Permit Number: D11-0029
Parcel: 11702112A

Address:
1004 N 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D11-0029
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/08/2011 JWILLIA4 PIMA COUNTY WASTEWATER Approved Pima County Regional Wastewater Reclamation Department


Jackson Jenkins
Director
201 N. Stone Ave., 8th Floor
Tucson, Arizona 85701-1207


PH: (520) 740-6500
FAX: (520) 620-0135

December 7, 2011

To: KEVIN HALL
CYPRESS CIVIL DEVELOPMENT

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: MATA RESIDENCE OFFICE
Development Plan – 2nd Submittal
D11-0029

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
The Pima County Regional Wastewater Reclamation Department hereby approves the above referenced submittal of the development plan as submitted.
If you have any questions please call me at the phone number above.


cc: Chad Amateau, PE Checked by:______
Kristin Borer, PE, DLU Manager
DLU Project folder
12/08/2011 JASON GREEN ENGINEERING REVIEW Approved
12/12/2011 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
D11-0029
1004 North Sixth Avenue
Administrative Office


TRANSMITTAL: December 12, 2011


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1) The site is located in the HO-3 zone (LUC Section 2.4.3.2). The proposed use is Administrative Office and the Development Designator is "30" (LUC Sections 3.2.3.2.A.1 and 3.2.3.2.B). The Perimeter Yard Indicator is DD (LUC Section 3.2.6.4).

2) This site is in the HR-3 Zone. Historic review is required (LUC Section 2.8.8.2 & 2.8.8.5). Contact Frank Podgorski at 520-837-4962 or Frank.Podgorski@tucsonaz.gov for historic review.

3) A maximum of one year from the date of application is allowed to obtain approval of a development plan. The one expiration date for this development is August 31st of 2012. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review (LUC Section 5.3.8.2.A).

4) Please be aware that additional comments maybe forthcoming relative to additional information provided with subsequent submittals.
12/14/2011 JWILLIA4 ENV SVCS REVIEW Approved Date Case Number Project Address
December 12, 2011 D11-0029 MATA RESIDENCE OFFICE
DEVELOPMENT PLAN

Comments: The proposed parking lot for the MATA RESIDENCE OFFICE, development Case
No. D11-0029, located at 1004 N. 6th Avenue. Meets the minimum
requirements for Environmental Services Solid Waste and Recycle materials, and is
approved with the following condition.

The following notes must be added to the Development Plan:
1. The owner will be responsible for placing the Solid Waste and Recycle
containers at the locations for cube side and alley service as required.

2. The Solid Waste and Recycle containers will be stored within the property
boundaries for this development when not located for service.



Environmental Services Department
Development Plan Review
Reviewer: Tony Teran
Office Phone (520) 837-3706
E-mail: Tony.Teran @tucsonaz.gov
12/15/2011 JOE LINVILLE LANDSCAPE REVIEW Approved
12/20/2011 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D11-0029 MATA RESIDENCE OFFICE

() Tentative Plat
(X) Development Plan
(X) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other - Elevations

CROSS REFERENCE: C9-85-22

NEIGHBORHOOD PLAN: University Area Plan and West University Neighborhood Plan

GATEWAY/SCENIC ROUTE: NO

COMMENTS DUE BY: December 20, 2011

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Rezoning Conditions
() RCP Proposal Complies with Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on: 09/23/2011
() Resubmittal Required:
() Tentative Plat
() Development Plan
() Landscape Plan
() Other

REVIEWER:msp 837-6971 DATE: 12/16/2011
12/20/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

December 20, 2011

Kevin Hall
Cypress Civil Development
2102 N. Country Club Rd #9
Tucson, Arizona 85716

Subject: D11-0029 MATA RESIDENCE OFFICE Development Plan

Dear Kevin:

Your submittal of August 30, 2011 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 2 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

2 Copies Revised Development Plan (Zoning, PDSD)

2 Copies Revised Landscape Plan (Zoning, PDSD)


Should you have any questions, please call me at 837-4893.


Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 798-3341