Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D11-0008
Parcel: 11105063G

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D11-0008
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2011 JWILLIA4 START PLANS SUBMITTED Completed
06/02/2011 JASON GREEN ENGINEERING REVIEW Approved DATE: June 2, 2011
SUBJECT: Mintec Development Plan- 2nd Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 3544 E Fort Lowell Road, T13S R14E Sec33, Ward 3
REVIEWER: Jason Green, CFM
ACTIVITY: D11-0008


SUMMARY: Engineering Division of Planning Development Services Department has received the revised development plan and Drainage Statement (JAS Engineering, 23MAR11) for the proposed project. Engineering Division has reviewed the submitted development plan and recommends approval at this time.


For any questions call me at 837-4929.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services
06/16/2011 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Planning & Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: MINTEC - Revision
Development Plan (2nd Review)
D11-0008

TRANSMITTAL DATE: June 16, 2011

DUE DATE: June 27, 2011

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section conditionally approves the development plan for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. D.S. 2-05.2.4.O The loading space calculation is not correct. The calculation calls out "(2 SPACES PER 10,000 - 30,000 GFA) LUC TABLE 3.4.5.5 - 1 SPACE @ 12'X 35'", this is not correct. The calculation should show "REQUIRE - 0, PROVIDED 1".

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D11-0008

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan.
06/23/2011 RONALD BROWN H/C SITE REVIEW Approved
06/24/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES


June 24, 2011

William L. Ford
WLFA Associates
1227 N. 3rd Avenue
Tucson, Arizona

Subject: D11-0008 MINTEC Development Plan Revision

Dear William:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per Zoning, please submit the following documents for sign-off.

1 Rolled blue line COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.

1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

Additional black line copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. The printing company will deliver the original rolled blue line to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

Plans will not be signed and released until the CDRC office has been notified by PC Addressing that all fees for this plan have been paid. The CDRC office will need this confirmation in writing

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html.
BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4893.

Sincerely,




John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 623-0360