after the scheduled meeting with the architect to discuss my comments.
03/06/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved