Permit Number: D10-0046
Parcel: 13505149X

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D10-0046
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/05/2011 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
04/06/2011 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Quick Trip Store 1496
Development Package (2nd Review)
D10-0046

TRANSMITTAL DATE: April 6, 2011

DUE DATE: April 28, 2011

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section conditionally approves the development package for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements.

2. This comment was not fully addressed. Add the "A" to the subject to section. D.S. 2-01.3.7.A.4 Revise Permitting Note 3 to include "SUBJECT TO SECTION 3.5.9.2.A" adjacent to the proposed use.

3. This comment was not addressed D.S. 2-01.3.8.B There is a "32' Ingress/Egress Easement Per Dkt 12726, Page 291, P.C.R" that appears to be located under the proposed building. This easement will need to be abandoned prior to approval of the development package.

4. This comment was not addressed D.S. 2-01.3.9.E The proposed lot split must be completed prior to approval of the development package..

5. This easement must be recorded prior to approval of the development package. D.S. 2-01.3.9.L Some type of access easement or access agreement is required for the proposed access at the southeast corner of this project.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D10-0046
04/12/2011 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: D10-0046 QUIKTRIP STORE NO. 1496/REVISED DEVELOPMENT PLAN
DATE: April 11, 2011



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.
04/12/2011 JOE LINVILLE LANDSCAPE REVIEW Approved
04/13/2011 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Denied PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


April 13, 2011

To: RICHARD CORDOVA
DOWL HKM

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), Pima County Regional Wastewater Reclamation Department

Subject: QUIKTRIP STORE #1496
Development Plan – 2nd Submittal
D10-0046

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
The ingress/egress/private sewer easement will need to be recorded before approval of the development plan.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.
The next submittal of this project will be the third(3rd) submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.
If the number of sheets changes, please adjust the review fee accordingly.

cc: Chad Amateau, PE Checked by:_________
Kristin Greene, PE, DLU Manager
DLU Project folder
04/14/2011 JASON GREEN ENGINEERING REVIEW Approv-Cond DATE: April 14, 2011
SUBJECT: QuikTrip #1496 Development Plan Core Review- 2nd Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 6385 E Golf Links Rd, T145S R15E Sec19 Ward 4
REVIEWERS: Jason Green, CFM
ACTIVITY: D10-0046


SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Development Plan Package, Drainage Report (DOWL HKM, 22DEC10, revised 29MAR11), Stormwater Pollution Prevention Plan (DOWL HKM, 22DEC10, revised 28MAR11) and Geotechnical Evaluation (Kleinfelder, 17JAN11. Engineering Division recommends conditional approval of the Development Plan Package at this time. The following items need to be addressed prior to final CDRC approval:


DRAINAGE STATEMENT:

1) Completed.


DEVELOPMENT PLAN:

2) Completed.

3) Completed.

4) Completed.

5) Restated: DS Sec.2-01.3.8.B: All easements that are proposed to be abandoned (32-foot ingress/egress easement under the building footprint) are required to be vacated prior to approval of the development plan documents therefore the easements that are to be abandoned must be removed from the development plan documents for clarity.

6) Completed.

7) Acknowledged.

8) Completed.

9) Completed.

10) Completed.

11) Completed.

12) Restated: DS Sec.2-01.3.9.L: Provide the recordation information for all new proposed easements in plan view prior to final CDRC approval, specifically the new ingress/egress easement for the access drive to Wilmot Road.

13) Acknowledged.

14) Completed.

15) Completed.

16) Completed.

17) Completed.

18) Completed.

19) Completed.

20) Completed.

21) Completed.

22) Completed.

23) Completed.

24) Approval from TDOT Permits and Codes will be required for all improvements within the public right-of-way and for the connection of the private storm drains into the public infrastructure. A right-of-way use permit application will be required prior to construction. Contact Thad Harvison, (520)-837-6592 or Thad.Harvison@tucsonaz.gov for all right-of-way requirements and permit applications.

25) Completed.


GEOTECHNICAL REPORT:

26) Completed.


STORMWATER POLLUTION PREVENTION PLAN: The SWPPP meets the minimum requirements of the AzPDES Construction General Permit (CGP).

27) Completed.

28) Completed.

29) Completed.


GENERAL COMMENTS:

Provide all recordation information for both easement abandonment and new easements being created by this project prior to final CDRC approval.

For any questions or to schedule meetings call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
04/19/2011 RONALD BROWN H/C SITE REVIEW Approved
04/19/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

April 19, 2011

Richard Cordova
DOWL HKM
166 W. Alameda St.
Tucson, Arizona 85701

Subject: D10-0046 QUIKTRIP STORE #1496 Development Package

Dear Richard:

Your submittal of December 22, 2010 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 4 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Development Package (Zoning, Wastewater, Engineering, PDSD)

1 Check Made out to "Pima County Treasurer" for $39.00 (Wastewater)


Should you have any questions, please call me at 837-4893.

Sincerely,




John Williams
Planning Technician

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/

Via fax: (520) 624-0384