Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: D10-0009
Parcel: 110113610

Address:
2480 N SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - DEV PLAN

Permit Number - D10-0009
Review Name: RESUBMITTAL - CDRC - DEV PLAN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2010 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
04/21/2010 JOSE ORTIZ COT NON-DSD TRAFFIC Denied April 21, 2010
ACTIVITY NUMBER: D10-0009
PROJECT NAME: Fry's Fuel Station # 131
PROJECT ADDRESS: 2480 N Swan Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Development Plan; therefore a revised Development Plan is required for re-submittal. The following items must be revised or added to the development plan. Include a response letter with the next submittal that states how all comments have been addressed.

1. The proposed median does not provide standard queue lengths for the left turn lane in either the northbound or southbound directions. Modification to the main entrance may need to be considered to obtain minimum queue lengths. Per the city's Pavement Marking Manual a minimum 100' taper and 110' queue lengths for the left turn lanes are required.
2. The modification of the existing main driveway will include striping to provide a right turn lane and left tun lane out of the Fry's shopping complex. A meeting can be scheduled to clarify the pavement marking layout.



If you have any questions, I can be reached at 837-6730 or Jose.Ortiz@tucsonaz.gov
04/22/2010 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Fry's Food & Drug #131 - Fuel Center
Development Package (2nd Review)
D10-0009

TRANSMITTAL DATE: April 22, 2010

DUE DATE: May 11, 2010

DEVELOPMENT PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 5.3.8.2, LUC, permits a maximum of one year from the date of application to obtain approval of a development package. If, at the end of that time, the development package has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this development plan is February 10, 2011

2. D.S. 2-01.3.9.H.5.a Based on the provided vehicle parking calculation, per LUC Section 3.3.5.6.A.1 Where the gross floor area of a shopping center is fifty thousand (50,000) square feet or more, the parking requirements are as follows. Motor Vehicle Spaces. One (1) space for each two hundred (200) square feet of GFA. 317,267 Sq. Ft. / 200 = 1,586 vehicle parking spaces required, 1,518 vehicle parking spaces provided. A Board of Adjustment for Variance is required for a reduction of 68 vehicle parking spaces. Contact Russlyn Wells for information in regards to the process for the Board of Adjustment at 520-837-4948 or email at Russlyn.Wells@tucsonaz.gov. If the Board of Adjustment is approved on the plan provide the Board of Adjustment number, date of approval, what was approved and any conditions of approval.

3. D.S. 2-01.3.9.R As a landscape area has been added along the striped area located north of the fuel canopy the pedestrian circulation/accessible route in this area is required to be a sidewalk, meeting the requires of D.S. 2-08.4.1 and 5.a.C. Recommend that the landscape buffer be expanded to include a sidewalk separated from the vehicle use area by a curb. This sidewalk can be flush with the pavement.

4. If applicable ensure all changes are made to the grading and landscape plans.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

Sshield1 on DS1/planning/New Development Package/ D10-0009
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan & copy of the last approved development plan or site plan.

CDRC TRANSMITTAL

TO: Planning and Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Fry's Food & Drug #131 - Fuel Center
Development Package (2nd Review)
D10-0009

TRANSMITTAL DATE: April 22, 2010

DUE DATE: May 11, 2010

GRADING PLAN COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning cannot approve the grading plan until the development package has been approved.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.com

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/29/2010 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Landscape area has been added within striped area located north of the canopy. The pedestrian circulation/accessible route is required to be a sidewalk. Revise site and landscape plans as necessary to comply with Zoning comment #3.

2. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape & grading plans.

3. The grading plan has been reviewed by the Landscape / NPPO Section but cannot approve the plan until all Engineering, comments, concerns, and appropriate revisions have been addressed
05/04/2010 RONALD BROWN ZONING HC REVIEW Denied AT SHEETS SP AND C-2
1. Please correlate sheets SP and C-2 to be the same design. Please show all ramps, detectable warnings and island cut areas on SP.
RESUBMITTAL COMMENTS
1A. PLEASE SHOW ALL REQUIRED DETECTABLE WARNINGS AND INDICATE RAMPS WITH AN ARROW AND DIRECTION OF SLOPE.

2. At the most Southerly marked crossing:
a. The south end of this crossing is reference by note 12 to COT 207. Detail 207 is for COT DOT use only and is strictly for accessibility in the public right of way. Please change reference to read ICC (ANSI) 117.1, Sections 406.12 and/or 406.14.
RESUBMITTAL COMMENTS: OK

Redesign all ramps with this reference to meet the ICC (ANSI) requirements.
The detectable warning need be only 2' deep in the direction of travel.
Where is the ramp taking the sidewalk down to be flush with the pavement?
RESUBMITTAL COMMENTS: ABOVE OK
2A. SHOW ALL THE RAMPS AND DETECTABLE WARNINGS ON PLANS 1/C2 AND SP
3. At the most northerly marked crossing:
a. This crossing is an extremely long crossing and directs physcially impared persons across an area at the end of the canopy where vehicle traffic is not direct and may be helter skelter creating a extra hazardous crossing area at this location.
b. Please provide a crossing island at the North end of the canopy in the middle of the shown marked crossing, to be as long as the canopy is wide. It may be flush with raised concrete curbs or raised as desired . If raised, please provide all required sidewalk/curb ramps. Insure that all required detectable warnings are in place regardless of elevation.
RESUBMITTAL COMMENTS:
3A. PLEASE MOVE THE ISLAND SOUTH TO A POSITION WHERE THE ACCESSIBLE ROUTE (MARKED CROSSING) IS IN THE MIDDLE OF THE ISLAND. PROVIDE ALL RAMPS AND DETECTABLE WARNINGS REQUIRED. VERIFY WITH ZONING THAT THIS ACCESSIBLE ROUTE MUST BE CONCRETE.

4. Where the new accessible route is connected to the existing accessible route to the main store entrance, there is no marked crossing at the PAAL in front of the store. Please provide a new marked crossing as required by section 406.12 and/or 406.14. Provide all required ramps and detectable warnings.
RESUBMITTAL COMMENTS:
4A. WHERE ARE THE RAMPS AND DETECTABLE WARNINGS AT BOTH ENDS OF THE MARKED CROSSING?

5. At the new marked crossing indicated at the North West corner of the Fry's building, for both ends of the crossing, please provide required sidewalk and/or curb ramps, proper slopes and detectable warnings as required by Sections 406.12 and 406.14.
RESUBMITTAL COMMENTS
5A. PLEASE SHOW THE RAMP AND DETECABLE WARNING REQUIRED AT THE SOUTH END OF THE MARKED CROSSING.

SHEET DP-1
6. At detail 7, please provide accessible parking plan exactly as design on the sheets SP and C-2. Gernic details are not acceptable.
RESUBMITTAL COMMENTS:
6A. A "VAN ACCESSIBLE" PARKING SPACE SPACE MAY BE 8' WIDE WITH AN 8' WIDE AISLE OR 11' WIDE WITH A 5' AISLE. THE NEWLY ADDED DETAIL 4/G1.6 IS NEITHER. PLEASE REVISE THIS DETAIL TO COMPLY WITH ICC (ANSI 117.1), SECTION 5, SECTION 502.2.

GENERAL COMMENTS
7. Please provide large scale details of each different ramp and or landing access ends and accessible parking layouts showing all critical accessibile requirements, slopes, dimensions, curbs, detectable warnings and access to the accessible route.
RESUBMITTAL COMMENTS:
7A. REFERENCE ALL ABOVE COMMENTS
END OF REVIEW
05/11/2010 LOREN MAKUS ENGINEERING REVIEW Denied May 11, 2010
D10-0009 Development Package
Fry's Food and Drug #131 Fuel Center

The Engineering Division doesn't recommend approval of the development plan/development package as submitted.

The development plan and grading plan must be revised to address the following:

1. The drainage scheme and petroleum product interceptor are acceptable. Provide additional construction details for the system. Clearly show the elements of the drainage facilities and indicate which elements are existing and which are proposed.

Loren Makus EIT
Senior Engineering Associate
05/11/2010 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

May 11, 2010

Bill Burke
Metro Architecture, LLC
4501 N. 22nd Street # 100
Phoenix, Arizona 85016

Subject: D10-0009 Fry's Food & Drug # 131 Fuel Center Development Package

Dear Bill:

Your submittal of February 11, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 6 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

6 Copies Revised Development Package (Traffic, Zoning, Landscape, Zoning HC Site, Engineering, PDSD)

2 Copies Copy of Last Approved DP or Site Plan (Zoning, PDSD)


Should you have any questions, please call me at 837-4917.


Sincerely,





John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (602) 532-7287