Permit Number: D10-0035
Parcel: 125041120

Address:
2000 E 1ST ST

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D10-0035
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2011 JWILLIA4 DESIGN EXAMINER REVIEW Denied D10-0035 1st Street & Norris Avenue: Development Plan
January 3, 2011

Design Examiner & Adam Smith's Comments


1. Correct Section F. Management of Common Properties to read as follows:

"1F. The subdivision will provide…the homeowner's association or joint and several liability…with the Development Standards."

2. Delete reference 3F in Section F. Management of Common Properties as there is no note provided.

3. Add a parenthesis at the end of the title for "Section H. Open Space notes"

4. Section H, Subsection 5 - delete "minimum"

5. Make the following changes to the Development Plan Keynotes section as follows:

Note #19 - "grill"
Note #23 - delete "(minimum provided)"
Note #24 - "Pre-manufactured playground equipment to be determined"

6. Please describe your proposed screening privacy mitigation strategy between the proposed 2-story and the residence adjacent to the project site to the east.
01/04/2011 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied ADDRESSING REVIEW
201 N STONE AVE, 2ND FLOOR
TUCSON, ARIZONA 85701-1207
PHONE: (520) 740-6800





TO: CITY PLANNING
FROM: ADDRESSING REVIEW
SUBJECT: D10-0035 S.E.C. 1ST ST & NORRIS AVE
DATE: JANUARY 4, 2011

The above referenced Project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Per letter dated 10-27-2010: Include the section, township and range in all Title Blocks.
01/04/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

January 4, 2011

Gene Goldstein
Bramic Design Group
6255 N. Camino Pimeria Alta # 136
Tucson, Arizona 85718

Subject: D10-0035 1st STREET & NORRIS AVENUE Development Plan

Dear Gene:

Your submittal of October 7, 2010 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 8 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

8 Copies Revised Development Plan (Zoning, Landscape, Engineering, Wastewater, Design Examiner (2), Addressing, PDSD)

6 Copies Revised Landscape Plan (Zoning, Landscape, Engineering, Design Examiner (2), PDSD)

2 Copies Revised Drainage Statement (Engineering, PDSD)

2 Copies Approved Pima County Combo Request (Zoning, PDSD)

1 Check Made out to "Pima County Treasurer" for $39.00 (Wastewater)

1 CD Full Digital Set of Plans and Elevations on 300dpi Tiff CD (PDSD)


Should you have any questions, please call me at 837-4893.

Sincerely,


John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via Email
12/02/2010 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/06/2010 JOSE ORTIZ COT NON-DSD TRAFFIC Approv-Cond A private improvement agreement (PIA) may be necessary for the proposed work to be performed within the alleyway/Right of Way. An approved development plan is required prior to applying for a PIA. Contact the Richard Leigh or Thad Harvison of TDOT-Permits and Codes for additional PIA information at 791-5100.

If you have any questions, I can be reached at 837-6730 or Jose.Ortiz@tucsonaz.gov
12/10/2010 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved CDRC Review
Planning and Development Services Dept., Community Planning Review
D10-0035, 1st Street & Norris Ave., 2nd submittal
Comments Due: 11/4/10
Comments Submitted: 1/3/11

Items reviewed: Development Plan, Landscape Plan, compact disc with photos of site and surrounding neighborhood area


Comments:

The plans are approved. No resubmittal is required.

Reviewed by: J. Hershenhorn, 12/9/10


F:\Shardir\UPDfiles\Development Review\CASE_REVIEW\CDRC\2010 Cases\D10-0035a.doc
12/15/2010 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Denied PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
MICHAEL GRITZUK, P.E. PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135


December 14, 2010

To: GENE GOLDSTEIN
BRAMIC DESIGN GROUP

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

__________________________
Reviewed by: Chad Amateau, P.E., Civil Engineer PCRWRD

Subject: S.E.C. 1ST ST. & NORRIS AVE.
Dev. Plan – 2nd Submittal
D10-0035

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer collection lines for the above-referenced project. The following comments are offered for your use:
Show how the new building will be sewered. Also show how the existing buildings are sewered. The symbols for existing and proposed sewers should be shown in the Legend.
Call out the rim and invert elevations for the existing public sewer manholes on plan.

The submitted plans are not signed and sealed. Make sure that the plans submitted for the third review are signed and sealed.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the third(3rd ) submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions about this review letter please call me @ the phone number below.
______________________________
Tom Porter, Sr. CEA, (520)740-6719 PCRWRD

cc: Chad Amateau, PE
Kristin Greene, PE, DLU Manager
DLU Project folder
12/20/2010 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Fences or walls constructed in a single continuous line shall extend into a street landscape border no more than the actual width of the fence or wall. Where a fence or wall incorporates offsets or similar design features, a screen may extend a maximum of three (3) feet into the street landscape border. Revise the plans address the screen wall location requirements along Norris Ave.

2) Revise the plans to meet the 50% vegetative coverage requirements for the Norris Ave. street landscape border. LUC 3.7.2.4.A.5
12/20/2010 RONALD BROWN ZONING HC REVIEW Approved
12/22/2010 FRODRIG2 ENV SVCS REVIEW Approved Date Case Number Project Address
December 22, 2010 D10-0035 1st Street & Norris Avenue
DEVELOPMENT PLAN

Comments: The proposed Development Plan for the 1st Street & Norris Avenue,
Case No.D10-0035. Meets the minimum requirements for the Environmental
Services, Solid Waste Disposal and Recycle Materials Standard 6-01, and is
Approved.


Environmental Services Department
Development Plan Review
Reviewer: Tony Teran
Office Phone (520) 837-3706
E-mail: Tony.Teran @tucsonaz.gov
12/27/2010 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: 1st Street and Norris Avenue
Development Package (2nd Review)
D10-0035

TRANSMITTAL DATE: December 27, 2010

DUE DATE: January 03, 2011

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development package. If, at the end of that time, the development package has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is October 06, 2011.

2. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the entire site.

3. The requested documents were not provided with this submittal. This project comprises two (2) parcels and as a structure is proposed to be built across the property boundary the parcels must be combined. Provide a copy of the approved Pima County Combination Request form with your next submittal.

The Following comments are based on Development Standard 2-01.0 & LUC Section 3.6.1.

Until the Board of Adjustment for Variance has been approved Zoning cannot approve the development plan. If approved provide the following information on the plan; Board of Adjustment Number, Date of Approval, What was Approved, and any conditions of approval.

1. D.S. 2-01.3.9.H.5.a & LUC Section 3.6.1.5.F.2 Per LUC Section 3.6.1.5.F.2 An alley abutting an existing development shall not be used for parking access. That said a Board of Adjustment for Variance is required for the alley access to the proposed garages.

2. D.S. 2-01.3.9.H.5.a The proposed provided vehicle parking does not meet the requirement of LUC Section 3.3.4. RESIDENTIAL USE GROUP, Multifamily Dwellings 0-70 units/acre. Based on the number of bedrooms in each unit ten (10) vehicle parking spaces area required, eight (8) provided. A Board of Adjustment for Variance is required to reduce the number of vehicle parking spaces.

3. D.S. 2-01.3.9.O & LUC Section 3.6.1.5.C.1 As this is full code compliance for the entire site provide perimeter yard setback dimension from all existing structures along the east property line. It appears that the two (2) existing structures will not meet perimeter yard setbacks and will require a Board of Adjustment for Variance.

4. D.S. 2-01.3.9.O & LUC Section 3.6.1.5.C.1 The proposed 9'-0" perimeter yard setback shown from the propose garage does not meet the requirements of LUC 3.2.6.4. The minimum perimeter yard for the proposed project is based on the development designator FLD-6, Perimeter Yard Indicator "BB" adjacent to R-2 zoned property is 10 or ¾ of the exterior building wall, which ever is greatest. A Board of Adjustment for Variance is required.

5. D.S. 2-01.3.9.O & LUC Section 3.6.1.5.C.1 There is a cross section call out on sheet 1 near the east side of the proposed "NEW SINGLE FAMILY UNIT" that calls out 1 of 1, there is no cross section on sheet 1.

Depending on how the above comments are addressed addition comments may be forth coming.
If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D10-0035

4. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan, copy of the approved Pima County Combination Request form.
12/28/2010 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: December 28, 2010
SUBJECT: Development Plan Review
TO: Bramic Design Group
LOCATION: 899 N Wilmot Rd, T14S, R14E, Section 12, Ward 6
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: D10-0035 (Second Review)


RESUBMITTAL REQUIRED: Development Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed development plan for the above referenced property. Engineering Division does not recommend approval of the development plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the development plan.

Development Plan:

1. Per 2-05.2.1.G.2 - Per Development Standard, brief legal description is to be identified within title block.
Comment: Per legal description, it appears two lots are included in development. Appropriate documentation is to be submitted to show lots as one.
2. Per 2-05.2.1.J - Please provide legend that shows and describes all symbols used in the drawing.
Comment: Include all lines and symbols in legend.
3. Per 2-05.2.1.K - Verify that any applicable rezoning, annexation, or subdivision case numbers are listed in the lower right hand corner, next to the title block.
Comments: Include lot combination and/or variance numbers.
4. Per 2-05.2.2.C.1.b.- Within Drainage Note 2, revise note to add read "drainage" prior to "plan".
Comment: Add period (.) following sentence.
5. DS Sec.2-02.2.3.B - Verify that all easements have been drawn on the plan; be sure to include recordation information, location, width, and purpose of easement. More specifically, verify that there are no easements located within area of proposed addition to building.
Comment: Standard comment to remain.
6. DS Sec.2-02.2.3.E - Indicate the ground elevation on site based on City of Tucson Datum (indicate City of Tucson field book number and page). DS Sec.2-02.2.3.E.1 - For land less than one (1) percent, contour lines shall be drawn at intervals of not more than one (1) foot. DS Sec.2-02.2.3.E.2 - For land that slopes between approximately one (1) percent and five (5) percent, , contour lines shall be drawn at intervals of not more than two (1) feet.
Comment: Include book and page as previously requested and include contours.
7. DS Sec.2-02.2.4.E -H - Provide drainage statement and indicate all proposed ground elevations at different points to provide reference to future grading and site drainage.
18 DS Sec.2-02.2.4.R - Label existing and future sight visibility triangles
Comment: Far side SVT along Norris Ave should be 110'. Include SVT's along 1st Street.
19.DS Sec.2-02.2.4.S.- Show fire circulation, including accessibility and vehicle maneuverability.
20.DS Sec.2-02.2.4.T Show refuse collection area, including location of dumpsters, screening locations, size, materials, and vehicle maneuverability, fully dimensioned.
Comments: Include approval from Environmental Services for size, number and type of refuse containers being proposed.
8. Verify that keynotes are accurately identified within plan.
1. Keynote 2: Indicate COT Standard Detail number and/or reference detail sheet number.
2. Check Keynote 4: Indicate COT Standard Detail number and/or reference detail sheet number.
3. Keynote 7: Reference detail and add sheet number (Example: See Detail # on page X).
4. Keynote 11: Verify if slab is correct, should it be "sidewalk"? Please clarify and provide width and type.
5. Keynote 14: Revise 4 ft to 4' 0" to stay consistent with dimension representation used throughout remainder of the plan.
6. Keynote 15: Fill in detail ? and sheet 2 of?, with appropriate information. Provide height of fence.
7. Keynote 21: Indicate COT Standard Detail number and/or reference detail sheet number.
8. Keynote 22: Indicate COT Standard Detail number and/or reference detail sheet number.
9. Keynote 28: Revise SVT 20' X 125' to 20' X 110'.
9. Any alley abutting an existing development is not to be used for access to parking.
10. Additional Comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez, CFM
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax