Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D10-0037
Parcel: 10510252A

Address:
4262 N 1ST AV

Review Status: Completed

Review Details: DEVELOPMENT PLAN

Permit Number - D10-0037
Review Name: DEVELOPMENT PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2010 JWILLIA4 START PLANS SUBMITTED Completed
11/08/2010 JASON GREEN ENGINEERING REVIEW Denied DATE: November 8, 2010
SUBJECT: Sola Salon Development Plan- Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 4262 N 1st Ave, T13S R14E Sec19, Ward 3
REVIEWERS: Jason Green, CFM
ACTIVITY: D10-0037

SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the proposed development plan, A.S.P. Engineering Division does not recommend approval of the development plan at this time. The following items need to be addressed:

DEVELOPMENT PLAN:

1) DS Sec.2-05: Provide the last approved site plan (T08CM02057) that accurately shows the building location and square footage. The Tentative Plat submitted with old and revised building foot print should reflect the shell building site plan for the accurate foot print and calculations for the change. The overall site plan is required to be revised to correctly show the new dumpster location and loading zone locations, with maneuverability for stamp approval. Sheet A.S.P. can be used to clearly show dimensions and details for construction purposes; however the proposed development plan needs to include an Overall site plan of the entire site showing the new site layout for refuse and loading maneuverability.

2) DS Sec.2-05.2.1.C: Revise the development plan so that all lettering and dimensions are equivalent of twelve (0.12") point or greater in size. The purpose of this requirement is to assure that all lettering is legible when reviewed and will maintain that legibility when reproduced and photographically reduced (microfilmed) for record-keeping purposes.

3) DS Sec.2-05.2.1.K: The development plan number (D10-0037) must be added to the lower right hand corner of the plan.

4) DS Sec.2-05.2.1.O: Revise the A.S.P. sheet to clearly show the new location for the loading zones and refuse enclosure. Per the sheet it appears that the refuse enclosure is proposed over the loading zones. Per the LUC the loading zone can be dimensioned in front of the refuse enclosure but not over it, revise.

5) DS Sec.2-2-05.2.1.T: Revise the development plan document and Detail 1 to clearly label and dimension all construction details for the proposed refuse container and enclosure location. Refer to DS Sec.6-01 (draft Figure 3) for all required refuse enclosure dimensions and construction details. Refer to Environmental Services, Tony Teran (791-4183 or Tony.Teran@tucsonaz.gov) for further information.

6) DS Sec.2-2-05.2.1.T: Provide approval from Environmental Services for the new location and proposed refuse maneuverability. The new pick up location does not match the overall flow of the Master Plan Development for refuse truck flow direction.

GENERAL COMMENTS:

Please provide a revised development plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon resubmittal of the development plan review.

For any questions or to schedule meetings call me at 837-4929.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services
11/16/2010 JOE LINVILLE LANDSCAPE REVIEW Approved
11/17/2010 FRODRIG2 ENV SVCS REVIEW Approved Due Date Case Number Project Address
November 17, 2010 D10-0037 SALO SALON STUDIO
DEVELOPMENT PLAN

Comments: The proposed Development Plan for the SALO SALON STUDIO,
Case No. D10-0037, Located at 4262 N. 1st Avenue, Suite 130. The proposed
development meets the minimum requirements for the Environmental Services, Solid
Waste Disposal Standard 6-01.0 and is here Approved.


Environmental Services Department
Development Plan Review
Reviewer: Tony Teran
Office Phone (520) 837-3706
E-mail: Tony.Teran @tucsonaz.gov
11/18/2010 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Sola Salon Studio
Development Plan (1st Review)
D10-0037

TRANSMITTAL DATE: November 18, 2010

DUE DATE: December 01, 2010

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development package. If, at the end of that time, the development package has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is October 06, 2011.

2. This development plan revision was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the area of change only.

3. Provide a development plan that meets the requirements of D.S. 2-05.0 and is clearly readable.

4. D.S. 2-05.2.1.H The north arrow, contour interval, and scale should be placed together on each sheet, preferably in the upper right corner of the plat.

5. D.S. 2-05.2.1.K The following relevant case numbers shall be listed in the lower right corner, next to the title block; S05-207, C9-05-26 & C9-04-11.

6. D.S. 2-05.2.2.B.1 List as a general note: "EXISTING ZONING IS C-1".

7. D.S. 2-05.2.2.B.2 Provide the development plan number D10-0037 near the title block on all sheets.

8. D.S. 2-05.2.2.B.2 Provide a general note stating "SEE TENTATIVE PLAT/DEVELOPMENT PLAN S05-207 FOR ALL CONDITIONS RELATED TO REZONING CASE C9-04-11"

9. D.S. 2-05.2.2.B.3 List the proposed use on the plan. The use should be listed as shown in the LUC along with the development designator and any subject to sections.

10. D.S. 2-05.2.2.B.10 Add a general note stating that the project is designed to meet the overlay zone criteria: Sec. 2.8.3, Major Streets and Routes (MS&R) Setback Zone.

11. D.S. 2-05.2.2.B.11 List the gross area of the site by square footage and acreage.

12. D.S. 2-05.2.3.B All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated.

13. D.S. 2-05.2.4.B All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning bondaries clearly defined.

14. D.S. 2-05.2.4.O There appears to be and an additional loading space shown on the plan. If this is new loading space and appears to encroach into the dumpster enclosure. If this is an additional dumpster provide a new loading space calculation on this plan that includes the required and provided number of loading spaces for the entire site. See the revised S05-207 Tentative plat/development plan for the current loading space calculation.

15. Provide a note on the plan stating "SEE TENTATIVE PLAT/DEVELOPMENT PLAN S05-207 FOR ALL RELEVANT TENTATIVE PLAT /DEVELOPMENT PLAN CALCULATIONS

16. Depending on how the above comments are addressed addition comments may be forth coming.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D10-0037

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan..
11/19/2010 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

November 19, 2010

Mario Sanchez
Anderson Studio Architects
1643 N. Alvernon Way # 106
Tucson, Arizona 85712

Subject: D10-0037 SOLA SALON STUDIO Development Plan

Dear Mario:

Your submittal of October 29, 2010 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 3 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

3 Copies Revised Development Plan (Engineering, Zoning, PDSD)

2 Copies Last Approved Site Plan - T08CM02057 (Engineering, PDSD)


Should you have any questions, please call me at 837-4917.


Sincerely,




John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: N/A
Sent to: Mario@Andersonstudioarchitects.com