Permit Number: D11-0026
Parcel: 11521010H

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D11-0026
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2012 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
02/27/2012 JASON GREEN ENGINEERING REVIEW Approv-Cond DATE: February 27, 2012
SUBJECT: Bella Vista Apartment Development Plan Package- 4th Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 1900 W Speedway Blvd, T15S R13E Sec3/10 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: D11-0026

SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the revised Development Plan Package, Drainage Statement (HILGARTWILSON, 02MAY11, revised 20OCT11 & 09FEB12), Geotechnical Engineering Evaluation (02MAY11, restamped 14FEB12), and Stormwater Pollution Prevention Plan (HILGARTWILSON, 25OCT11). Engineering Division recommends conditional approval of the Development Plan Package at this time. The following items need to be addressed prior to final CDRC approval:

DEVELOPMENT PLAN:

" Restated: DS Sec.2-01.3.9.L: Revise the development plan document to delineate and label all new/proposed easements with recordation information. Specifically the recordation information for the 15 sq ft TEP easement as shown in Keynote #6. It is acknowledged that the TEP easement along with the construction and maintenance easement for the offsite drainage improvements will be submitted as one document that will be recorded, however prior to final CDRC approval this must be submitted and approved.


GENERAL COMMENTS:

Provide the recorded easements for both offsite improvements and the proposed TEP easement for final CDRC approval.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services Department
02/29/2012 JWILLIA4 PIMA COUNTY WASTEWATER Approv-Cond PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


February 28, 2012

To: HILGART WILSON
HILGART WILSON, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: BELLA VISTA APARTMENTS
Dev. Plan – 4th submittal
D11-0026

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:

1. Sheet 10: Show the public sewer easement with recordation information over the existing public sewer shown on plan. The sewer line including the 6” line to be abandoned should have an associated public sewer easement and this should be shown on plan. Ref. A.

2. A specific public sewer access easement should be associated with the public sewer line shown on plan. The easement submitted for review (sequence #20112790500) is not the public sewer ingress/egress access easement requested in the last review. The access easement should include a turnaround on site per WWM 110. Ref. A.

3. Remove the reference to sewer construction note #12 for existing MH# 9522-01 since the force main will not be connecting to the existing manhole. Ref. A and F


This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the fifth(5th) submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


cc: Chad Amateau, PE Checked by:_________
Kristin Greene, PE, DLU Manager
DLU Project folder

Ref. A. Development Plan Checklist Requirements – Chapter 18.71 of the Pima County Code - Section J
http://www.pimaxpress.com/SubDivision/Documents/2006/DP_Requirements2Aug04.pdf

Ref. C - Arizona Administrative Code, Title 18, Chapters 5 & 9 (R18-5-205)
http://www.azsos.gov/public_services/Title_18/18-05.htm
and (R-18-9-E301)
http://www.azsos.gov/public_services/Title_18/18-09.htm

Ref. D - PCRWRD Procedures, Preliminary Sewer Layout Requirements, 1984 (revised April 1988)
http://www.pima.gov/wwm/eng/stddet/pdf/procedures.pdf

Ref. E - PCRWRD Design Standards for Public Sewerage Facilities, 1983 (revised April 1988)
http://www.pima.gov/wwm/eng/stddet/pdf/design_standards.pdf

Ref. F - City of Tucson/Pima County Standard Details
http://www.pima.gov/wwm/eng/stddet/pdf/all_det.pdf

Ref. G - Pima County Code of Ordinances, Title 13 - Public Services, Division II - Sewers
http://library.municode.com/index.aspx?clientID=16119&stateID=3&statename=Arizona

Ref. H - City of Tucson/Pima County Standard Specifications for Public Improvements, 2003 Edition
http://dot.pima.gov/transeng/stdspecsdet/standardspecs2003.pdf

Ref. I - PCRWRD Engineering Directives
http://www.pima.gov/wwm/eng/directives/
02/29/2012 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES


February 29, 2012

Philip Carhuff
Krebs Carhuff Architects
3149 E. Prince Road # 151
Tucson, Arizona 85716

Subject: D11-0026 BELLA VISTA APARTMENTS Development Plan

Dear Philip:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made, please submit the following documents for sign-off.

1 Rolled COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.

1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

Additional print copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City’s contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your prints to the CDRC office for sign-off approval. The printing company will deliver the original rolled prints to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

Plans will not be signed and released until the CDRC office has been notified by PC Addressing that all fees for this plan have been paid. The CDRC office will need this confirmation in writing.

NOTICE: The final plans will have to be reviewed by Pima County Wastewater Management prior to submittal to the CDRC Office and the approval must be in writing (an email is okay).

A Development Plan remains valid for a period of three (3) years from the date of approval. This Development Plan will expire on 03/01/2015 per LUC 5.3.8.2.B.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html.
BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4893.

Sincerely,


John Williams
Planning Technician
All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 577-4560
02/29/2012 JWILLIA4 PIMA COUNTY WASTEWATER Approv-Cond PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


February 28, 2012

To: HILGART WILSON
HILGART WILSON, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: BELLA VISTA APARTMENTS
Dev. Plan – 4th submittal(Rev)
D11-0026

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
The Pima County Regional Wastewater Reclamation Department hereby conditionally approves the above referenced submittal of the site plan with the following revisions which can be shown on mylar:

1. Sheet 10: Show the public sewer easement with recordation information over the existing public sewer shown on plan. The sewer line including the 6” line to be abandoned should have an associated public sewer easement and this should be shown on plan. Ref. A.

2. A specific public sewer access easement should be associated with the public sewer line shown on plan. The easement submitted for review (sequence #20112790500) is not the public sewer ingress/egress access easement requested in the last review. The access easement should include a turnaround on site per WWM 110. Ref. A.

3. Remove the reference to sewer construction note #12 for existing MH# 9522-01 since the force main will not be connecting to the existing manhole. Ref. A and F


This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the fifth(5th) submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


cc: Chad Amateau, PE Checked by:_________
Kristin Greene, PE, DLU Manager
DLU Project folder

Ref. A. Development Plan Checklist Requirements – Chapter 18.71 of the Pima County Code - Section J
http://www.pimaxpress.com/SubDivision/Documents/2006/DP_Requirements2Aug04.pdf

Ref. C - Arizona Administrative Code, Title 18, Chapters 5 & 9 (R18-5-205)
http://www.azsos.gov/public_services/Title_18/18-05.htm
and (R-18-9-E301)
http://www.azsos.gov/public_services/Title_18/18-09.htm

Ref. D - PCRWRD Procedures, Preliminary Sewer Layout Requirements, 1984 (revised April 1988)
http://www.pima.gov/wwm/eng/stddet/pdf/procedures.pdf

Ref. E - PCRWRD Design Standards for Public Sewerage Facilities, 1983 (revised April 1988)
http://www.pima.gov/wwm/eng/stddet/pdf/design_standards.pdf

Ref. F - City of Tucson/Pima County Standard Details
http://www.pima.gov/wwm/eng/stddet/pdf/all_det.pdf

Ref. G - Pima County Code of Ordinances, Title 13 - Public Services, Division II - Sewers
http://library.municode.com/index.aspx?clientID=16119&stateID=3&statename=Arizona

Ref. H - City of Tucson/Pima County Standard Specifications for Public Improvements, 2003 Edition
http://dot.pima.gov/transeng/stdspecsdet/standardspecs2003.pdf

Ref. I - PCRWRD Engineering Directives
http://www.pima.gov/wwm/eng/directives/