Permit Number: DP11-0017
Parcel: 10409002D

Address:
4329 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - DP11-0017
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2012 JASON GREEN ENGINEERING REVIEW Approved
02/24/2012 ANDREW CONNOR LANDSCAPE REVIEW Approved
03/06/2012 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Buffalo Wild Wings @ Wetmore Plaza
Development Package (2nd Review)
DP11-0017

TRANSMITTAL DATE: March 6, 2012

DUE DATE: March 14, 2012

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is December 08, 2012

2. D.S. 2-01.3.9.H.5.d Remove all references to "CLASS 1 & CLASS II" bicycle parking as it is no longer applicable. For your information D.S. 2-09.0 is no longer applicable.

3. D.S. 2-01.3.9.H.5.d Per LUC Section 3.3.9.2.B.6 Each required short-term bicycle parking space must be at least two (2) feet by six (6) feet. That said the minimum distance between racks is 4'-0" clear. Revise you detail accordingly.

4. D.S. 2-01.3.9.R Provide sidewalk width dimensions for the sidewalk shown on the north side of proposed building and the sidewalk connection to the sidewalk along Oracle Road.

Once the above comments have been addressed Zoning is willing to provide and over-the-counter review. Please call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ DP11-0017

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
03/13/2012 RONALD BROWN HC SITE REVIEW Denied 1. Section 502.5 requires 2% maximum for all surface slopes. Please indicate slope from left to right.
2. Detectable warnings shall be as required by ICC A 117.1, Section 705.5, truncated domes.
a. Please reference ICC A117.1, Sections 406.12, 13 and 14 for detectable warning sizes and locations.
END OF REVIEW
03/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved