Permit Number: D10-0043
Parcel: 11308208F

Address:
2802 N 1ST AV

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D10-0043
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2011 RONALD BROWN ZONING HC REVIEW Denied 1. Most Northerly curb ramp flared sides must be 1:10 slope minimum as per ICC (ANSI 117.1), Section 406.3.
END OF REVIEW
01/05/2011 TIM ROWE PIMA COUNTY WASTEWATER Denied PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
MICHAEL GRITZUK, P.E. PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


January 4, 2011

To: DAVID W. LITTLE, P.E.
THE WLB GROUP, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

__________________________
Reviewed by: Chad Amateau, P.E., Civil Engineer PCRWRD

Subject: QUIKTRIP STORE #1454
2802 N 1ST AVENUE
Development Plan – 1st Submittal
D10-0043

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:

Obtain a letter from the PCRWRD’s Development Liaison Unit, written within the past year, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/developer.htm#permits

The development plan for this project cannot be approved until a copy of this letter has been received by this office.

Sheet C002: Fill in the blank for existing FUE on site for Wastewater General Note # 4.

Sheet C002: Revise Wastewater General Note #2 to read as follows:

THE ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

Sheet C002: There should be a distinction between existing and proposed sewer line and elements. Show this in the Legend and on plan.

Sheet C150: Call out the IMS #’s with rim and invert elevations for all of the existing public manholes shown on plan. Also call out the construction plan # with pipe sizes for the existing public sewer.

Sheet C150: Call out the length and slope for the proposed private BCS and call out the rim and invert elevations for the proposed cleanouts.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second(2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions about this review letter please call me @ the phone number below.

______________________________
Tom Porter, Sr. CEA, (520)740-6719 PCRWRD

cc: Chad Amateau, PE
Kristin Greene, PE, DLU Manager
DLU Project folder
01/07/2011 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Basin A on sheet C110 (as well as other required or proposed elements) may not comply with the provisions of LUC 2.8.3.5. No portion of the MS&R right-of-way area that is publicly owned will be used toward complying with Land Use Code (LUC) requirements, unless specifically stipulated. An approved site plan is required indicating how the project will comply with LUC requirements when the MS&R right-of-way can no longer be used as part of the site. LUC 2.8.3.5.A, & F.

2) Basin A on sheet C110 should be designed such that planted areas account for at least 35% of the total basin area. Revise the landscape plans as necessary. SDRM P.89

3) The site is required to include screening per LUC Table 3.7.2-I. LUC 3.7.3 & DS 2-06.3.7. Revise the plans to provide a continuous screen along First Ave. (see LUC 3.7.2.3.C) and the required masonry screen wall along the eastern property boundary to screen the site from the adjacent residentially zoned properties.

4) Sheet C030 indicates removal of existing trees east of the parcel boundary. Please verify that the NPP application is still accurate. LUC 3.8.3.4.D

5) Fifty (50) percent or more of the area of the street landscape border must be covered with shrubs or vegetative ground cover. Revise the plans and calculations if necessary to exclude plant material used for screening purposes. LUC 3.7.2.4.A.5, DS 2-06.3.7

6) Vegetation or structures higher than thirty (30) inches must be located outside of the sight visibility triangle. Address this requirement where SVT's based on the MS&R Plan apply. DS 2-06.3.7.B.1

7) Provide an interior landscape border as applicable along the east boundary. See LUC Table 3.7.2-I

8) Provide screening for utility cabinets and other elements east of the driveway at Glenn Street. LUC Table 3.7.2-I

9) For the purposes of calculating the percentage of water demand met for the total site, an adjustment is required where an individual WHIA exceeds 100 %. Excess water provided for a particular WHIA provides no benefit to the others on the site, therefore the excess skews the average if a value over 100 percent is included. DS 1-03.4.1.C

10) Revise the landscape plan to include the location and purpose of utility or other easements.
DS 2-07.2.2.E.1

11) Trees and shrubs are to be selected and located so that, at maturity, they do not interfere with existing on-site or off-site utility service lines or utility easements or with solar access. LUC 3.7.2.6.B
01/07/2011 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: January 7, 2011
CDRC/Zoning Manager

SUBJECT: QuikTrip, 2802 N. 1st Ave.
Development Package D10-0043 (First Review)
T13S, R14E, Section 31

RESUBMITTAL REQUIRED: Development Package.

The Development Package (DP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Development Package:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. Due to substantial drainage issues for this project, the site design as shown will not meet many of the City of Tucson drainage design regulations. A major site re-design must be made in order for this site to comply with those regulations. Therefore a proper and complete review of the Site plan, Grading Plan, Drainage Report and Stormwater Prevention Pollution Plan for this project cannot be performed. A section of the major issues are noted, but not limited to, are contained in the following comments.
3. Basins and/or other drainage improvements for the specific project cannot be located in the existing or future right-of-way.
4. Major Streets and Routes intersection widening is required for this project and will impact the design of Site plan dramatically.
5. Off-site construction and/or design is cannot be approved with out the registered property owner's permission.

Drainage Report/Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. The DR report cannot be reviewed until an acceptable drainage concept is provided.
3. Detention requirements cannot be waived especially due to the drainage problems associated with the channel to the east of the project.
4. A Flood Plain Use Permit and the requirements for an elevation certificate are required for this project.
5. An stormwater encroachment analysis using the non-diverted flow of 142.2 cfs shall be performed and the results included in the DR.
6. Buildings or other substantial improvements are not allowed in a drainage easement.
7. The stormwater Detention/Retention basin, water-harvesting basins or other drainage improvements for the specific project cannot be located in the existing or future right-of-way.
8. Major Streets and Routes intersection widening is required for this project will impact the drainage facilities substantially triggering a re-design of the drainage concept.
9. A diversion or the change of the existing drainage patterns entering and exiting the site are not generally allowed unless it is specifically designed to alleviate a drainage issue.
10. Any additional major stormwater discharge into the right-of-way must demonstrate no adverse impact to the existing drainage facilities and must be accepted by the City of Tucson Department of Transportation (TDOT).
11. The erosion hazard setback must be delineated.
12. Submit a geotechnical report with the re-submittal.

Stormwater Prevention Pollution Plan:
1. The SWPPP must reflect the re-design of the project.



If you have any questions or comments, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson - Planning and Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/2802 N. 1st Ave._DEV_PKG A
01/10/2011 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: D10-0043
2802 N. 1st Ave. - Quik Trip
Development Package

TRANSMITTAL: 01/10/2011

DUE DATE: 01/07/11

COMMENTS:

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development plan. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is 12/07/11.

2. DS 2-01.2.6 The project location map shall be located in the upper right corner of the cover sheet.

3. DS 2-01.3.2.B A brief legal description is requried to be placed near the title block.

This site contains four (4) separate parcels therefore you will need to show how the parcels can work as stand alone parcels if sold separately or provide a Pima County Tax Parcel Combo and a recorded covenant regarding development and use of real property.

4. DS 2-01.3.3 Provide relevant case numbers (DDO, DSMR, overlay etc.)adjacent to the title block on each sheet.

Case number D10-0043 has been assigned to this development plan (DP). Please place this number in the right corner of all sheets of the development plan, landscape plan, NPPO, and any other associated sheets.

5. DS 2-01.3.4.C The project location map shall include the following:
Section, township, and range will be labeled.

6. DS 2-01.3.7.A..6 If a DSMR is approved for this project, please add the DSMR number, date of approval, what the DSMR is for and any conditions of approval on the development plan (DP)
If a DDO is approved for this project, please add the DDO number, date of approval, what the DDO is for and any conditions of approval on the development plan (DP)

7. DS 2-01.3.8.B All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

There is a 9' easement located along the east side of the property which must be addressed as per above. The building appears to be built over the easement.

8. DS 2-01.3.8.C The following information regarding existing public right-of-way adjacent to shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

This site must be designed as to incorporate the future widening of the intersection of Glenn and 1st Ave. The 1st Ave side as indicated has not taken into account the intersection widening to a width of 75' half right of way with the required taper.

Clearly indicate the location of the future right of way and the future curb location on the site plan.

The location of the future sight visibility triangles will be affected by the above.

On the site plan clearly indicate the location of the landscape buffer.

9. DS 2-01.3.9.F On the site plan clearly indicate the zoning classifications of the adjacent properties.

10. DS 2-01.3.9.H.5.d Bicycle parking provided on the DP does not meet the requirements of revised DS (Development Standard) 2-09. Per DS 2-09.4.1 Class 2 bicycle parking facilities will be located no more than fifty (50) feet from the main building entrance(s) and will be along the front side of the building as well as along other sides of the building that has an entrance. Reviewer is assuming a DSMR will be applied for.

11. DS 2-01.3.9.O The required building setback along the east property line is 1 ½ times the height of the buliding wall. A setback of 2.17' does not meet this requirement. A Design Development Option (DDO) variance will be required to be completed and approved. Provide wall height of the east elevation of the building in order to complete comments for the variance.

12. DS 2-01.3.9.W The location of the monument sign along Glenn is located within the right of way, either a TRE will be required or relocate the sign. The monument sign on 1st Ave is located within the future right of way. Provide a note on the plan stating the upon the widening of 1st Ave the sign will be removed or relocated at no expence to the City of Tucson.

13. Additional comments may apply based on changes to to the plan and responces to above comments.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\developmentplan\D10-0043dp.doc


01/10/2011

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
01/11/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

January 11, 2011

David Little
The WLB Group
4444 E. Broadway Blvd.
Tucson, Arizona 85711

Subject: D10-0043 QUIKTRIP STORE 1454 Development Package

Dear David:

Your submittal of December 8, 2010 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 8 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

8 Copies Revised Development Package (Fire, Zoning HC, Wastewater, Engineering, Landscape, Zoning, Traffic, PDSD)

2 Copies Drainage Report (Engineering, PDSD)

2 Copies Geotechnical Report (Engineering, PDSD)

2 Copies SWPPP (Engineering, PDSD)

1 Check Made out to "Pima County Treasurer" for $100.00 (Wastewater)

Should you have any questions, please call me at 837-4893.

Sincerely,



John Williams
Planning Technician

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/

Via fax: (520) 881-7492
01/11/2011 JOSE ORTIZ COT NON-DSD TRAFFIC Approv-Cond January 10, 2011
ACTIVITY NUMBER: D10-0043
PROJECT NAME: QT Store 1454
PROJECT ADDRESS: 1st/Glenn
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering recommends a conditional approval of the Development Plan. The following items must be revised or added to the development plan. Include a response letter with the next submittal that states how all comments have been addressed.

1. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.

2. Identify the location of the future right of way along 1st Avenue and Glenn Street.

3. The proposed drainage in the right of way will need to be reviewed by Steve Tineo to verify that the proposed drainage design is acceptable to TDOT-Engineering.


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
12/08/2010 RONALD BROWN ADA REVIEW Passed
12/08/2010 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/09/2010 DAVID MANN COT NON-DSD FIRE Denied Fire Comments:

Sheet C150

1. Please indicate existing fire hydrant location(s), with dimensions to buildings and/or property lines. Refer to City of Tucson amendments to the 2006 International Fire Code (section 508) for spacing and location requirements.

2. Fire sprinklers may be required. Fire flow calculation area exceeds 3600 sq. ft. Refer to 2006 IFC, appendix B,Section B104, B105.