Permit Number: D11-0006
Parcel: 12703001A

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D11-0006
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/04/2011 RONALD BROWN ADA REVIEW Passed
03/09/2011 MARTIN BROWN COT NON-DSD FIRE Approved
03/15/2011 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: March 15, 2011
CDRC/Zoning Manager

SUBJECT: Circle 'K', 5502 E. Speedway Blvd.
Development Package D10-0006 (First Review)
Grading Plan T11BU00299
T14S, R14E, Section 12

RESUBMITTAL REQUIRED: Development Package: Site Plan, Grading Plan and Stormwater Pollution Prevention Plan.

The Development Package (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Package:

1. Please include a detailed response letter to the comments along with the corrected copies of the DP.
2. A legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet. D.S. 2-01.2.9. Include the wall symbol in the legend.
3. Complete the DP plan number in the title block. Also list the GP number (T11BU00299) on all sheets too.
4. The title block shall include the following information. D.S. 2-01.3.2.
D. The administrative street address.
5. Relevant case numbers (development package document, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. D.S. 2-01.3.3. A DSMR will be required for exceeding the max. back-up distance of 40' for the service vehicle per D.S. 6-01.4.0.C.
6. Existing Site Conditions. The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within fifty (50) feet of the site. On sites bounded by a street with a width of fifty (50) feet or greater, the existing conditions across the street will be provided. D.S. 2-01.3.8.
B. All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from the easement holder(s) is provided. A cross access agreement with the property adjacent to the east will be necessary prior to the approval of the DP.
E. Indicate the ground elevation on the site based on City of Tucson Datum (indicate City of Tucson field book number and page). List the field book and page on the datum.
7. Information on Proposed Development. The following information on the proposed project shall be shown on the drawing or added as notes. D.S. 2-01.3.9.
H. Proposed traffic circulation:
2. Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section. The SVT's at the NE corner of Craycroft Rd. and 1st St. are not shown correctly. The SVT's on the right side of a street with medians should be 20'x30' pedestrian triangles.
I. Show all right-of-way dedications on or abutting the site and label. If the development package documents have been prepared in conjunction with a subdivision plat or is required as a condition of approval of a review process, such as a rezoning, street dedications in accordance with the Major Streets and Routes (MS&R) Plan may be required by these processes. Projects bounded by streets having only a portion of the right-of-way width dedicated will be required to dedicate right-of-way, up to one-half (½), to complete the street width. Should there be any proposed street or alley vacation, provide this information. If vacation has occurred, include the recording information. Label the R/W to be dedicated per the MS&R plan.
O. All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown. There is a wall and a "Circle K" monument sign located in the SVT's. A free standing wall on the south side of the driveway on Craycroft Rd. is in the SVT and the monument sign that is located on the west side of the driveway on Speedway Blvd. is also in the future SVT.
R. Show on-site pedestrian circulation as required by the LUC utilizing location and the design criteria in Development Standard 2-08.0. Provide pedestrian access for 1st street.
W. Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to LUC Sec. 3.5.4.26 may be required. See note "O" above.
8. The water harvesting basins cannot be located in the exist. or fut. r/w. Obtain documentation from TDOT for allowing the locations of the basins in the r/w.
9. Elongate the x-sections A, B, C and D on sht. 6 to include the exist. and future r/w's, on-site improvements, landscaped areas and a portion of the P.A.A.L., just a bit past the vertical curb. Also it seems as if the sections don't exactly depict the actual conditions of the street. The aerials show the exist. concrete in different places than it is shown on the x-sections or on the plan view. Show the proposed sidewalks on the x-sections with a continuous dark line instead of dashed and a light line.
10. Call out the type of curbs proposed on-site, ie: vertical or extruded. Include a detail if a standard PC/COT is not used.
11. Replace the "weep holes" on the all note call-outs including section D/6 for the walls with "drainage blocks". Drainage blocks shall also be installed on the wall on the east property line. Also remove the quantity or update the amount of drainage blocks on the wall call-outs because the drng. blks. on the east wall were not accounted for.
12. Show the water harvesting basin slopes with continuous lines instead of dashed lines and use slope arrows to clarify the slopes and basin limits.
13. Section B/6 calls out for a proposed 5' asphalt sidewalk, yet it appears on the site plan view as concrete and is called out on the key notes also as concrete as well. On the s/w call-out on 1st Ave, move the 6' s/w dimension so it can be read easier. Use a keynote symbol on South portion of the s/w as well, like the other side walks.
14. List administrative address/site address on plans.

Drainage Statement:
1. The DS is accepted by engineering.

Grading Plan:
1. Curb and Gutter elevation include drainage flow with percent slope.
2. Show details of all surface materials. Show detail of extruded curb if used. Also rip-rap shall be installed at the inlets from the P.A.A.L. into the basin. Also include a detail showing the size, filter fabric etc. of the rip-rap.
3. FYI - The length of the refuse enclosure wall (11'-8") is not "block module". In other words, if they were to build the enclosure using that dimension, the mason would have to cut the block. The next dim. without having to cut block is 12'-0". Here is the rule for masonry construction:
Dim. for feet that end in an even number, use 0" or 8", ex. 12'-0" or 12'-8"
Dim. for feet that end in an odd number, use 4", ex. 1'-4" or 11'-4"
4. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
5. Cut or fill slopes require a 2' minimum setback from property line. Show on all x-sections.
6. List all Cut and Fill quantities in cubic yards. If both are 0 cy, please list.
7. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers and/or sidewalk scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof drain/sidewalk scupper locations have been designed and located will suffice.
8. Call out surface paving material. Show a detail or show the pavement (ac/abc) on any of the cross-sections.
9. List the information of the Geotechnical Investigation Report in the grading plan notes.

Geotechnical Investigation Report:
1. Remove and replace any reference to Maricopa County standards and/or any other municipal jurisdiction with the appropriate City of Tucson specifications.

Stormwater Pollution Prevention Plan:
BEST MANAGEMENT PRACTICES (BMPs):
1. Indentify and provide the location(s) of all non-stormwater discharges allowed by this permit expected to be associated with the project and describe BMP's used to minimize discharge of pollutants. Part IV.E.2. Show the concrete wash-out area on the site plan.
Inspections

2. Add a note stating that the operator(s) shall report to ADEQ any noncompliance (including spills) which may endanger human health or the environment. The operator shall orally notify the office listed below within 24 hours:

" Arizona Department of Environmental Quality
1110 W. Washington, 5th floor (5515B-1)
Phoenix, AZ 85007
Office: 602-771-4466; Fax 602-771-4505


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/5502 E. Speedway Blvd. Dev Pkg
03/15/2011 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approv-Cond AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: D11-0006 CIRCLE K AT SPEEDWAY AND CRAYCROFT/DEVELOPMENT PLAN
DATE: March 15, 2011



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

Note: On the Final Development Plan

Change Sahuara Road to Avenue on the Location Map.
Delete the street direction E. from E. 1st Street on sheet 3.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.
03/16/2011 FRODRIG2 ENV SVCS REVIEW Approved Date Case Number Project Address
March 15, 2011 D11-0006 CIRCLE-K AT 5502 E. Speedway BL
Development Plan

Comments: The proposed Development Plan for the CIRCLE-K, located at 5502 E. Speedway
Boulevard and Craycroft Road, Case No. D11-0006, meets the minimum
requirements for Environmental Services, Solid Waste Disposal and
Recycle materials Standard 6-01.0 and is here Approved.


Environmental Services Department
Development Plan Review
Reviewer: Tony Teran
Office Phone (520) 837-3706
E-mail: Tony.Teran @tucsonaz.gov
03/17/2011 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#234852 March 16, 2011



Dear Mr. Harris :

SUBJECT: Circle K at Speedway / Craycroft
D11-0006


Tucson Electric Power Company has reviewed and approved the development plan submitted March 9, 2011 It appears that there are conflicts with the existing facilities within the boundaries of this proposed development. TEP poles and Overhead Primary lines are in conflict with the new development. Easements were shown the Development plan but not TEP poles in conflict.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. All relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Richard Harrington
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8726

Please call the area Designer Nancy DiMaria at (520) 918-8267, should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
Pima County (Email only)
cc:W. McElyea
03/21/2011 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Denied CDRC Review
Planning and Development Services Dept., Community Planning Review
D11-0006, Circle K, Speedway/Craycroft, 1st submittal
Comments Due: 4/4/11

Items reviewed: Development Plan Package
Rezoning Pre-submittal Meeting Notes, meeting date 10/27/10)

Note: This project was submitted as a concurrent rezoning case (C9-11-02, Circle K - Speedway Boulevard, R-1 to C-1) and Development Plan package. The following comments are based on anticipated rezoning conditions, which may be approved or modified by the Mayor and Council. Any Mayor and Council changes to the conditions must be addressed by the applicant prior to resubmitting the development plan.

Comments:

1. Please label the wrought iron fencing around the convenience store. Provide a detail for the wrought iron fencing.

2. Please provide a detail for the masonry screen wall, indicating the decorative treatment, and that the wall will be graffiti-resistant.


Reviewed by: J. Hershenhorn, 3/21/11


F:\Shardir\UPDfiles\Development Review\CASE_REVIEW\CDRC\2011 Cases\D11-0006_CircelKSpdwyCrycft.doc
03/22/2011 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Add the CDRC Case Number to the plans.

Submit any revised plans for review.
03/22/2011 JANE DUARTE COT NON-DSD PARKS & RECREATION Approved
03/31/2011 JOSE ORTIZ COT NON-DSD TRAFFIC Denied March 31, 2011
ACTIVITY NUMBER: D11-0006
PROJECT NAME: Circle K
PROJECT ADDRESS: Craycroft/Speedway
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Development Plan; therefore a revised Development Plan is required for re-submittal. The following items must be revised or added to the development plan. See the redlines provided for clarification to the following comments

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. The proposed crosswalks across the driveways are within public right of way and are not warranted. Remove the proposed crosswalks from the plan sheets.

3. TDOT currently has no plans to widened the Craycroft/Speedway intersection so it is TDOT's preference that the proposed sidewalks and ramps be placed within the 10' pedestrian area as illustrated in the Major Streets and Routes plan.

4. The access points shall have 25' radius curb returns. (DS 3-01.0 figure 6). An 18' radius curb return can be considered as part of the required bus pullout.

5. A private improvement agreement (PIA) will be necessary for the proposed work to be performed within the Right-of-way. An approved development plan is required prior to applying for a PIA.

6. An existing light pole may be impacted with the installation of the proposed driveway. If applicable, relocate the light pole and provide confirmation from Ernie Encinas that the new location is acceptable to the city. This comment can be addressed on the PIA.

7. Tucson City Code Chapter 25 Section 38 states that the maximum driveway width for adjoining properties is 30-feet. The proposed driveway along Speedway Blvd exceeds 30-feet in width.

8. The COT Transportation Access Management Guidelines 5.4 requires a minimum driveway separation of 80' along any major-street and route. The separation of the proposed driveway along Speedway Blvd to the existing driveway to the east is less then 80-feet.

9. Schematically illustrate the recommended off site improvements on the development plan. Final dimensions for all off site improvements will be illustrated on the PIA plans.

Comment from Tom Fisher
A standard bus pullout and bus shelter pad will be needed, and may be designed in coordination with a right-turn/deceleration lane if needed. The pad will need to be wheelchair accessible and connected to adjacent walkways per ADA requirements. TDOT can provide design specifications to the project design consultant when ready. TDOT's contractor will provide a bus shelter, trashcan, and other amenities.


If you have any questions, I can be reached at 837-6730 or Jose.Ortiz@tucsonaz.gov
04/04/2011 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D11-0006
5502 E. Speedway Blvd.
Development Package

TRANSMITTAL: 04/04/2011

DUE DATE: 04/04/2011

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is 03/03/2012.

2. DS 2-01.3.3 Provide the case number for the rezoning case (C9-11-02) near the title block. Clarify the case number (C10-27-10) as to what it pertains to. The rezoning case number, date of approval, and conditions of approval are to be provided on the plan. A separate sheet is to be provided clearly indicating how each of the rezoning conditions have been meet.

Case number D11-0006 has been assigned to this development plan (DP). Please place this number in the right corner of all sheets of the development plan, landscape plan, NPPO, and any other associated sheets.

3. DS 2-01.3.7.A.3 List the proposed zoning as C1 and C-2.

4. DS 2-01.3.7.A.3 The proposed use (uses) should be listed for both the C-1 portion and the C-2 portion. Each with separate subject to sections. Each will also have different development designators.

5. DS 2-01.3.7.A.9 Provide the allowed and proposed Floor Area Ratio (FAR) for each zone. The most restrictive can be used as the proposed.

Lot coverage percentages are not required and can be removed from the plan.

6. DS 2-01.3.8.A Provide the distance and bearings of the future property lines.

7. DS 2-01.3.8.B A cross access agreement with the property to the east will be required to be provided. Provide recording docket and page information for the agreement on the plan.

8. DS 2-01.3.8.C Clearly indicate if dedication of right of way is to occur at this time. Provide recording information on the plan for the dedication.

9. DS 2-01.3.9.A A tax parcel lot combination will be required to be completed and approved for the 4 separate lots. Provide a copy of the combination. Remove all combined lot lines from the plan.

10. DS 2-01.3.9.F The indicated zoning classifications are to be shown as they will be after the rezoning is complete. Clearly indicate the boundaries of the C1 and C2 zoning.

11. FYI: As of March 8, 2011 ordinance 10884 for loading zone requirements was passed and as of March 22,2011 ordinance 10886 for parking space and bicycle parking was passed. A review of these ordinances may or may not be advantageous to this plan. This review will be done under the LUC prior to adoption of these ordinances. If you chose to use the new ordinances you must use all of the ordinances or use the previous code.

12. DS 2-01.3.9.H.d Bicycle parking provided on the DP does not meet the requirements of revised DS (Development Standard) 2-09. Per DS 2-09.4.1 Class 2 bicycle parking facilities will be located no more than fifty (50) feet from the main building entrance(s) and will be along the front side of the building as well as along other sides of the building that has an entrance.

Relocation of the class two bicycle parking spaces will be required or approval through the DSMR process. If a DSMR is applied for and approved provide the case number in the lower right corner and provide a note indicating the case number, date of approval, what the DSMR is for and any conditions of approval.

Please provide a plan view detail of the proposed class 2 bicycle parking spaces. Single rack spaces placed in a row will allow a minimum of seventy -two (72) inch length per bicycle parking space and a minimum of thirty (30) inches between outer spaces of racks. A five (5) foot wide access aisle measured from the front or rear of the seventy-two (72) inch long parking space will be provided beside each row. Lighting will be provided such that all facilities are thoroughly illuminated and visible from adjacent sidewalks, parking lots, or buildings, during working hours. The surface of the facility can be surfaced the same as for motor vehicle parking or with a minimum of one (1) inch thickness of one-fourth (1/4) inch aggregate material.
DS 2-09.5.1, DS2-09.5.2, DS 2-09.5.4, & DS 2-09.6.2


13. DS 2-01.3.9.R Provide a pedestrian circulation connection to the sidewalk in the right of way for 1st Street.

14. DS 2-01.3.9.V Please indicate the location and type of postal service to assure there are no conflicts with other requirements. If mail is to be delivered to an area within a building please state so on the plan.

15. DS 2-01.3.9.W The proposed monument sign at the entrance from Speedway is located within the future sight visibility triangle. A DSMR will be required to be completed and approved. If dedication of right of way is to be done at this time then a Board of Adjustment variance will be required to be completed and approved.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\D11-0006dp.doc



Grading Comments

04/04/2011

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
04/04/2011 RONALD BROWN ZONING HC REVIEW Denied 1. A per the 2006 IBC, ICC (ANSI 117.1, 2003 Edition), Section 502.4.3, the length of the access aisle shall extend the full length of the parking spaces it serves.
a. The minimum depth of a parking space is 18'. Please adjust both accessible parkings spces to a full 18' depth and resubmit.
END OF REVIEW
04/04/2011 FERNE RODRIGUEZ COT NON-DSD QWEST Passed
04/04/2011 FERNE RODRIGUEZ COT NON-DSD SOUTHWEST GAS Passed
04/04/2011 FERNE RODRIGUEZ COT NON-DSD U. S. POST OFFICE Passed
04/05/2011 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
04/05/2011 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Passed
04/05/2011 ED ABRIGO PIMA COUNTY ASSESSOR Passed
04/05/2011 PGEHLEN1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
04/05/2011 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Passed
04/05/2011 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
04/05/2011 TIM ROWE PIMA COUNTY WASTEWATER Approved Pima County Regional Wastewater Reclamation Department


Jackson Jenkins
Director
201 N. Stone Ave., 8th Floor
Tucson, Arizona 85701-1207


PH: (520) 740-6500
FAX: (520) 620-0135

April 1, 2011

To: ERIN HARRIS
STAR CONSULTING

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department
____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: CIRCLE K AT SPEEDWAY AND CRAYCROFT
Development Plan - 1st Submittal
D11-0006

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
The Pima County Regional Wastewater Reclamation Department hereby approves the above referenced submittal of the development plan as submitted.
If you have any questions please call me at the phone number above.


cc: Chad Amateau, PE Checked by:______
Kristin Borer, PE, DLU Manager
DLU Project folder
04/06/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

April 6, 2011

Erin Harris
STAR Consulting of Arizona, Inc.
5405 E. Placita Hayuco
Tucson, Arizona 85718

Subject: D11-0006 CIRCLE K Development Package

Dear Erin:

Your submittal of March 4, 2011 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 8 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

8 Copies Revised Development Package (Addressing, Engineering, Planning, Landscape, Traffic, Zoning HC, Zoning, PDSD)
2 Copies Revised Geotechnical Report (Engineering, PDSD)
2 Copies Revised SWPPP (Engineering, PDSD)
2 Copies Cross Access Agreement Documentation (Zoning, PDSD)
2 Copies Tax Parcel Lot Combo Documentation (Zoning, PDSD)
1 CD Digital Copy of Revised Plans and/or Documents (PDSD)

Should you have any questions, please call me at 837-4893.

Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/

Via fax: (520) 529-1240
04/06/2011 PGEHLEN1 COT NON-DSD TUCSON POLICE DEPARTMENT Approved I have no issues with this request at this time.
CSO Becky Noel #37968
Tucson Police Dept
837-7428