Permit Number: DP11-0022
Parcel: 13612001P

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP11-0022
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2012 GBONILL1 START PLANS SUBMITTED Completed
09/18/2012 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approv-Cond Conditional approval based on in leui fees. Work with Jose Ortiz for details.
10/01/2012 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: DP11-0022 SORRENTO SQUARE GOODWILL/REVISED DEVELOPMENT PLAN
DATE: September 27, 2012



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar or bond paper of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.
10/02/2012 JASON GREEN ENGINEERING REVIEW Denied DATE: October 2, 2012
SUBJECT: Sorrento Square Goodwill (Phase II) Development Plan Package-2nd Engineering Review
TO: CYPRESS Civil Development; Attn: Kevin Hall
LOCATION: 10240 E Golf Links Rd, T14S R15E 26 Ward 4
REVIEWERS: Jason Green, CFM
ACTIVITY: DP11-0022

SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the proposed Development Plan Package, Drainage Statement (Cypress Civil Development, 31AUG12), Geotechnical Supplemental Recommendation (LMT Engineering Inc., 27AUG12) and Stormwater Pollution Prevention Plan (Cypress Civil Development, 14DEC11). Engineering Division does not recommend approval of the Development Plan Package at this time. This review falls under Development Standard 2-01. All comments reflect Site Plan, Grading Plan and SWPPP review. The following items need to be addressed:

SITE PLAN:

1) Restated: DS Sec.2-01.3.9.L: Revise the plan documents to provide the recordation information for all new and proposed easements in plan view where indicated. Specifically the 1-foot No Access Easement per the Final Plat and the Payless Prudence Properties LLC Sequence #.

2) Restated: DS Sec.2-01.3.9.M: Revise the development plan document to clearly define the limits of grading. Per the documentation provided it appears that the water and sewer line crosses the platted Natural Undisturbed Area (NUA) and neither of the civil sheet or landscape sheet clearly shows the limits of grading to account for this disturbance or the mitigation of the disturbance within the NUA. All areas of platted Natural Undisturbed Areas must provide temporary fencing during the construction phase to prevent parking, storage or other disturbance within these areas.

3) Restated: DS Sec.2-01.3.9.N.2: Revise the development plan documents to clearly label the proposed grate located within the loading dock area. Verify the grate detail and outlet area for the proposed recessed loading dock since the development plan documents are to be used as the construction drawings. At a minimum the proposed grate must have a detail call out to ensure accurate construction.

4) Restated: DS Sec.2-01.3.9.X: Revise the development plan documents to clearly label the required 6-foot high masonry wall all the south perimeter per the property per Rezoning Condition #30. Per the current proposal it is unclear that the new site wall along the south perimeter is continues clarify by moving the grading limit hashing to show the proposed wall location in all areas or provide additional labels to ensure that the rezoning condition is meet.

STORMWATER POLLUTION PREVENTION PLAN: The proposed SWPPP meets the minimum requirements of the AzPDES Construction General Permit (CGP). However the SWPPP and Exhibits can not be stamped approved until approval of the Development Plan Package.

GENERAL COMMENTS:

Please provide a revised Development Plan Package that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon re-submittal of the Development Plan Package. For any questions or to schedule meetings call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services Department
10/04/2012 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: DP11-0022
New Commercial Building - Sorrento Square Goodwill
Development Package

TRANSMITTAL: 10/08/2012

DUE DATE: 10/09/2012

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is 12/19/2012.

2. DS 2-01.3.2.E The page numbers, such as 1 of 3, should include all pages of the development package, such as 1 of 25. The landscape plans shall be included in the numbering sequence.

3. DS 2-01.3.3 Add relevant case numbers to the lower right corner of each sheet. The Special Exception case number once approved.

At the time of this review neither the Final Plat nor the Special Exception have been approved. This Development Package cannot be approved until both have been approved.

4. DS 2-01.3.7.A.6.a Provide a separate note indicating the case number, date of approval and conditions of approval of the special exception.

5. DS 2-01.3.7.A.9.d The calculations for the following do not appear to be correct. Parking calculations, FAR calculations, square footage of all proposed buildings, bicycle parking calculations, loading zone calculations, etc. As well as calculations for this site as a stand alone.

Note this project has been provided with parking calculations per the new LUC requirements (1:300). The tentative plat approved for the rest of the project was parked at 1:200. A change to the tentative plat may be required.

6. DS 2-01.3.9.H.5.d Provide dimensioned details of the long term and short term bicycle parking spaces. Clearly indicate the location, type and size of locker, method of securing, access aisle, etc. for long term spaces.. See LUC Sec. 3.3.9.3 and 3.3.9.4.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\D11-0022dp.doc




Grading notes for permits plus.
With DEVELOPMENT PLAN

10/08/2012

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
10/09/2012 JOE LINVILLE LANDSCAPE REVIEW Approved
10/16/2012 TIM ROWE PIMA COUNTY WASTEWATER Approved PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


September 11, 2012

To: Kevin Hall, PE
CYPRESS CIVIL DEVELOPMENT, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: SORRENTO SQUARE GOODWILL
Dev. Plan - 2nd submittal
DP11-0022

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
The Pima County Regional Wastewater Reclamation Department hereby approves the above referenced submittal of the development plan.
10/16/2012 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied This review has been completed. Resubmittal is required.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/17/2012 CINDY AGUILAR REJECT SHELF Completed