Permit Number: DP11-0015
Parcel: 11205030B

Review Status: Completed

Review Details: SITE

Permit Number - DP11-0015
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2011 RBROWN1 ADA REVIEW Passed
12/02/2011 DAVE MANN FIRE REVIEW Denied This comments apply to the job as a whole and will be repeated for all activity numbers.
1) Fire Department approved lock boxes will be required at
sliding gates.
2) Fire sprinklers will need to be installed in building A. Reference 2006 IFC, section 903.2.7.
3) An alarm system will be required in all residential buildings
except those containing fire sprinklers. Reference 2006
IFC, section 907.3.6.
4) Please provide clarification regarding separation between
Building A and Leasing building. Are they connected by
a roof structure? Do they require fire wall separation?
12/14/2011 RONALD BROWN H/C SITE REVIEW Denied SHEET SP1.1
1. As per the 2006 IBC, Section 1106.6, accessible parking spaces shall be dispersed and located near the all the accessible entrances.
a. Please do not locate all the accessible parking spaces in one area.
2. Detectable Warning strips are not required at the accessible parking aisles.
3. Please provide large scale details of of the different typers of accessible parking layoutS and include all required accessible dimensions, slopes, signage, ramps, "Van Accessible" spaces and accessible routes.
SHEET SP1.2
4. Detail 3:
a. Detectable warning strips are not required at accessible parking aisles.
b. Provide large scale details of the exact parking layout as designed and shown on sheet SP1.1.
5. Detail 6:
a. Detectable warning strips are not required at accessible parking aisles.
6. Parlking calculations and Project Scope statistics call out different parking spaces provided. Please reconcile.
7. For 128 parking spaces provided on site, 5 accessible parking spaces are required as per Table 1106.1.
END OF REVEIW
12/20/2011 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: DP11-0015
2002 E. Ft. Lowell Rd.
Development Package

TRANSMITTAL DATE: 12/23/2011

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-01.2.6 The provided location map indicates this project is in Marana, revise to Tucson Az.

2. DS 2-01.3.3 This project has been assigned case number DP11-0015. Place this number near the lower right corner of all sheets.

3. DS 2-01.3.7.A.4 List the existing use as follows: Family Dwelling "P", subject to: Sec. 3.5.7.1.F

4. DS 2-01.3.7.A.9.c Provide expansion calculations clearly indicating the percentage of building expansion for this project.

5. DS 2-01.3.8.C Along Ft. Lowell clearly indicate the location of the future curb. Along Wilson Ave. and Olsen Ave. clearly indicate the ½ right of way width as well as the nearest lane of travel location. Provide dimensions for all of the above.

6. DS 2-01.3.9.H.2 Show correctly the existing and future sight visibility triangles.

7. DS 2-01.3.9.H.5.a Per the last approved site plan this site is considered legal nonconforming for parking, indicating 114 parking spaces being provided. Revise parking calculations to indicate the amount of existing parking (114) and indicate the number of new required parking spaces (3 two bedroom units = 6 parking spaces). The total number of required parking spaces is then 120. Remove note indicating on street parking.

Revise note in the project scope portion of sheet T1.1 in regards to the existing parking.

8. DS 2-01.3.9.H.5.d Provide long term and short term bicycle parking for the 3 additional units. Provide a dimensioned detail of the short term and long term bicycle parking spaces including a detail of the type of racks and lockers being provided. Minimum 2 short term and 2 long term bicycle parking spaces are required.

9. DS 2-01.3.9.O Provide all building setback dimensions to the new construction (porches, additions, clear story additions) portions of this project from the correct property line, back of future curb or the nearest travel lane which ever is required. It appears that the addition at the north west corner of building B is being proposed to be built in the right of way. This is not allowed under any circumstance. If the new porches or additions do not meet the required setback a DDO (Design Development Option) will be required.

If a DDO is applied for and approved provide on the plans the case number, date of approval, what the DDO is for and any conditions of approval.

In the code analysis portion of sheet T1.1 revise the requited setbacks to the correct distances. Street (Ft. Lowell) : 21' or the height of the wall of the structure whichever is greater from the back of future curb. Side Streets (Olsen and Wilson): 21' or the height of the wall of the structure whichever is greater from the edge of the nearest travel lane. Back (or south): 10' or ¾ the height of the wall of the structure whichever is greater.

10. DS 2-01.3.9.Q In the code analysis provide the correct maximum building height (40').

FAR calculation are not required please remove.

Lot coverage calculations are required. Provide the maximum allowed (70%) and the provided. Lot coverage includes all buildings and vehicle use area.

11. DS 2-01.3.9.H.1 Provide the width of the PAAL on the site plan. Minimum width is 24' for a two way PAAL.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\DP11-0015.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
12/29/2011 ANDREW CONNOR NPPO REVIEW Needs Review Ensure that all Zoning & Engineering comments and concerns are addressed prior to Landscape approval.

Additional comments may apply
12/29/2011 ANDREW CONNOR LANDSCAPE REVIEW Needs Review Ensure that all Zoning & Engineering comments and concerns are addressed prior to Landscape approval.

Additional comments may apply
12/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/29/2011 PAUL MACHADO ENGINEERING REVIEW Denied To: architectural design group, inc.DATE: December 29, '11
2510 E. Grant Rd., ste. 140 Tucson, Arizona 85716

Subject: Casa Presidio Apartments, 2002 E. Fort Lowell Rd.
Site plan DP11-0015 (First Review)
T13S, R14E, Section 32

RESUBMITTAL REQUIRED: Development Package and Drainage Statement.

The Development Package (DP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Please provide property description per D.S. 2-02.2.1.3.
3. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. The fut. FOC location for a 100' MS and R is 11' from the fut. R/W line. All SVT's begin at the face of curb with the stem side of the SVT is drawn toward the property, not the street. The SVT dimensions for a local st. to an arterial (Ft. Lowell Rd.): NS = 20'x 340', FS = 20'x 125'. The SVT dimensions for a Drive/PAAL to a Local St. (Olson and Wilson Aves.): NS = 20'x 185', FS = 20'x 110'.
4. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15. Any const. in the FEMA regulated flood plain requires a Flood Plain Use Permit (FUP). Separate FUP's will be required for Bldg. "A" and Bldg. "B". The FUP for the proposed patio wall in the flood plain will be attached to Bldg. "B's" FUP. Submit 2 sets of the site plan, drainage statement along with the FUP application for both buildings.
5. Construction cost estimates are required or shall be included for any improvements to any structures that are attached to Bldg. "A". This includes Bldg. J, Bldg. L and the associated improvements.
6. The construction cost of the improvements shall not exceed 50% of the total appraised/assessed value of the existing structure, not including the land. An appraisal for each bldg. separate from the cost of the land that is located in the FEMA regulated floodplain shall be included with the cost est.
7. Provide a note on the plans indicating that any future construction (covered parking) in the flood plain shall require separate FUP's.
8. List the total disturbed area in sq. feet on the plans.
9. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
10. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. List on the plans if both are "0".
11. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
12. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
13. Provide City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
14. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27. Any const. in the FEMA regulated flood plain requires a FUP. See comment no. 4. Walls constructed in flood plain shall be built with engineered drainage openings.
15. Show Development plan (DP11-0015) number on all sheets per D.S. 2-02.2.1.29.
16. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0. Call out that any new construction done to the existing refuse enclosures shall be per COT Development Standard 6-01.0.
17. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
18. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
19. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers and/or sidewalk scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof drain/sidewalk scupper locations have been designed and located and that the 10-year flow must be conveyed under any other sidewalks and/or pedestrian paths will suffice.
20. List the consulting engineer and the owner/developer on the plans with the pertinent information.
21. A floodplain use permit is required.
22. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
23. "A grading permit may be required for this project depending on the earthwork quantities listed plan. See note no. 10. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".
24. If you would like to discuss the comments prior to the re-submittal of the DP, a meeting can be scheduled to do so. The contact information is listed below.

Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. Show the limits of the 100-year floodplain and water surface elevation in the DS.
3. The construction cost of the improvements shall not exceed 50% of the total appraised/assessed value of the existing structure, not including the land. An appraisal for each bldg. separate from the cost of the land that is located in the FEMA regulated floodplain shall be included with the cost est.
4. Any const. in the FEMA regulated flood plain requires a Flood Plain Use Permit (FUP). Separate FUP's will be required for Bldg. "A" and Bldg. "B". The proposed patio wall in the flood plain will be attached to Bldg. "B's" FUP. Submit 2 sets of the site plan, drainage statement along with the FUP application for both buildings.
5. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted with the re-submittal of the DP.
6. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2.
7. Show the project address or administration address on the cover sheet of the DS.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/ 2002 E. Fort Lowell Rd. Site-DP

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2012 CINDY AGUILAR OUT TO CUSTOMER Completed