Permit Number: D10-0042
Parcel: 116206350

Address:
125 S LINDA AV

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D10-0042
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
02/28/2011 PAUL MACHADO ENGINEERING REVIEW Approv-Cond Development package approval is dependant on extent of the proposed off-site improvements shown on plans and the issuance of a permit to penetrate the ex. bank protection of the Santa Cruz Wash by the PCFCD.
02/28/2011 PAUL MACHADO ENGINEERING REVIEW Approv-Cond NO FEMA Floodplain per LOMR 11-09-1389A. Property has been removed from the SFHA therefore no FUP or ELCERTS are required. JG 03/02/12
03/01/2011 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: New Armory Building
Development Package (3rd Review)
D10-0042

TRANSMITTAL DATE: March 1, 2011

DUE DATE: March 10, 2011

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Zoning Review Section conditionally approves the development package for this project, subject to the following changes on the sign-off copies. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development plan to verify that those changes do not affect any zoning requirements

1. D.S. 2-01.3.8.B The "30' RECLAIMED WATER ESMT (TO BE ABANDONED)" will need to be abandoned prior to approval of the development package. Provide the recordation information, docket and page, on the plan.

2. D.S. 2-01.3.9.E As this project proposes a change to the property boundary Zoning cannot approve the development package until the final plat has been revised and approved.

3. D.S. 2-01.3.9.L Provide the docket and page for the proposed "RECLAIMED WATER ESMT." on the plan. Provide the recordation information, docket and page, on the plan.

4. D.S. 2-01.3.9.L Provide written documentation from Tucson Water that allows the proposed improvements, shown at the northeast corner of the building, to be constructed within the reclaimed water easement.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D10-0042
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan.
03/03/2011 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approved MICHAEL GRITZUK, P.E. PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


March 2, 2011

To: CARL BUETER
CORNERSTONE ENVIRONMENTAL

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


From: Tom Porter, Sr CEA., PCRWRD Checked by_______

Subject: SENIOR HOUSING GROUP
NEW ARMORY BUILDING
Development Plan – 3rd Submittal
D10-0042

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
The Pima County Regional Wastewater Reclamation Department hereby approves the above referenced submittal of the development plan as submitted.

If you have any questions about this review letter please call me @ the phone number below.

______________________________
Tom Porter, Sr. CEA, (520)740-6719 PCRWRD

cc: Chad Amateau, PE
Kristin Greene, PE, DLU Manager
DLU Project folder
03/04/2011 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond 1) Resolve any outstanding issues with the final plat and offsite improvements cited by other agencies.

2) Revise the landscape plans to specify Prosopis velutina in order to meet the mitigation requirements of LUC 3.8.6.2.C.
03/11/2011 JANE DUARTE COT NON-DSD PARKS & RECREATION Approv-Cond Conditional approval upon addressing other agency comments.

-Matt Flick
03/11/2011 MATT FLICK ZONING-DECISION LETTER REVIEW Completed COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

March 11, 2011

Carl Bueter, EIT
Cornerstone Environmental Group
17 W Wetmore Rd. # 310
Tucson, AZ 85705

Subject: D10-0042 NEW ARMORY BUILDING Development Package

Dear Mr. Bueter:

Your submittal of February 24, 2011 for the above project has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off:

1 Rolled blue line COMPLETE SET of the Development Package, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal). Please include applicable sheets from any other concurrent reviews.

1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

Additional black line copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your plans to the CDRC office for sign-off approval.

*** NOTICE *** PRIOR TO SUBMITTING TO CDRC, YOU WILL NEED TO TAKE THE PLANS TO PIMA COUNTY ADDRESSING FOR APPROVAL. WE WILL NEED THE APPROVAL IN WRITING (EMAIL IS OKAY) FROM ADDRESSING BEFORE CDRC CAN ACCEPT THE SUBMITTAL.

Plans will not be signed and released until the CDRC office has been notified by PC Addressing that all fees for this plan have been paid. The CDRC office will need this confirmation in writing.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html. BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4931.

Sincerely,

Matt Flick, PE
Project Manager

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/

Via fax: (520) 888-4804

_______________________________________________________________