Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2012 GBONILL1 START PLANS SUBMITTED Completed
03/05/2012 JOSE ORTIZ COT NON-DSD TRAFFIC Denied There are two conflicts with the proposed driveway location along Ajo Way.

1. The City of Tucson's Access Management Guidelines requires 80 feet of separation between driveways and limits the number of driveways to two per 300 feet of frontage along any major roadway. The proposed driveway location is too close to the existing driveways to the east.

2. The existing bus stop is located too close to the proposed driveway, which will impact visibility at the proposed driveway when a bus is servicing the stop.

The driveway location needs to be revised. Contact Jose Ortiz with TDOT for options acceptable to the City for driveway locations.


If you have any questions, I can be reached at 520-837-6730 or Jose.Ortiz@tucsonaz.gov