Permit Number: D10-0027
Parcel: 116193770

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D10-0027
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2011 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/22/2011 FRODRIG2 ENV SVCS REVIEW Approved Date Case Number Project Address
March 21, 2011 D10-0027 Western Archeological and
Conservation Center
DEVELOPMENT PLAN

Comments: The revised Development Plans for the Western Archeological and Conservation
Center, Case No.D10-0027, meet the minimum requirements for the
Environmental Services, Solid Waste and Recycle Disposal Standard 6-01.
Therefore, the plans for this proposed Development are approved by Environmental
Services.


Environmental Services Department
Development Plan Review
Reviewer: Tony Teran
Office Phone (520) 837-3706
E-mail: Tony.Teran @tucsonaz.gov
03/25/2011 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

D10-0027 Western Archaeological Conserv

() Tentative Plat
(X) Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other - Elevations

CROSS REFERENCE: D10-0023

NEIGHBORHOOD PLAN: PAD-4

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: March 31, 2011

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an FLD, No Comment
() Proposal Complies with PAD-4 (Rezoning Conditions)
() RCP Proposal Complies With Plan Policies
() See Additional Comments Attached
(X) No Additional Comments - Complies With Planning Comments Submitted on: 3/07/2011







REVIEWER: msp l 791-5505 DATE:3/23/11
03/29/2011 JOE LINVILLE LANDSCAPE REVIEW Approved
03/29/2011 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Western Archaeological Conserv..
Development Package (2nd Review)
D10-0027

TRANSMITTAL DATE: March 29, 2011

DUE DATE: March 31, 2011

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development package. If, at the end of that time, the development package has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is August 16, 2011

2. This comment was not fully addressed. Per LUC Table 3.3.7-I the minimum "E" Curb Length for 0 degree parking is 23'. Based on 23' for each parallel vehicle parking space a total of 23 x 4 = 92' is required, only 87' has been provided. D.S. 2-01.3.9.H.5.a A typical parking space detail shall be provided for both standard parking spaces and for the proposed parallel parking spaces. Clearly indicate how the proposed parallel vehicle parking spaces meet the required Curb length of 23'.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D10-0027

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan.


CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Western Archaeological Conserv..
Development Package (2nd Review)
T11BU00234

TRANSMITTAL DATE: March 29, 2011

DUE DATE: March 31, 2011


GRADING PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning cannot approve the grading plan until the development package has been approved.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
03/31/2011 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

March 31, 2011

Tri Miller
Rick Engineering Company, Inc.
3945 E. Fort Lowell Rd. # 111
Tucson, Arizona 85712

Subject: D10-0027 WESTERN ARCHAEOLOGICAL Development Package

Dear Tri:

Your submittal of August 17, 2010 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 2 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

2 Copies Revised Development Package (Zoning, PDSD)


Should you have any questions, please call me at 837-4893.

Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.tucsonaz.gov/dsd/

Via fax: (520) 322-6956
03/31/2011 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved TO: RICK Engineering, Tri Miller, P.E., Paul Iezzi, P.E.
REVIEWER: Elizabeth Leibold, PE
SUBJECT: Western Archeological Conservation Center Development Package Engineering resubmittal
ADDRESS: 251 N Commerce Park Loop
LOCATION: T14S R13E Sec11
FLOODPLAIN STATUS: X-unshaded & X-shaded zones, 2226K
REZONING CASE: C9-07-14, PAD-4
CASE NUMBER: D10-0027, T11BU00234

SUMMARY: A resubmittal package was submitted for the proposed parking improvements for Western Archeological Conservation Center Development Package. Engineering Division of Planning & Development Services Department has received and reviewed the Development Package and recommends approval of the Development Package with the following conditions to be applied for the grading permit to be completed during grading construction.

GRADING PERMIT CONDITIONS:
The following 14 conditions apply to grading permit T11BU00234:
1) Call for SWPPP inspection and Grading Pre-construction meeting. For a PDSD Engineering Inspections, call IVR (740-6970), or schedule with a Customer Service Representative at the Planning & Development Services Department, or contact PDSD Engineering at 837-4888.
2) For inspection purposes, post City of Tucson's "AZPDES - Posting Requirements" green sheet, or the NOI at construction entrance of site, at beginning of construction activities, and maintain this posted document throughout project construction.
3) A copy of the approved plans, permits, and other documents shall be kept at the site at all times, until final grading approval. These documents are for onsite finish grading construction for redesigned parking area, utility infrastructure, private paving, drainage improvements, and landscaping associated with Development Package D10-0027 (sealed 3-16-11 Bruce Paton, P.E.).
4) SWPPP measures shall be maintained and updated throughout project until final grading approval. Sequential list of grading construction activities for this project shall be updated and provide for installation of SWPPP control measures at start of project prior to clearing and rough grading of this site, and removal or interim controls once all permanent controls are in place. All Operators shall be identified and have separate certification statements. For the Owner/Operator Certification Statements, provide name and signature for the Operators with each certification statement. Assure these certifications are available on-site. List of contractors and subcontractors shall be filled out at commencement of grading construction activity and updated on site and kept with SWPP documents.
5) Operator shall report to ADEQ any noncompliance (including spills) which may endanger human health or the environment. Operator shall orally notify office listed below within 24 hours:
(a) Arizona Department of Environmental Quality
1110 W. Washington, 5th floor (5515B-1)
Phoenix, AZ 85007
Office: 602-771-4466; Fax 602-771-4505
6) Receiving waters is unnamed tributary which connects to Santa Cruz River located quarter mile downstream of project.
7) Stabilized entrances shall be maintained at all active access entrances. Use of water trucks or other dust controls shall be utilized, and construction entrances shall be maintained to minimize sedimentation, dust issues, and tracking onto public streets.
8) Stormwater shall be prevented from entering and possibly causing ponding/infiltration within the landfill boundary.
9) No storage of materials, no vehicular storage, no concrete wash out shall occur in water harvest areas.
10) There shall be no disturbance outside of these approved grading limits. Any grading outside of the grading limits requires separate grading permit or a submittal, review, and approval for separate permits.
11) Contractor is responsible to protect in place the existing sewer line; all work within this easement must be coordinated with Pima County Waste Water prior to any site construction.
12) Any revisions to Grading Plan must be reviewed by PDSD Engineering Engineer and may include discussion, details, or a revised grading plan/development package. Call PDSD Engineering at 791-5550 to discuss any revisions. If grading construction is expected to last longer than expiration date of grading permit, contact PDSD to renew/extend Grading Permit. If Final Grading Inspection has not been completed before Grading Permit expires, and permit has not been renewed, additional fees and reviews may be required. Requests for grading permit extensions may be submitted to Planning & Development Services Department (attn: Claudia Buford), prior to grading permit expiration date, for consideration of grading plan extension approval.
13) Permitee shall notify PDSD when grading operation is ready for final grading inspection. Final grading approval shall not be given until all work, including installation of all drainage improvements and their permanent protective devices, and all erosion control measures have been completed in accordance with approved grading plan and grading permit, and all conditions of permit are completed.
14) As-builts are required to be submitted under activity number T11BU00234 to PDSD permit clerks. Submittal will be reviewed and then if acceptable, a copy will be provided to PDSD Engineering Inspector for final grading inspections. For Grading Permit Project Completion documentation, submit: one copy of original grading plans, 2 copies of as-builts ("Final Revised Grading Plan"), letters of substantial completion.

If you have questions, call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department