Permit Number: DP11-0024
Parcel: 12112062C

Review Status: Completed

Review Details: SITE

Permit Number - DP11-0024
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2012 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Within a vehicular use area, one (1) canopy tree is required for each 4 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.

2. A 30" continuous screen along street frontages must be provided per LUC Table 3.7.2-I. I. Identify all screening elements on the landscape plans.

3. DS 10-03.0 COMMERCIAL RAINWATER HARVESTING applies to all commercial development plans submitted after June 1, 2010. Provide Rainwater Harvesting Plan.

4. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.

5. Revise maintenance notes to read:

6. MAINTENANCE STANDARDS DS 2-06.6.0

A. Any plant material in areas of required landscaping that does not survive will be replaced with an equivalent size and species within thirty (30) days.

B. Plant material will be pruned as necessary to control size but not to disrupt the natural growth pattern or characteristic form of the plant except as necessary to achieve height clearance for visibility and pedestrian passage or to achieve a continuous opaque hedge if required.

C. Clipping and pruning of the plant material are required to allow maximum shading while preserving surveillance opportunities and preventing obstructive overhang into walks, curb areas, drives, and line of sight triangles.

D. All dead or removed plant material will be replaced with plant material acceptable under the requirements of the xeriscape landscaping regulations. Replacement material will be a minimum fifteen (15) gallon size for trees and five (5) gallon size for shrubs.

7. Additional comments may apply.
01/20/2012 ANDREW CONNOR NPPO REVIEW Approved
01/20/2012 RONALD BROWN H/C SITE REVIEW Denied SHEET AS1
1. At detail 8:
a. Please correct the title
b. If flared sides are to be installed here, please comply with ICC/ANSI 117.1, Section 406.3 that requires a minimum slope of 1:10.
c. If flared side are not used for this ramp, please return the 6" curb to the top of the ramp.
2. At detail 2:
a. Please reference detail 5/As1 that indicates a flush transition condition.
b. Please reference detail 3/AS1
c. Please revise the detail to show the exact conditions as per detail A/AS2. Please show the aisle is part of a marked crossing and provide a deteectable warning strip at the edge of the sidewalk.
3. At detail 3/AS1: Please call out the "Van Accessible" sign.
4. At detail 12:
a. Please show the riser height.
b. Please provide a handrail detail showing compliance with Section 505.
c. Please comply with clearances required by Section 404.2.3.1 and figure 404.2.3.1 (f).
SHEET AS2
5. At keynote 27, please add the detail reference 8/AS1
6. At keynote 23, please add the reference 5/AS2 in lieu of ????
7. At the ramp on the West side of the building:
a. Please provide a complete marked crossing at this crossing of the vehicle access to the building. Please provide a marked crossing stripes, another ramp on the North end and a detectable warning strip.
8. Where a pedestrian crossing is shown from the west side of the building to Rosemont, please provide a marked crossing with proper markings, ramps and detectable warning strips.
9. Insure all accessible route slopes comply with ICC/ANSI 117.1, Section 403.3.
END OF REVIEW
01/20/2012 RBROWN1 ADA REVIEW Passed
01/25/2012 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP11-0024
5101 E. Speedway Blvd.
Development Package - Site Plan

TRANSMITTAL DATE: 01/25/2012

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The indicated "monument" sign located at the southeast corner of the property must be removed prior to approval of the development package. Contact Glenn Moyer @ 837-4954 for further information regarding this sign.

2. DS 2-01.2.4 Provide a title block at the lower right corner of each sheet including the landscape and grading plans.

3. DS 2-01.2.9 A legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet.

4. DS 2-01.3.2.E The title block shall include the following information:
Page number and number of pages. This shall include all pages which comprise the development package including landscape and grading plans. (such as 1 of 6, 2 of 6, etc.)

5. DS 2-01.3.4. The project-location map shall cover approximately one (1) square mile, be drawn at a minimum scale of 3" = 1 mile, and provide the following information.
A. Show the subject property approximately centered within the one (1) square mile
area.
B. Identify major streets and regional watercourses within the square mile area and all
streets that abut the subject property.
C. Section, township, and range; section corners; north arrow; and the scale will be
labeled.

6. DS Sec.2-01.2.5: Revise the development plan document to include the approval stamp in the lower right quadrant of each sheet. The link to the stamp can be found here: http://cms3.tucsonaz.gov/pdsd/cdrc-rezoning/cdrd-stamp

7. DS 2-01.3.7.A.4 In general note number 3 list the proposed use as follows: Automotive - Service and Repair "30", subject to: Sec. 3.5.13.5

8. DS 2-01.3.7.A.b List overlay zones that are applicable to the property, such as Sec. 2.8.3, Major Streets and Routes (MS&R). As a general note state that the project is designed to meet the overlay zone(s) criteria.

9. DS 2-01.3.7.A.9.b Provide the allowed (0.75) and proposed Floor Area Ratio (FAR) for this project. Lot coverage is not required.

10. DS 2-01.3.8.B Provide recording information for all easements including the easement to be abandoned.

11. DS 2-01.3.9.H.1 The indicated backup spur must have a clear area of 3' behind the backup spur. Provide dimension.

The demolition plan indicates curbs being removed along the north and east sides of this property. Clearly indicate how vehicles will be prevented from driving onto the adjacent properties.

Clearly indicate what the portion of the property located east of the proposed building will be used for. Clearly indicate any additional paving being done in this area.

It appears the area east of the building will be used for storage. If this is the case provide some type of barrier or signage preventing the public from accessing this area

12. DS 2-01.3.9.H.5.d The indicated number of long term bicycle parking spaces is incorrect. Per LUC Sec. 3.3.8.2 minimum two long term bicycle parking spaces are required.

Clearly indicate the location, type of locker, access aisle, etc. for the long term bicycle parking spaces inside of the building.

The indicated short term bicycle parking spaces do not meet the requirements of LUC Sec. 3.3.9.5.B., access aisle is measured from the end of the required six foot bicycle parking space.

Relabel the indicated class 2 and class 1 bicycle parking to short term and long term.

13. DS 2-01.3.9.J Provide either the street intersection widening per the MS&R maps or provide documentation from the department of transportation that the intersection widening will not occur.

Clearly indicate the location of the future curb along both Speedway and Rosemont.

Indicate the location of the future sight visibility triangles.

14. DS 2-01.3.9.Q Provide dimensions of the proposed building on the footprint shown on sheet 2 of 3.
15. DS 2-01.3.9.R Chuck, I made a mistake when I told you only one accessible route for pedestrian circulation is required. Per DS 2-08.3.1 Within the pedestrian circulation path, an accessible route must connect to all areas of the development and the pedestrian circulation path located in any adjacent streets.

Clearly indicate the location of handicap ramps and striped cross walks including the cross walk to the trash enclosure.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP11-0024.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
01/25/2012 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied CLEARLY INDICATE ON SITE PLAN SIZE AND LOCATION OF NEW OR EXISTING WATER METERS AND WATER SUPPLY LINES.

CLEARLY INDICATE ON SITE PLAN SIZE AND LOCATION OF ANY EXISTING OR NEWLY PROPOSED SITE SEWER LINES.
01/25/2012 LOREN MAKUS ENGINEERING REVIEW Denied Clarify the proposed use for the areas north and northeast of the new building. Since part of this area is to remain paved and may be accessible by vehicles, the edges of the pavement must be provided with a means to prevent the vehicle from driving onto unpaved surfaces. Delineate the limits of paving in these areas.
01/27/2012 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2012 CPIERCE1 OUT TO CUSTOMER Completed
01/27/2012 GERARDO BONILLA REJECT SHELF Completed