Permit Number: D11-0018
Parcel: 13708021D

Address:
5663 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D11-0018
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/31/2011 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Dollar General 5663 S. 12th Avenue
Development Package (3rd Review)
D11-0018

TRANSMITTAL DATE: August 31, 2011

DUE DATE: September 12, 2011

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section conditionally approves the development package for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development package to verify that those changes do not affect any zoning requirements.

2. D.S. 2-01.3.9.L Provide the sequence number for the proposed "INGRESS/EGRESS EASEMENT" shown on the plan.

3. D.S. 2-01.3.9.R Per D.S. 2-08. Per D.S. 2-08.4.1.A A sidewalk is required from the proposed building to Drexel Road. To eliminate the sidewalk from this project a Development Standard Modification Request (DSMR) must be processed and approved. Provide the DSMR Number, Date of Approval, What Was Approved and Conditions of Approval on the Development Package.


If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D11-0018

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package.
09/06/2011 RONALD BROWN H/C SITE REVIEW Approved
09/07/2011 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approved PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


August 31, 2011

To: Jeff Stanley, P.E.
JAS Engineering, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: Dollar General- 12th Ave & Drexel
Dev. Plan – 3rd submittal
D11-0018

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
The Pima County Regional Wastewater Reclamation Department hereby approves the above referenced submittal of the development plan as submitted.

cc: Chad Amateau, PE Checked by:_________
Kristin Greene, PE, DLU Manager
DLU Project folder
09/08/2011 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: D11-0018 DOLLAR GENERAL – 12TH & DREXEL/REVISED DEVELOPMENT PLAN
DATE: September 2, 2011



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar or bond paper of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.
09/12/2011 JOE LINVILLE LANDSCAPE REVIEW Approved Existing wall at north boundary per previously approved DP.
09/13/2011 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: September 13, 2011
CDRC/Zoning Manager

SUBJECT: Dollar General, 5663 S. 12TH Ave.
Development Package D11-0018
T15S, R13E, Section 01

RESUBMITTAL REQUIRED: Development Package.

The Development Package (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Package:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Per our discussions, the DP cannot be approved prior to the recordation of the TEP easement. Place the sequence number on the plan prior to the re-submittal.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/5663 S. 12TH Ave_Dev_Pkg
09/15/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

September 14, 2011

Jeffrey Stanley
JAS Engineering
PO Box 1888
Tucson, Arizona 85702

Subject: D11-0018 DOLLAR GENERAL Development Package

Dear Jeff:

Your submittal of June 10, 2011 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 3 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

3 Copies Revised Development Package (Zoning, Engineering, PDSD)

Should you have any questions, please call me at 837-4893.

Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/

Via fax: 624-0993
09/15/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES
*** REVISED ***

September 15, 2011

Jeff Stanley
JAS Engineering
PO Box 1888
Tucson, Arizona 85702

Subject: D11-0018 DOLLAR GENERAL Development Package

Dear Jeff:

The above referenced Development Package has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made, please submit the following documents for sign-off.

1 Rolled COMPLETE SET of the Development Package. Please include applicable sheets from any other concurrent reviews.

1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan (if applicable).

Additional print copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City’s contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your plans to the CDRC office for sign-off approval.

Plans will not be signed and released until the CDRC office has been notified by PC Addressing that all fees for this plan have been paid. The CDRC office will need this confirmation in writing.

A Development Package remains valid for a period of three (3) years from the date of approval. This Development Package will expire on 09/15/14 per LUC 5.3.8.2.B.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4893.

Sincerely,



John Williams
Planning Technician

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/