Permit Number: DP11-0023
Parcel: 11515051A

Address:
501 W GRANT RD

Review Status: Completed

Review Details: SITE

Permit Number - DP11-0023
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2012 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Ensure that no conflict exist per the proposed Public Improvement Plans.

2. Ensure that all Zoning and Engineering comments and concerns are addressed.

3. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.

4. All landscape areas will be depressed to accept water flow from roofs, PAAL, and parking areas. Show by detail or spot elevations how landscape areas will accommodate water harvesting.

5. Additional comments may apply upon subsequent reviews
01/18/2012 ANDREW CONNOR NPPO REVIEW Approved
01/18/2012 RONALD BROWN H/C SITE REVIEW Approved
01/20/2012 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP11-0023
501 W. Grant Rd.
Development Package - Site Plan

TRANSMITTAL DATE: 1-19-12

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-01.3.1 Provide the names of the owner and developer along with addresses and phone numbers for this project.

2. DS 2-01.3.2.E The page numbering should include all sheets, such as DP1 of 3, DP2 of 3, etc.

3. DS 2-01.3.7.A.2 In general note #2 list the square footage of the entire site along with the acreage.

4. DS Sec.2-01.2.5: Revise the development plan document to include the correct CDRC approval stamp in the lower right quadrant of each sheet. The link to the stamp can be found here: http://cms3.tucsonaz.gov/pdsd/cdrc-rezoning/cdrd-stamp

5. DS 2-01.3.7.A.4 In general note #3 remove the "subject to 6.3.5".

6. DS 2-01.3.7.A.9.c Provide building expansion calculations.

7. DS 2-01.3.9.H.2 Show all future and existing sight visibility triangles.

8. DS 2-01.3.9.H.5.a Provide dimensioned details of the standard and handicap parking spaces including location of wheel stops.

9. DS 2-01.3.9.H.5.d Provide dimensioned details of the long term and short term bicycle parking spaces including surfacing materials, lighting, type of locker and rack, access aisle, etc. See LUC Sec. 3.3.9 for design criteria.

The number of required bicycle parking spaces per LUC Sec. 3.3.8 for Administrative Offices is minimum 2 short term and 2 long term spaces. Revise calculations and show location of both short term and long term spaces on the site plan.

10. DS 2-01.3.9.J The future MS&R right of way may be indicated incorrectly. The new Grant Rd. widening may or may not require future dedication. Contact Mike Holder with Tucson Department of Transportation and Dorothy Wiedman with Real Estate Division concerning the location of the future right of way along the front of this property.

If future dedication is required, a future site plan will be required to be submitted clearly indicating how this site will meet all codes requirements once the widening occurs. A MS&R Covenant would be required to be recorded. Provide recording information on the site plan along with a note clearly indicating that at the time of widening any changes to this site will be at no expense to the City of Tucson.

11. DS 2-01.3.9.O Provide dimensions from property lines and future curb location to each building. Remove the standard 21' setback lines.

12. DS 2-01.3.9.R Provide dimensions for all sidewalks clearly indicating the required width of 4'.

13. DS 2-01.3.9.V Please indicate the location and type of postal service to assure there are no conflicts with other requirements. If mail is to be delivered to an area within a building please state so on the plan.

14. DS 2-01.3.9.W If applicable, indicate the locations and types of proposed signs (wall, freestanding, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP11-0023.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
01/20/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to include the following information:
a. the location of the main water lines and fire hydrants
b. the location, invert, and rim elevation of the upstream and downstream manholes and cleanouts
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
2. Indicate how the existing natural gas service line will be re-routed to accommodate the building addition.
12/21/2011 RBROWN1 ADA REVIEW Passed
12/22/2011 MARTIN BROWN FIRE REVIEW Approved
12/23/2011 JASON GREEN ENGINEERING REVIEW Denied DATE: December 23, 2011
SUBJECT: Integra Group Real Estates Development Plan Package- Engineering Review
TO: CadMan Designs; Attn: Alex Enoch
LOCATION: 501 W Grant Rd, T14S R13E 02 Ward 3
REVIEWERS: Jason Green, CFM
ACTIVITY: DP11-0023


SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the proposed Development Plan Package. Engineering Division does not recommend approval of the Development Plan Package at this time. This review falls under Development Standard 2-01. The following items need to be addressed:


SITE PLAN: It is recommended that Development Standard 2-01 "Development Package" be reviewed prior to resubmittal. DS Sec.2-02 and 2-05 no longer exists and all reviews fall under DS Sec.2-01 for Development Package. The standard has changes that must be incorporated into the plan sheets for review and approval.

1) DS Sec.2-01.2.0: Revise the development plan documents to remove the reference to "Book __ Page __" as shown in the lower right and upper right portions of the plan sheets.

2) DS Sec.2-01.2.5: Revise the development plan document to include the CDRC approval stamp in the lower right quadrant of each sheet. The link to the stamp can be found here: http://cms3.tucsonaz.gov/pdsd/cdrc-rezoning/cdrd-stamp

3) DS Sec.2-01.3.2.D: Revise the title block on the development plan document to include the administrative address.

4) DS Sec.2-01.3.3: The relevant Development Plan Package number (DP11-0023) may be added to the lower right hand corner of the plan on all sheets.

5) DS Sec.2-01.3.5: Revise the plan set to include a sheet index on the first sheet listing the names of each sheet included in the development plan package, to include the Landscape Plan.

6) DS Sec.2-01.3.9.H: Provide approval (email or letter) from TDOT for the future MS&R right-of-way lines as shown. It is acknowledged that the lines match the last approved site plan (T07CM01666) however due to the new Grant Road widening project verification from TDOT is required to ensure that no conflict exist per the proposed Public Improvement Plans.

7) DS Sec.2-01.3.9.T: Provide approval (email or letter) from Environmental Services for the elimination of the existing refuse enclosure and the proposed rollout dumpster. Verify that the rollout meets all requirements within DS Sec.6-01.


GENERAL COMMENTS:

Please provide a revised Development Plan Package that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon re-submittal of the Development Plan Package. For any questions or to schedule meetings call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2012 CPIERCE1 OUT TO CUSTOMER Completed